Carrier 50PEC09-18 specifications A50-8380, Wshp Open Control

Page 29

 

 

 

 

RED

 

 

 

 

WHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRN

 

 

 

 

 

 

 

 

 

 

 

 

 

GRN

 

 

 

 

 

 

PINK

 

 

 

 

 

ORN

 

SPACE RH

 

SPACE CO2

 

YLW

 

 

 

SENSOR

 

SENSOR

 

 

 

BLU

 

+24vac

 

+24vac

 

RED

 

 

+

 

+

 

BLU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORN

 

 

 

 

 

4-20mA

 

4-20mA

 

 

 

 

 

BRN

-

 

-

 

 

 

 

 

 

 

 

 

 

 

PINK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIO

FIELD INSTALLED (OPTIONAL) – SEE NOTE 2

PINK

J1

 

J2

6

5

4

3

2

1

10

1

7

1

 

 

 

J4

8

7

6

5

4

3

2

1

J5

+ 24vac

Condensate

(DI-3/Dry Contact)

Overflow Switch

 

- Gnd

Fan (DO-1) (Fan On or Low Speed)

Aux Heat (DO-2)

Reversing Valve (DO-3)

Comp #2 (DO-4)

Comp #1 (DO-5)

Comp Status (DI-5) (If not installed, it must be connected to DO-5) LWT (Input 6)

SAT (LAT) (Input 7)

AO1 – Aux Reheat or Cond.

WTR. Loop Econ. (AO 1)

a50-8380

OA DAMPER (AO-2)

 

 

 

 

 

LEGEND

AI

 

 

 

Analog Input

AO

 

 

 

Analog Output

BI

 

 

 

Binary Input

BO

 

 

 

Binary Output

SPT

 

 

 

Space Temperature

 

 

 

 

 

 

 

 

 

Factory Wiring

 

 

 

 

 

 

 

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

NOTES:

1.Mount the water source heat pump controller in the equipment controls enclosure with at least two #6 x 1 in. self-tapping screws. Allow adequate clearance for wiring.

2.Verify sensor power and wiring requirements prior to making any terminations. Sen- sors requiring a separate isolated 24 vac power source will not utilize WSHP termi- nals J4-1, or 4.

29

J12

MSB LSB

9 0

1

2

9 0

1

8

 

8

2

7

 

3

7

3

6

4

 

6

4

5

 

 

5

 

MSTP Baud

Field Installed

Local Access Port

4

RED4

3

BLACK3

2

WHITE2

1

GREEN1

J13

 

1 2

J22

To

SPT PLUS

J11

1 2 3 4 5 6 7 8

DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION)

FAN SPEED (DO-7) (MED OR LOW)

FAN SPEED (DO-8) (HIGH OR FAN ON )

WSHP Open Inputs and Outputs Table

9600

19.2k

38.4k

76.8k

 

J17

 

 

 

SW3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

J14

 

 

 

 

 

 

 

 

N

4

3

2

1

J19

 

 

 

8

7

6

5

4

3

2

1

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J20

 

 

 

FIELD INSTALLED

 

 

INPUT/OUTPUT TYPE

 

 

 

 

 

 

 

 

 

 

SPT PLUS Sensor

 

 

Inputs

 

Shown

 

 

Space Temperature Sensor

 

 

Space Relative Humidity

Rnet Terminals (J1

To WSHPController

Indoor Air Quality

Condensate Switch

Stage 1 Compressor Status

RED

BLACK

WHITE

GREEN

Leaving Condenser Water Temperature

Supply Air Temperature

PART NUMBERS

TYPE OF I/O

CONNECTION

CHANNEL

PIN NUMBERS

DESIGNATION

 

 

SPS, SPPL, SPP

Communicating

J13, 1 - 4

Local Access Port

33ZCSENSRH-01

AI (4 - 20mA)

J4, 5 and 6

Analog Input 1

33ZCSENCO2

AI (4 -20mA)

J4, 2 and 3

Analog Input 2

N/A

BI (Dry Contacts)

J1, 2

Binary Input 3

N/A

BI (Dry Contacts)

J1, 10

Binary Input 5

10K Type II

AI (10K Thermistor)

J2, 1 and 2

Analog Input 6

33ZCSENSAT

AI (10K Thermistor)

J2, 3 and 4

Analog Input 7

FIELD INSTALLED

 

 

 

 

SPT PLUS Sensor

 

 

 

 

Shown

To WSHP Controller Rnet Terminals (J13)

RED

BLACK

WHITE

GREEN

 

+12V

Rnet-

Rnet+

Gnd

 

 

 

 

DB

 

 

 

 

 

 

5BT81BT4-012207

Install BT485 where device is located at the end of network segment only.

