Carrier 50PEC09-18 specifications Unit Does Not Operate

Page 49

Table 18 — Troubleshooting (cont)

 

FAULT

 

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Only Compressor Runs

 

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.

 

 

 

 

 

 

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in Test mode.

 

 

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR

 

 

 

 

 

 

contacts.

 

 

 

 

 

 

Check fan power enable relay operation (if present).

 

 

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

Unit Does Not Operate in

 

 

X

Reversing valve

Set for cooling demand and check 24-vac on RV coil and at control.

Cooling

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

operating engage and disengage RV coil voltage to push valve.

 

 

 

 

X

Thermostat setup

Check for ‘O’ RV setup not ‘B’.

 

 

 

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil.

Insufficient Capacity/

 

X

X

Dirty filter

Replace or clean.

Not Cooling or Heating

 

 

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Properly

 

 

 

 

 

heating

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

cooling

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

X

X

Leaky ductwork

Check supply and return-air temperatures at the unit and at distant

 

 

 

 

 

 

duct registers if significantly different, duct leaks are present.

 

 

 

X

X

Low refrigerant charge

Check superheat and subcooling.

 

 

 

X

X

Restricted metering device

Check superheat and subcooling. Replace.

 

 

 

 

X

Defective reversing valve

Perform RV touch test.

 

 

 

X

X

Thermostat improperly

Check location and for air drafts behind thermostat.

 

 

 

 

 

located

 

 

 

 

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

 

 

X

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

 

 

exchanger

 

 

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

heating

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

 

 

 

 

 

cooling

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

 

 

 

 

 

 

 

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture.

 

 

 

X

 

Air temperature out of range

Bring return-air temperature within design parameters.

 

 

 

 

 

in heating

 

 

 

 

 

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

 

 

exchanger

 

 

 

 

X

X

Unit overcharged

Check superheat and subcooling. Reweigh in charge.

 

 

 

X

X

Non-condensables in

Vacuum system and reweigh in charge.

 

 

 

 

 

system

 

 

 

 

X

X

Restricted metering device

Check superheat and subcooling. Replace.

Low Suction Pressure

 

X

 

Reduced water flow in

Check pump operation or water valve operation/setting.

 

 

 

 

 

heating

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

 

 

range

 

 

 

 

 

X

Reduced airflow in cooling

Check for dirty air filter and clean or replace.

 

 

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

High external static. Check duct design and downstream interference.

 

 

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering air temperature within design

 

 

 

 

 

 

parameters.

 

 

 

X

X

Insufficient charge

Check for refrigerant leaks.

Low Discharge Air

 

X

 

Too high airflow

Check blower.

Temperature in Heating

 

X

 

Poor performance

See ‘Insufficient Capacity’ above.

High Humidity

 

 

X

Too high airflow

Check blower.

 

 

 

 

X

Unit oversized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

LEGEND

 

 

 

 

FP

Freeze Protection

 

 

 

 

HP

High Pressure

 

 

 

 

LED — Light-Emitting Diode

 

 

 

 

LP

Low Pressure

 

 

 

 

RV

Reversing Valve

 

 

 

 

49

Image 49
Contents Safety Considerations ContentsGeneral Installation50PEC Physical Data Water OUT OUTCondensate A50-833522.2 OD WaterA50-8337 A50-8338Damper Opening A50-833950PEC18 Bottom Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC18 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Right Hand Piping 50PEC18 Front Return Cabinet Dimensions Right Hand Piping A50-8345 50PEC09-15 Front Return Cabinet Dimensions Left Hand Piping50PEC18 Front Return Cabinet Dimensions Left Hand Piping A50-8347 Optional Autoflow Valve Motorized 50PEC09-15 Chassis Dimensions Front ReturnOptional Disconnect Box Autoflow Optional FusedOptional Motorized Water Valve Optional Autoflow50PEC18 Chassis Dimensions Front Return Mount Unit Wire Electrical Connections09-18 A50-8452A50-8327.eps Sensor, Water Coil Freeze Protection A50-8328A50-8329 Night Low Limit SwitchReturn Air Sensor Blower Motor Wiring NLL PremierLink Controller Applications with Complete C Control A50-8355 8354 A50LWT 8353 Wshp Open Control A50-8380Electrical Data 50PEC Units Wire Low Voltage ConnectionsA50-7467tf A50-8441Field-Supplied Sensors for Wshp Open Controller Recommended Thermostat Wire SizesSPT Sensors Rnet Wiring Specifications Install Supply and Return PipingRnet Wiring A50-8443Temporary Connection for Flushing System Piping PRE-START-UPMin Ambient Air Rated Ambient Air Max Ambient Air Air and Water LimitsMin Entering Air Rated Entering Air, dry bulb/wet bulb Max Entering Air, dry bulb/wet bulbWater Quality Guidelines Deluxe D Control Jumper Settings See , 20, Complete C Control Jumper Settings See , 18,DIP Switch Block S2 Accessory 1 Relay Options Field Selectable InputsSTART-UP DIP Switch Block S2 Accessory 2 Relay OptionsUnit Start-Up/Cooling Operating LimitsBACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM Coaxial Water Pressure DropAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Page Complete C and Deluxe D Board System Test Aquazone Deluxe D Control LED Indica Complete C Control LED Code and Fault DescriptionsService Gravity Flow Method Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Alarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Optimal StartService Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceAlarm High Alarm LimitPage Page Copyright 2009 Carrier Corporation II. START-UP 50PEC Unit START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8453 A50-8454