Carrier 50PEC09-18 Unit Start-Up with Wshp Open Controls, BACview6 Display Interface

Page 38

5.Slowly turn thermostat toward cooler position. Both fan and compressor should shut off when thermostat set point equals room temperature. Room temperature must be above 65 F for unit to shut off.

Unit Start-Up with WSHP Open Controls —

The WSHP Open is a multi-protocol (default BACnet*) con- troller with extensive features, flexible options and powerful capabilities. The unit comes from the factory pre-programmed and needs minimal set up to function in a BAS (Building Automation System) system or provide additional capabilities to Carrier's WSHP product line. Most settings on the controller have factory defaults set for ease of installation. There are a few settings that must be configured in the field and several settings that can be adjusted if required by unique job condi- tions. Refer to Appendix A — WSHP Open Screen Configura- tion. In order to configure the unit, a BACview6 display is required. See Fig. 36.

NOTE: If the WSHP Open control has lost its programming, all display pixels will be displayed on the SPT sensor. See the WSHP Third Party Integration Guide.

When the unit is OFF, the SPT sensor will indicate OFF. When power is applied, the SPT sensor will indicate tempera- ture in the space at 78 F.

To start-up a unit with WSHP Open controls:

1.To plug in the BACview6 handheld display into a SPT sensor, point the two ears on the connector up and tilt the bottom of the plug toward you. Insert the plug up into the SPT sensor while pushing the bottom of the plug away from you.

2.BACview6 should respond with "Establishing Connec- tion." The Home screen will then appear on the display showing operating mode and space temperature. Press any button to continue.

See Appendix A — WSHP Open Screen Configuration for the hierarchal structure of the WSHP Open controller. All functions of the controller can be set from the Home screen.

3.When the Login is requested, type 1111 and push the OK softkey. The Logout will then be displayed to indicate the password was accepted.

4.To set the Clock if it is not already displayed:

a.Select System Settings from the Home screen, then press Clockset.

b.Scroll to hour, minute and second using the arrow keys. Use the number keypad to set actual time.

c.Scroll to day, month and year using arrow keys. Use number keypad to set date.

5.To set Daylight Savings Time (DST):

a.Push the DST softkey. The display will indicate 02:00:060 which is equal to 2:00AM.

b.To program the beginning and end dates, scroll down to the beginning month and press the enter key. The softkeys (INCR and DECR) will activate to increment the month in either direction, Jan, Feb, March, etc.

c.Use number keys to select the day of month and year.

d.Push the OK softkey to finalize the data.

6.To view configuration settings:

a.Select the Config softkey.

b.Select the Service Config softkey. Scroll through the factory settings by using the up and down arrow keys. See below for factory settings.

Only the following settings will need to be checked.

# of Fan Speeds — This should be set to "1" for units with PSC motors and set to "3" for units with ECM motors.

Compressor Stages — This should be set to "1."

Factory Dehumidification Reheat Coil — This should be set to "none" unless the modulating hot water reheat option is supplied in the unit, then set to "installed."

The condenser water limit needs to be verified depending on design parameters and application, whether geothermal or boiler/tower.

7.To view unit configuration settings:

a.Select the Unit Configuration softkey, then select Unit.

b.Scroll through the unit settings by using the up and down arrow keys. Unit settings include:

Fan Mode: Default Continuous

Fan Delay:

Minimum SAT Cooling: Default 50 F

Maximum SAT Heating: Default 110 F

Filter Service Alarm: Must be set from 0 to 9999 hr

8.To set local schedules:

a.Select the Schedule softkey from the Configuration screen, then press enter.

Fig. 36 — BACview6 Display Interface

*Sponsored by ASHRAE (American Society of Heating, Refrigerat- ing and Air Conditioning Engineers).

38

Image 38
Contents Contents Safety Considerations50PEC Physical Data InstallationGeneral Condensate OUTWater OUT A50-8335A50-8337 Water22.2 OD A50-8338A50-8339 Damper Opening50PEC18 Bottom Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC18 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Right Hand Piping 50PEC18 Front Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Left Hand Piping A50-834550PEC18 Front Return Cabinet Dimensions Left Hand Piping A50-8347 50PEC09-15 Chassis Dimensions Front Return Optional Autoflow Valve MotorizedOptional Motorized Optional FusedOptional Disconnect Box Autoflow Water Valve Optional Autoflow50PEC18 Chassis Dimensions Front Return Wire Electrical Connections Mount UnitA50-8452 09-18A50-8327.eps A50-8328 Sensor, Water Coil Freeze ProtectionReturn Air Sensor Night Low Limit SwitchA50-8329 Blower Motor Wiring NLL PremierLink Controller Applications with Complete C Control A50-8355 A50 8354LWT 8353 A50-8380 Wshp Open ControlA50-7467tf Wire Low Voltage ConnectionsElectrical Data 50PEC Units A50-8441SPT Sensors Recommended Thermostat Wire SizesField-Supplied Sensors for Wshp Open Controller Rnet Wiring Install Supply and Return PipingRnet Wiring Specifications A50-8443PRE-START-UP Temporary Connection for Flushing System PipingMin Entering Air Rated Entering Air, dry bulb/wet bulb Air and Water LimitsMin Ambient Air Rated Ambient Air Max Ambient Air Max Entering Air, dry bulb/wet bulbWater Quality Guidelines DIP Switch Block S2 Accessory 1 Relay Options Complete C Control Jumper Settings See , 18,Deluxe D Control Jumper Settings See , 20, Field Selectable InputsUnit Start-Up/Cooling DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Operating LimitsUnit Start-Up with Wshp Open Controls BACview6 Display InterfaceCoaxial Water Pressure Drop GPMOperation Approximate Fluid Volume gal Per 100 ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Complete C and Deluxe D Board System Test Complete C Control LED Code and Fault Descriptions Aquazone Deluxe D Control LED IndicaService Gravity Flow Method Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Replacing the Wshp Open Controller’s BatTroubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate Status Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationOptimal Start ScheduleTest Appendix a Wshp Screen Open ConfigurationService Configuration Service Point Name Password Editable Range Default LevelHigh Alarm Limit AlarmPage Page Copyright 2009 Carrier Corporation 50PEC Unit START-UP Checklist II. START-UPA50-8453 Heating Cycle AnalysisCooling Cycle Analysis A50-8454