3)

 

 

 

Outputs

 

Modulating Valve (Auxiliary Heat/Water

Economizer)

+12V

Rnet-

Rnet+

Gnd

Outside Air Damper

Supply Fan On/Low Speed

(3 Speed Only)

Auxiliary Heat or 2-Position Water Loop Economizer

Reversing Valve (B or O Operation)

Compressor 2nd Stage

Compressor 1st Stage

Dehumidification Relay

Fan Speed Medium/Low (3 Speed Only)

Fan Speed High/Low (3 Speed Only)

*These inputs are configurable.

N/A

AO (0-10Vdc/2 - 10Vdc)

J2 4 and 5*

Analog Output 1

N/A

AO (0-10Vdc/2 - 10Vdc)

J22 1 and 2*

Analog Output 2

N/A

BO Relay (24VAC, 1A)

J1, 4*

Binary Output 1 (G)

N/A

BO Relay (24VAC, 1A)

J1, 5*

Binary Output 2

N/A

BO Relay (24VAC, 1A)

J1, 6*

Binary Output 3 (RV)

N/A

BO Relay (24VAC, 1A)

J1, 7

Binary Output 4 (Y2)

N/A

BO Relay (24VAC, 1A)

J1, 8

Binary Output 5 (Y1)

N/A

BO Relay (24VAC, 1A)

J11, 7 and 8 (NO)

Binary Output 6

N/A

BO Relay (24VAC, 1A)

J11, 5 and 6 (NO)*

Binary Output 7

N/A

BO Relay (24VAC, 1A)

J11, 2 and 3 (NO)*

Binary Output 8

 

 

 

 

Fig. 29 — WSHP Open Control

Image 29
Contents Safety Considerations Contents50PEC Physical Data InstallationGeneral Water OUT OUTCondensate A50-833522.2 OD WaterA50-8337 A50-8338Damper Opening A50-833950PEC18 Bottom Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC18 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Right Hand Piping 50PEC18 Front Return Cabinet Dimensions Right Hand Piping A50-8345 50PEC09-15 Front Return Cabinet Dimensions Left Hand Piping50PEC18 Front Return Cabinet Dimensions Left Hand Piping A50-8347 Optional Autoflow Valve Motorized 50PEC09-15 Chassis Dimensions Front ReturnOptional Disconnect Box Autoflow Optional FusedOptional Motorized Water Valve Optional Autoflow50PEC18 Chassis Dimensions Front Return Mount Unit Wire Electrical Connections09-18 A50-8452A50-8327.eps Sensor, Water Coil Freeze Protection A50-8328Return Air Sensor Night Low Limit SwitchA50-8329 Blower Motor Wiring NLL PremierLink Controller Applications with Complete C Control A50-8355 8354 A50LWT 8353 Wshp Open Control A50-8380Electrical Data 50PEC Units Wire Low Voltage ConnectionsA50-7467tf A50-8441SPT Sensors Recommended Thermostat Wire SizesField-Supplied Sensors for Wshp Open Controller Rnet Wiring Specifications Install Supply and Return PipingRnet Wiring A50-8443Temporary Connection for Flushing System Piping PRE-START-UPMin Ambient Air Rated Ambient Air Max Ambient Air Air and Water LimitsMin Entering Air Rated Entering Air, dry bulb/wet bulb Max Entering Air, dry bulb/wet bulbWater Quality Guidelines Deluxe D Control Jumper Settings See , 20, Complete C Control Jumper Settings See , 18,DIP Switch Block S2 Accessory 1 Relay Options Field Selectable InputsSTART-UP DIP Switch Block S2 Accessory 2 Relay OptionsUnit Start-Up/Cooling Operating LimitsBACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM Coaxial Water Pressure DropAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Complete C and Deluxe D Board System Test Aquazone Deluxe D Control LED Indica Complete C Control LED Code and Fault DescriptionsService Gravity Flow Method Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Alarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Optimal StartTest Appendix a Wshp Screen Open ConfigurationService Point Name Password Editable Range Default Level Configuration ServiceAlarm High Alarm LimitPage Page Copyright 2009 Carrier Corporation II. START-UP 50PEC Unit START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8453 A50-8454