OPTIONAL WALL-MOUNTED THERMOSTAT — The 50PEC water source heat pump units are built with standard in- ternal thermostats in either manual changeover (MCO) or auto- matic changeover (ACO) configuration. Refer to Fig. 17-20.

When desired, the unit can be furnished with a 24-v control circuit which is field wired to a Carrier-supplied accessory re- mote thermostat. Most heat pump thermostats can be used with the controller. Use a thermostat with Y, G, O and W outputs. Refer to unit wiring diagrams in Fig. 21 and 22 and Aquazone Controls, Operation, and Troubleshooting Instructions for addi- tional information.

Vendor installation instructions and additional installation information is shipped with each thermostat.

NOTE: Low-voltage wiring between the unit and the wall ther- mostat must comply with all applicable electrical codes (i.e., NEC and local codes), and be completed before the unit is installed.

Table 3 lists recommended wire sizes and lengths to install the thermostat. The total resistance of low-voltage wiring must not exceed 1 ohm. Any resistance in excess of 1 ohm may cause the control to malfunction because of high voltage drop.

Table 3 — Recommended Thermostat Wire Sizes

WIRE SIZE

MAX WIRE LENGTH*

18-Gage

75 ft

16-Gage

125 ft

14-Gage

200 ft

*Length = Physical distance from thermostat to unit.

OPTIONAL PREMIERLINK™ CONTROLLER — This di- rect digital controller (DDC) allows the water source heat pump to be incorporated into a Carrier Comfort Network® (CCN) system installation. PremierLink control is factory- installed with the Complete C controller, or field-installed with the Deluxe D control option. Refer to Fig. 23 and 24.

WSHP OPEN WIRING — The WSHP Open controller will be factory wired to the Complete C or Deluxe D control board, however, the system wiring will need to be completed utilizing WSHP Open controller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation includes harness, LWT (leaving water temperature), supply air, and condensate sensor.

WARNING

Disconnect all power to the unit before performing mainte- nance or service. Unit may automatically start if power is not disconnected. Failure to follow this warning could cause personal injury, death, and/or equipment damage.

Wiring Sensors to Inputs — Sensors can be wired to the WSHP Open controller’s inputs. See Table 4.

All field control wiring that connects to the WSHP Open con- troller must be routed through the raceway built into the corner post. The raceway provides the UL required clearance between high and low-voltage wiring.

1.Pass control wires through the hole provided in the corner post.

2.Feed the wires through the raceway to the WSHP Open controller.

3.Connect the wires to the removable Phoenix connectors.

4.Reconnect the connectors to the board.

Field-Supplied Sensor Hardware — The WSHP Open con- troller is configurable with the following field-supplied sen- sors. See Table 4.

Table 4 — Field-Supplied Sensors for

WSHP Open Controller

SENSOR

NOTES

Space Temperature Sensor

Field Installed (Must be used with

(SPT)

WSHP Open controller.)

Outdoor Air

Network Sensor

Temperature Sensor

 

Indoor Air Quality Sensor

Required only for demand

(Separate Sensor)

control ventilation.

Space Relative Humidity

Separate Sensor

Sensor

 

NOTE: BACview6 Handheld or Virtual BACview can be used as the user interface.

For specific details about sensors, refer to the literature sup- plied with the sensor.

Wiring a SPT Sensor — A WSHP Open controller is connect- ed to a wall-mounted space temperature (SPT) sensor to moni- tor room temperature using a Molex plug.

The WSHP Open system offers the following SPT sensors. See Table 5.

Table 5 — SPT Sensors

SENSOR

PART

FEATURES

NUMBER

SPT

SPS

• Local access port

Standard

• No operator control

 

 

 

• Slide potentiometer to adjust set point

SPT Plus

SPPL

• Manual on button to override schedule

• LED to show occupied status

 

 

 

 

• Local access port

 

 

• LCD display

 

 

• Manual on button to override schedule

 

 

• Warmer and cooler buttons to adjust set

SPT Pro

SPP

point

• Info button to cycle through zone and

 

 

 

 

outside air temperatures, set points, and

 

 

local override time

 

 

• Local access port

 

 

• LCD display

 

 

• Manual on button to override schedule

 

 

• Warmer and cooler buttons to adjust set

SPT Pro

 

point

SPPF

• Info button to cycle through zone and

Plus

 

outside air temperatures, set points, and

 

 

 

 

local override time

 

 

• Local access port

 

 

• Fan speed*

*The SPT Pro Plus fan speed adjustment has no effect in this application.

Wire SPT sensors to the WSHP Open controller’s Rnet port. An Rnetbus can consist of any of the following combinations of devices wired in a daisy-chain configuration:

1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

1 to 4 SPT Standard sensors

1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

Any of the above combinations, plus up to 2 BACview6 Handheld but no more than 6 total devices

NOTE: If the Rnetbus has multiple SPT Standard sensors, each sensor must be given a unique address on the Rnetbus. See the Carrier Open Sensor Installation Guide.

Use the specified type of wire and cable for maximum signal integrity. See Table 6.

31

Image 31
Contents Safety Considerations ContentsGeneral Installation50PEC Physical Data A50-8335 OUTWater OUT CondensateA50-8338 Water22.2 OD A50-8337Damper Opening A50-833950PEC18 Bottom Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC18 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Right Hand Piping 50PEC18 Front Return Cabinet Dimensions Right Hand Piping A50-8345 50PEC09-15 Front Return Cabinet Dimensions Left Hand Piping50PEC18 Front Return Cabinet Dimensions Left Hand Piping A50-8347 Optional Autoflow Valve Motorized 50PEC09-15 Chassis Dimensions Front ReturnWater Valve Optional Autoflow Optional FusedOptional Disconnect Box Autoflow Optional Motorized50PEC18 Chassis Dimensions Front Return Mount Unit Wire Electrical Connections09-18 A50-8452A50-8327.eps Sensor, Water Coil Freeze Protection A50-8328A50-8329 Night Low Limit SwitchReturn Air Sensor Blower Motor Wiring NLL PremierLink Controller Applications with Complete C Control A50-8355 8354 A50LWT 8353 Wshp Open Control A50-8380A50-8441 Wire Low Voltage ConnectionsElectrical Data 50PEC Units A50-7467tfField-Supplied Sensors for Wshp Open Controller Recommended Thermostat Wire SizesSPT Sensors A50-8443 Install Supply and Return PipingRnet Wiring Specifications Rnet WiringTemporary Connection for Flushing System Piping PRE-START-UPMax Entering Air, dry bulb/wet bulb Air and Water LimitsMin Ambient Air Rated Ambient Air Max Ambient Air Min Entering Air Rated Entering Air, dry bulb/wet bulbWater Quality Guidelines Field Selectable Inputs Complete C Control Jumper Settings See , 18,Deluxe D Control Jumper Settings See , 20, DIP Switch Block S2 Accessory 1 Relay OptionsOperating Limits DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Unit Start-Up/CoolingBACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM Coaxial Water Pressure DropUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Page Complete C and Deluxe D Board System Test Aquazone Deluxe D Control LED Indica Complete C Control LED Code and Fault DescriptionsService Gravity Flow Method Replacing the Wshp Open Controller’s Bat TroubleshootingRefrigerant Charging Air Coil Fan Motor RemovalFault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Sensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Optimal StartService Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceAlarm High Alarm LimitPage Page Copyright 2009 Carrier Corporation II. START-UP 50PEC Unit START-UP ChecklistA50-8454 Heating Cycle AnalysisCooling Cycle Analysis A50-8453