APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME
Configuration
→
Service
Configuration
POINT NAME | PASSWORD | EDITABLE | RANGE | DEFAULT | NOTES | |
LEVEL | ||||||
|
|
|
|
| ||
# of Fan Speeds |
| X | 1,2,3 | 3 | Used to set number of | |
| fan motor speeds | |||||
|
|
|
|
| ||
|
|
|
|
| When set to Fan On, G output is | |
|
|
|
|
| energized when ever any fan speed | |
G Output Type |
| X | Fan On/Fan Low | Fan On | is active (required for ECM and Fan | |
| control board). When set to Fan | |||||
|
|
|
|
| ||
|
|
|
|
| Low, output is only energized for | |
|
|
|
|
| Low Speed | |
Compressor Stages |
| X | One Stage/Two Stages | One Stage | Defines the number of | |
| stages of compression | |||||
|
|
|
|
| ||
Reversing Valve Type |
| X | O type output/B type output | O type | Determines reversing valve | |
| signal output type | |||||
|
|
|
|
| ||
Leaving Air Auxiliary |
| X | None | Determines Auxiliary | ||
Heat Type |
| Electric/Modulating HW | Reheat Coil Type | |||
|
|
| ||||
Entering Air Water |
| X | None | Determines Entering Air | ||
Economizer Type |
| Economizer Coil Type | ||||
|
|
|
| |||
| X | Normally Closed/Normally Open | Normally | Determines type of | ||
Valve Type |
| Closed | water valve used | |||
|
|
| ||||
Modulating Water |
| X | Normally Closed/Normally Open | Normally | Determines type of modulating | |
Valve Type |
| Closed | water valve used | |||
|
|
| ||||
Ventilation Damper |
| X | None | Determines Type of ventilation | ||
Type |
| damper control to be used | ||||
|
|
|
| |||
|
|
|
|
| Used to determine ventilation | |
Damper Actuator Type |
| X | damper output signal range | |||
|
|
|
|
| (closed - open) | |
Humidity Sensor |
| X | None/Installed | None | Set to Installed if Humidity | |
| sensor is present | |||||
|
|
|
|
| ||
Factory Dehumidifica- | Admin Password |
|
|
| Set to Installed if | |
level access only | X | None/Installed | None | dehumidification reheat coil | ||
tion Reheat Coil |
|
|
|
| is present | |
|
|
|
|
| ||
Occupancy |
| X | Occupied Open/Occupied Closed | Occupied | Used to determine external occu- | |
Input Logic |
| CLOSED | pancy switch contact occupied state | |||
|
|
| ||||
Condensate Switch |
| X | 5 - 600 seconds | 10 sec | Delay before equipment alarms on | |
Alarm Delay |
| high condensate level | ||||
|
|
|
| |||
Condensate Switch |
| X | Alarm OPEN/Alarm CLOSED | Alarm | Determine Alarm state of | |
Alarm State |
| CLOSED | condensate switch input | |||
|
|
| ||||
Minimum Condenser |
|
| 25 - 60 ° F | 60 ° F | Determines the minimum | |
Water Temperature in |
| X | acceptable water loop temperature | |||
Heating |
|
|
|
| to start heating | |
Maximum Condenser |
|
| 65 - 100 ° F | 90 ° F | Determines the maximum | |
Water Temperature in |
| X | acceptable water loop temperature | |||
Heating |
|
|
|
| to start heating | |
Minimum Condenser |
|
| 30 - 60 ° F | 60 ° F | Determines the minimum | |
Water Temperature in |
| X | acceptable water loop temperature | |||
Cooling |
|
|
|
| to start cooling | |
Maximum Condenser |
|
| 85 - 120 ° F | 95 ° F | Determines the maximum | |
Water Temperature in |
| X | acceptable water loop temperature | |||
Cooling |
|
|
|
| to start cooling | |
IAQ sensor |
| X | 0 - 5 ma | 4 ma | Minimum output current (mA) | |
minimum input |
| for IAQ sensor | ||||
|
|
|
| |||
IAQ sensor |
| X | 5 - 20 ma | 20 ma | Maximum output current (mA) for | |
maximum input |
| IAQ sensor | ||||
|
|
|
| |||
IAQ sensor |
| X | 0 - 9999 ppm | 0 ppm | Corresponding value in ppm for | |
minimum output |
| minimum output current | ||||
|
|
|
| |||
IAQ sensor |
| X | 0 - 9999 ppm | 2000 ppm | Corresponding value in ppm for | |
maximum output |
| maximum output current | ||||
|
|
|
|
| LEGEND |
BAS | — Building Automation System |
DCV | — Demand Controlled Ventilation |
IAQ | — Indoor Air Quality |
OAT | — Outdoor Air Temperature |
RH | — Relative Humidity |
SAT | — Supply Air Temperature |
SPT | — Space Temperature |
TPI | — Third Party Integration |