Carrier 50PEC09-18 specifications Coaxial Water Pressure Drop, Gpm

Page 39

b. Select Weekly, then press enter (7 schedules available).

c.Select day and press enter.

d.Press enter again and select ADD or DEL (DECR or INCR) set schedule.

e.Enter ON/OFF time, then press continue.

f.Press OK to apply and save to a particular day of the week.

g.Continue to add the same or different schedule spe- cific days of the week.

To add exceptions to the schedule:

i.Press Add softkey.

ii.Select exception type from following:

Date

Date Range

Week-N-Day

Calender Reference

9.Go back to Home Screen.

10.Remove BACview6 cable from SPT sensor by reversing the process in Step 1.

11.Perform system test.

Flow Regulation — Flow regulation can be accom- plished by two methods. Most water control valves have a built-in flow adjustment valve. Determine the flow rate by measuring the pressure drop through the unit heat exchanger. See Table 12. Adjust the water control valve until a flow of 1.5 to 2 gpm per ton cooling is achieved. Since the pressure constantly varies, two pressure gages may be needed.

An alternative method for regulating flow is to install a flow control device. These devices are typically an orifice of plastic material mounted on the outlet of the water control valve, designed to allow a specified flow rate. Occasionally these valves produce a velocity noise that can be reduced by

applying some back pressure. To accomplish this, slightly close the leaving isolation valve of the water regulating device.

CAUTION

DO NOT use “Stop Leak” or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and inhibit unit operation.

Antifreeze — In areas where entering loop temperatures drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leaving loop temperature would be 22 to 25 F. Therefore, the freeze pro- tection should be at 15 F (30 F –15 F) = 15 F.

IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or intro- duced under water level to prevent alcohols from fuming.

Calculate the total volume of fluid in the piping system. See Table 13. Use the percentage by volume in Table 14 to deter- mine the amount of antifreeze to use. Antifreeze concentration should be checked from a well mixed sample using a hydrome- ter to measure specific gravity.

FREEZE PROTECTION SELECTION — The 30 F FP1 fac- tory setting (water) should be used to avoid freeze damage to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (antifreeze 10 F) set point to avoid nuisance faults.

Table 12 — Coaxial Water Pressure Drop

 

 

 

 

 

 

 

PRESSURE DROP (ft wg)

 

 

 

UNIT

 

FLOW

 

30 F

 

 

50 F

 

70 F

 

90 F

50PEC

 

(GPM)

Without

With Cv = 2.9

 

Without

With Cv = 2.9

Without

With Cv = 2.9

Without

With Cv = 2.9

 

 

 

Motorized

MOPD = 125 psi

 

Motorized

MOPD = 125 psi

Motorized

MOPD = 125 psi

Motorized

MOPD = 125 psi

 

 

 

Valve

 

Valve

Valve

Valve

 

 

 

 

 

 

 

 

 

 

1.3

1.8

2.0

 

1.3

1.5

1.2

1.3

1.0

1.2

09

 

1.9

3.2

3.6

 

2.5

2.9

2.2

2.7

2.0

2.4

 

 

2.5

5.0

5.8

 

3.9

4.6

3.5

4.2

3.0

3.8

 

 

1.6

1.8

6.5

 

1.6

6.5

1.4

6.5

1.3

6.5

12

 

2.3

3.3

11.4

 

2.9

11.4

2.6

11.4

2.3

11.4

 

 

3.1

5.3

19.6

 

4.5

19.6

4.1

19.6

3.7

19.6

 

 

1.8

1.2

1.6

 

1.2

1.6

1.1

1.5

1.0

1.4

15

 

2.7

2.6

3.4

 

2.2

3.1

2.0

2.9

1.9

2.7

 

 

3.6

4.2

5.7

 

3.5

5.0

3.2

4.8

3.0

4.5

 

 

2.4

2.1

2.8

 

2.0

2.6

1.8

2.4

1.6

2.3

18

 

3.6

4.2

5.8

 

3.7

5.2

3.3

4.9

3.0

4.6

 

 

4.8

6.8

9.6

 

6.0

8.8

5.5

8.2

4.9

7.7

 

 

 

LEGEND

 

 

 

 

 

 

 

 

Cv

Flow Coefficient

 

 

 

 

 

 

 

 

MOPD — Maximum Operating Pressure Differential

 

 

 

 

 

 

39

Image 39
Contents Safety Considerations ContentsInstallation General50PEC Physical Data A50-8335 OUTWater OUT CondensateA50-8338 Water22.2 OD A50-8337Damper Opening A50-833950PEC18 Bottom Return Cabinet Dimensions Right Hand Piping 50PEC09-15 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC18 Bottom Return Cabinet Dimensions Left Hand Piping 50PEC09-15 Front Return Cabinet Dimensions Right Hand Piping 50PEC18 Front Return Cabinet Dimensions Right Hand Piping A50-8345 50PEC09-15 Front Return Cabinet Dimensions Left Hand Piping50PEC18 Front Return Cabinet Dimensions Left Hand Piping A50-8347 Optional Autoflow Valve Motorized 50PEC09-15 Chassis Dimensions Front ReturnWater Valve Optional Autoflow Optional FusedOptional Disconnect Box Autoflow Optional Motorized50PEC18 Chassis Dimensions Front Return Mount Unit Wire Electrical Connections09-18 A50-8452A50-8327.eps Sensor, Water Coil Freeze Protection A50-8328Night Low Limit Switch A50-8329Return Air Sensor Blower Motor Wiring NLL PremierLink Controller Applications with Complete C Control A50-8355 8354 A50LWT 8353 Wshp Open Control A50-8380A50-8441 Wire Low Voltage ConnectionsElectrical Data 50PEC Units A50-7467tfRecommended Thermostat Wire Sizes Field-Supplied Sensors for Wshp Open ControllerSPT Sensors A50-8443 Install Supply and Return PipingRnet Wiring Specifications Rnet WiringTemporary Connection for Flushing System Piping PRE-START-UPMax Entering Air, dry bulb/wet bulb Air and Water LimitsMin Ambient Air Rated Ambient Air Max Ambient Air Min Entering Air Rated Entering Air, dry bulb/wet bulbWater Quality Guidelines Field Selectable Inputs Complete C Control Jumper Settings See , 18,Deluxe D Control Jumper Settings See , 20, DIP Switch Block S2 Accessory 1 Relay OptionsOperating Limits DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Unit Start-Up/CoolingBACview6 Display Interface Unit Start-Up with Wshp Open ControlsGPM Coaxial Water Pressure DropUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Page Complete C and Deluxe D Board System Test Aquazone Deluxe D Control LED Indica Complete C Control LED Code and Fault DescriptionsService Gravity Flow Method Replacing the Wshp Open Controller’s Bat TroubleshootingRefrigerant Charging Air Coil Fan Motor RemovalFault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Sensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Optimal StartAppendix a Wshp Screen Open Configuration ServiceTest Point Name Password Editable Range Default Level Configuration ServiceAlarm High Alarm LimitPage Page Copyright 2009 Carrier Corporation II. START-UP 50PEC Unit START-UP ChecklistA50-8454 Heating Cycle AnalysisCooling Cycle Analysis A50-8453