Carrier 50PEC09-18 specifications Contents, Safety Considerations

Page 1

AQUAZONE™ 50PEC09-18 Water Source Heat Pump Console Unit

with PURON® Refrigerant (R-410A)

Installation, Start-Up and Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2

GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33

Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2

Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 17

STORAGE

UNIT PROTECTION

Step 3 — Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Step 4 — Wire Electrical Connections . . . . . . . . . . 17

SUPPLY VOLTAGE

EXTERNAL LOOP POWER CONNECTION

230-V OPERATION

Step 5 — Wire Low Voltage Connections . . . . . . . 30

WATER FREEZE PROTECTION

ACCESSORY CONNECTIONS

WATER SOLENOID VALVES

OPTIONAL WALL-MOUNTED THERMOSTAT

OPTIONAL PREMIERLINK™ CONTROLLER

WSHP OPEN WIRING

Step 6 — Install Supply and Return Piping. . . . . . 32

SUPPLY AND RETURN HOSES

SUPPLY AND RETURN PIPING

Step 7 — Install Condensate Piping . . . . . . . . . . . . 33

PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-35

System Cleaning and Flushing . . . . . . . . . . . . . . . . 33

System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .36,37

Complete C Control Jumper Settings. . . . . . . . . . . 36

Complete C Control DIP Switches. . . . . . . . . . . . . . 36

Deluxe D Control Jumper Settings . . . . . . . . . . . . . 36

Deluxe D Control DIP Switches . . . . . . . . . . . . . . . . 36

Deluxe D Control Accessory

Relay Configurations . . . . . . . . . . . . . . . . . . . . . . . 37 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-40 Unit Start-Up/Cooling . . . . . . . . . . . . . . . . . . . . . . . . . 37 Operating Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Unit Start-Up/Heating . . . . . . . . . . . . . . . . . . . . . . . . . 37 Unit Start-Up with WSHP Open Controls. . . . . . . . 38 Flow Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . 40

Ground Coupled, Closed Loop and Plateframe Heat Exchanger Well Systems . . . . . . . . . . . . . . . 40

OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-43 Power Up Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Units with Aquazone Complete C Control. . . . . . . 40 Units with Aquazone Deluxe D Control . . . . . . . . . 40 Units with WSHP Open Multiple Protocol . . . . . . . 41

COMPLETE C AND DELUXE D BOARD SYSTEM TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . 43-45

Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

WSHP Open Test Mode . . . . . . . . . . . . . . . . . . . . . . . 44

Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Aquazone Deluxe D Control LED Indicators. . . . . 44

Page

SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45-47

Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

System Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Condensate Pans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Blower Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Safety Control Reset. . . . . . . . . . . . . . . . . . . . . . . . . . 46

Checking System Charge . . . . . . . . . . . . . . . . . . . . . 47

Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . 47

Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . 47

Replacing the WSHP Open Controller’s

Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . .47-49

Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

WSHP Open Controller. . . . . . . . . . . . . . . . . . . . . . . . 47

APPENDIX A — WSHP OPEN SCREEN CONFIGURATION. . . . . . . . . . . . . . . . . . . . . . . . .50-55

START-UP CHECKLIST. . . . . . . . . . . . . . . . . CL-1, CL-2

IMPORTANT: Read the entire instruction manual before starting installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func- tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau- tions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Improper installation, adjustment, alteration, service, mainte- nance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accesso- ries when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and applicable electrical codes for special installation requirements.

Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53500052-01

Printed in U.S.A.

Form 50PEC-2SI

Pg 1

7-09

Replaces: 50PEC-1SI

Image 1
Contents Safety Considerations ContentsGeneral Installation50PEC Physical Data Water OUT OUTCondensate A50-833522.2 OD WaterA50-8337 A50-8338Damper Opening A50-833950PEC18 Bottom Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC18 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Right Hand Piping 50PEC18 Front Return Cabinet Dimensions Right Hand Piping A50-8345 50PEC09-15 Front Return Cabinet Dimensions Left Hand Piping50PEC18 Front Return Cabinet Dimensions Left Hand Piping A50-8347 Optional Autoflow Valve Motorized 50PEC09-15 Chassis Dimensions Front ReturnOptional Disconnect Box Autoflow Optional FusedOptional Motorized Water Valve Optional Autoflow50PEC18 Chassis Dimensions Front Return Mount Unit Wire Electrical Connections09-18 A50-8452A50-8327.eps Sensor, Water Coil Freeze Protection A50-8328A50-8329 Night Low Limit SwitchReturn Air Sensor Blower Motor Wiring NLL PremierLink Controller Applications with Complete C Control A50-8355 8354 A50LWT 8353 Wshp Open Control A50-8380Electrical Data 50PEC Units Wire Low Voltage ConnectionsA50-7467tf A50-8441Field-Supplied Sensors for Wshp Open Controller Recommended Thermostat Wire SizesSPT Sensors Rnet Wiring Specifications Install Supply and Return PipingRnet Wiring A50-8443Temporary Connection for Flushing System Piping PRE-START-UPMin Ambient Air Rated Ambient Air Max Ambient Air Air and Water LimitsMin Entering Air Rated Entering Air, dry bulb/wet bulb Max Entering Air, dry bulb/wet bulbWater Quality Guidelines Deluxe D Control Jumper Settings See , 20, Complete C Control Jumper Settings See , 18,DIP Switch Block S2 Accessory 1 Relay Options Field Selectable InputsSTART-UP DIP Switch Block S2 Accessory 2 Relay OptionsUnit Start-Up/Cooling Operating LimitsBACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM Coaxial Water Pressure DropAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Complete C and Deluxe D Board System Test Aquazone Deluxe D Control LED Indica Complete C Control LED Code and Fault DescriptionsService Gravity Flow Method Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Alarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Optimal StartService Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceAlarm High Alarm LimitPage Page Copyright 2009 Carrier Corporation II. START-UP 50PEC Unit START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8453 A50-8454