Dell E09J, E10J owner manual Replacing Rack Rails, Replace Both Storage Controllers Simultaneously

Page 35

h. Right-click the alerts for the temperature sensor and I/O modules, then click Acknowledge.

NOTE: The alerts may not appear immediately. If the alerts do not appear, wait 10 seconds and then click Refresh.

13.Clear the swap status for the temperature sensor and acknowledge the alert.

a.Click the Hardware tab.

b.In the Hardware tab navigation pane, expand the enclosure.

c.Select Temperature Sensors.

d.In the right pane, right-click the sensor, then click Request Swap Clear.

e.Click the Alerts tab.

f.Right-click the alert and select Acknowledge.

NOTE: The alert may not appear immediately. If the alert does not appear, wait 10 seconds and then click Refresh.

14.Shut down the other storage controller and repeat the previous steps.

Next steps

1.Use SupportAssist to send diagnostic data to Dell Technical Support Services.

Replace Both Storage Controllers Simultaneously

If you need to replace both storage controllers at the same time, contact Dell Technical Support Services for assistance.

Replacing Rack Rails

Rack rails are used to install the SCv2000/SCv2020 storage system into a rack.

Prerequisites

1.Use SupportAssist to send diagnostic data to Dell Technical Support Services.

2.Shut down the storage system using the Dell Storage Client.

About this task

Use this procedure to replace rack rails.

NOTE: Replacing rack rails must be performed during a scheduled maintenance window when the Storage Center system is unavailable to the network.

Steps

1.Make sure all of the cables are labeled.

2.Disconnect all of the cables from the storage system.

3.Remove the storage system from the rack rails.

4.Remove the rack rails from the rack.

5.Install the replacement rack rails in the rack.

6.Install the storage system in the rack rails.

7.Reconnect the cables to the storage system.

8.Start up the storage system.

Next steps

1.Use SupportAssist to send diagnostic data to Dell Technical Support Services.

Replacing SCv2000/SCv2020 Components

35

Image 35
Contents Dell Storage Center Page Contents SCv2000/SCv2020 Technical Specifications Troubleshooting SCv2000/SCv2020 ComponentsRelated Publications Revision HistoryAudience Contacting Dell Dell Enterprise Manager Administrator’s Guide SCv2000/SCv2020 Storage System Hardware SCv2000/SCv2020 Monitoring and DiagnosticsSCv2000 Front Panel View SCv2000/SCv2020 Back Panel View SCv2000/SCv2020 Back-Panel Features and IndicatorsSCv2000/SCv2020 Storage Controller Features and Indicators About the SCv2000/SCv2020 Storage System About the SCv2000/SCv2020 Storage System About the SCv2000/SCv2020 Storage System SCv2000/SCv2020 Storage Controller with SAS Front-End Ports SCv2000/SCv2020 Drives SCv2000/SCv2020 Drive IndicatorsAbout the SCv2000/SCv2020 Storage System Installation Safety Precautions Safety PrecautionsGeneral Safety Precautions Electrical Safety PrecautionsElectrostatic Discharge Precautions Shutting Down the Storage System Pre-Replacement ProceduresSending Diagnostic Data Using Dell SupportAssist Shutting Down a Storage ControllerReplacing the Front Bezel Replacing Power Supply/Cooling Fan ModulesIdentifying the Failed Power Supply Page Identifying the Failed Cooling Fan Rear View of the Enclosure Showing the Failed Cooling Fan Replacing a Power Supply/Cooling Fan ModuleRemoving a Power Supply/Cooling Fan Module Identifying the Failed Hard Drive Replacing Hard DrivesSCv2000/SCv2020 Storage System Drive Numbering Front View of the Enclosure Showing the Failed Hard Drive Replacing a Hard Drive Replacing a Hard DriveInstall Hard Drives in Storage System Replacing a Storage Controller Replacing the Storage Controller BatteryIdentify the Failed Storage Controller Replace a Single Storage Controller Replacing a Storage Controller Replace Both Storage Controllers in Succession Replacing a Storage Controller Replace Both Storage Controllers Simultaneously Replacing Rack RailsStart up the Storage System Post-Replacement ProceduresTroubleshooting Hard Drives Troubleshooting Power Supply/Cooling Fan ModulesTroubleshooting Storage Controllers Technical Specifications SCv2000/SCv2020 Technical SpecificationsSCv2000/SCv2020 Technical Specifications Hour SCv2000/SCv2020 Technical Specifications