HEATING CYCLE ANALYSIS
|
| ft wg |
| SST | |
|
|
|
|
| (SATURATED |
|
|
| F |
| SUCTION |
|
|
|
| TEMPERATURE) | |
|
|
|
|
|
- - - -
AIR
COIL
FF
EXPANSION | COAX |
VALVE |
|
| F |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
LIQUID LINE |
|
| F |
|
|
|
| F | |||
|
|
|
|
| ft wg |
|
|
|
| ft wg | |
|
|
| WATER IN |
| WATER OUT | ||||||
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
SUCTION
COMPRESSOR
DISCHARGE
a50-8453
LOOK UP PRESSURE DROP IN TABLE 12 TO DETERMINE FLOW RATE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - DOTTED LINE
COOLING CYCLE ANALYSIS
|
| ft wg |
| SST | |
|
|
|
|
| (SATURATED |
|
|
| F |
| SUCTION |
|
|
|
| TEMPERATURE) | |
|
|
|
|
|
- - - - - - - - - - - - - - - - CUT ALONG
AIR
COIL
FF
EXPANSION
VALVE
F
COAX
SUCTION
COMPRESSOR
DISCHARGE
a50-8454
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - DOTTED LINE
LIQUID LINE |
| F |
|
| F |
|
| ft wg |
|
| ft wg |
| WATER IN | WATER OUT |
LOOK UP PRESSURE DROP IN TABLE 12
TO DETERMINE FLOW RATE
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (gpm) x |
| TEMP. DIFF. (DEG. F) x |
| FLUID FACTOR* = |
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SATURATED SUCTION TEMPERATURE
=(DEG F)
SUBCOOLING = SATURATED CONDENSING TEMPERATURE – LIQUID LINE TEMPERATURE
=(DEG F)
*Use 500 for water, 485 for antifreeze.
97B0035N06