Carrier 50PEC09-18 specifications Water Quality Guidelines

Page 35

 

 

Table 9 — Water Quality Guidelines

 

 

 

 

 

 

 

 

 

CONDITION

HX

CLOSED

OPEN LOOP AND RECIRCULATING WELL**

MATERIAL*

RECIRCULATING†

 

 

 

 

 

 

Scaling Potential — Primary Measurement

 

 

 

 

 

 

Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.

 

pH/Calcium

All

N/A

pH < 7.5 and Ca Hardness, <100 ppm

Hardness Method

 

 

 

 

 

 

 

Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)

 

Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be

implemented.

 

 

 

 

 

 

 

Ryznar Stability Index

All

N/A

 

6.0 - 7.5

 

 

 

 

If >7.5 minimize steel pipe use.

 

 

 

 

 

 

Langelier Saturation Index

 

 

 

 

–0.5 to +0.5

 

 

All

N/A

 

If <–0.5 minimize steel pipe use.

 

 

 

 

Based upon 150 F HWG and direct well, 85 F indirect well HX.

Iron Fouling

 

 

 

 

 

 

 

Iron Fe2+ (Ferrous)

All

N/A

 

 

<0.2 ppm (Ferrous)

 

(Bacterial Iron Potential)

If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.

 

 

Iron Fouling

All

N/A

 

 

<0.5 ppm of Oxygen

 

 

 

Above this level deposition will occur.

 

 

 

 

 

 

Corrosion Prevention††

 

 

 

 

 

 

 

pH

All

6 - 8.5

 

6 - 8.5

 

 

 

Monitor/treat as needed.

Minimize steel pipe below 7 and no open tanks with pH <8.

 

 

Hydrogen Sulfide (H2S)

 

 

 

 

<0.5 ppm

 

 

All

N/A

At H2S>0.2 ppm, avoid use of copper and cupronickel piping of HXs.

 

 

 

Rotten egg smell appears at 0.5 ppm level.

 

 

 

Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.

Ammonia Ion as Hydroxide,

 

 

 

 

<0.5 ppm

 

Chloride, Nitrate and Sulfate

All

N/A

 

 

 

 

 

Compounds

 

 

 

 

 

 

 

Maximum Chloride Levels

 

 

Maximum allowable at maximum water temperature.

 

 

 

50 F (10 C)

 

75 F (24 C)

 

100 F (38 C)

 

Copper

N/A

<20 ppm

 

NR

 

NR

 

Cupronickel

N/A

<150 ppm

 

NR

 

NR

 

304 SS

N/A

<400 ppm

 

<250 ppm

 

<150 ppm

 

316 SS

N/A

<1000 ppm

 

<550 ppm

 

<375 ppm

 

Titanium

N/A

>1000 ppm

 

>550 ppm

 

>375 ppm

Erosion and Clogging

 

 

 

 

 

 

 

Particulate Size and Erosion

 

<10 ppm of particles and a

<10 ppm (<1 ppm “sandfree” for reinjection) of particles and a maximum

 

All

maximum velocity of 6 fps.

velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that

 

 

Filtered for maximum

is not removed can potentially clog components.

 

 

 

800 micron size.

 

 

 

 

 

 

 

 

Brackish

 

 

Use cupronickel heat exchanger when concentrations of calcium or sodium

 

All

N/A

chloride are greater than 125 ppm are present. (Seawater is approximately

 

 

 

25,000 ppm.)

 

 

 

 

 

 

LEGEND

HWG —

Hot Water Generator

HX

Heat Exchanger

N/A

Design Limits Not Applicable Considering Recirculating

NR

Potable Water

Application Not Recommended

SSStainless Steel

*Heat exchanger materials considered are copper, cupronickel, 304 SS (stainless steel), 316 SS, titanium.

†Closed recirculating system is identified by a closed pressurized piping system.

**Recirculating open wells should observe the open recirculating design considerations.

††If the concentration of these corrosives exceeds the maximum allow- able level, then the potential for serious corrosion problems exists. Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0.

To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.

35

Image 35
Contents Safety Considerations Contents50PEC Physical Data InstallationGeneral A50-8335 OUTWater OUT CondensateA50-8338 Water22.2 OD A50-8337Damper Opening A50-833950PEC18 Bottom Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC18 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Right Hand Piping 50PEC18 Front Return Cabinet Dimensions Right Hand Piping A50-8345 50PEC09-15 Front Return Cabinet Dimensions Left Hand Piping50PEC18 Front Return Cabinet Dimensions Left Hand Piping A50-8347 Optional Autoflow Valve Motorized 50PEC09-15 Chassis Dimensions Front ReturnWater Valve Optional Autoflow Optional FusedOptional Disconnect Box Autoflow Optional Motorized50PEC18 Chassis Dimensions Front Return Mount Unit Wire Electrical Connections09-18 A50-8452A50-8327.eps Sensor, Water Coil Freeze Protection A50-8328Return Air Sensor Night Low Limit SwitchA50-8329 Blower Motor Wiring NLL PremierLink Controller Applications with Complete C Control A50-8355 8354 A50LWT 8353 Wshp Open Control A50-8380A50-8441 Wire Low Voltage ConnectionsElectrical Data 50PEC Units A50-7467tfSPT Sensors Recommended Thermostat Wire SizesField-Supplied Sensors for Wshp Open Controller A50-8443 Install Supply and Return PipingRnet Wiring Specifications Rnet WiringTemporary Connection for Flushing System Piping PRE-START-UPMax Entering Air, dry bulb/wet bulb Air and Water LimitsMin Ambient Air Rated Ambient Air Max Ambient Air Min Entering Air Rated Entering Air, dry bulb/wet bulbWater Quality Guidelines Field Selectable Inputs Complete C Control Jumper Settings See , 18,Deluxe D Control Jumper Settings See , 20, DIP Switch Block S2 Accessory 1 Relay OptionsOperating Limits DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Unit Start-Up/CoolingBACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM Coaxial Water Pressure DropUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Page Complete C and Deluxe D Board System Test Aquazone Deluxe D Control LED Indica Complete C Control LED Code and Fault DescriptionsService Gravity Flow Method Replacing the Wshp Open Controller’s Bat TroubleshootingRefrigerant Charging Air Coil Fan Motor RemovalFault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Sensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Optimal StartTest Appendix a Wshp Screen Open ConfigurationService Point Name Password Editable Range Default Level Configuration ServiceAlarm High Alarm LimitPage Page Copyright 2009 Carrier Corporation II. START-UP 50PEC Unit START-UP ChecklistA50-8454 Heating Cycle AnalysisCooling Cycle Analysis A50-8453