SSI America 7SL Power Line and grounding, Power Supply, Preliminary Hardware Settings

Page 12

E) Power Line and grounding

 

N, L2

4

POWER SUPPLY

 

 

100 to 240 Vac

524 Vac/Vdc

R (S,T), L1

N, L2

 

R (S,T), L1

NOTE:

1)Before connecting the power line, check that the voltage is correct (see Model Number).

2)For supply connections use 16 AWG or larger wires rated for at least 75 °C.

3)Use copper conductors only.

4)Do not run input wires with power cables.

5)Polarity does not matter for 24 Vdc wiring.

6)The power supply input is not fuse protected. Please provide it externally.

Power Supply

Type

Current

Voltage

 

 

 

 

24 Vac/Vdc

T

500 mA

250 V

 

 

 

 

100/240 Vac

T

125 mA

250 V

 

 

 

 

PRELIMINARY HARDWARE SETTINGS

1)Remove the instrument from its case.

2)Set J106 according to the following table:

Input Type

 

 

J106

 

 

1-2

3-4

5-6

7-8

 

 

T/C, RTD,

 

 

 

 

 

0-60 mV, 12-60 mV

 

close

open

open

open

(standard configuration)

 

 

 

 

 

0-5 V, 1-5V

 

open

close

open

open

 

 

 

 

 

 

0-10V, 2-10 V

 

open

open

close

open

 

 

 

 

 

 

0-20 mA, 4-20 mA

 

open

open

open

close

 

 

 

 

 

 

Input CTTC R192=180K

 

 

 

 

SH120=Closed CH101=Open

When the fuse is damaged the instrument should be returned to your supplier to check the power supply.

7)Safety requirements for permanently connected equipment:

-Include a switch or circuit-breaker in the installation.

-Place the switch in close proximity to the equipment and within easy reach of the operator.

-Mark the switch as the disconnecting device for the equipment. NOTE: A single switch or circuit-breaker can drive more than one instrument.

8)When the NEUTRAL line is present, connect it to terminal 4.

9)To avoid shock and possible instrument damage, connect power last.

1 2

7sl-1-00.p65

12

9/17/02, 2:39 PM

Image 12
Contents Model 7SL HIGH/LOW Limitrol 16 DIN, Four Digit HIGH/LOW Limitrol Congratulations Guide to simple set-upTable of Contents USE Wire Suitable For 75C MinimumMounting Requirements Dimensions and Panel Cutout Wiring Guidelines Terminal LayoutMeasuring Inputs TC Input Linear Input RTD InputRTD Logic Input7sl-1-00.p65 17/02, 239 PM Relay Outputs OUTSerial Interface CommonPower Line and grounding Power SupplyPreliminary Hardware Settings Limitrol with RS-485 Limitrol without RS-485Configuration KEY Functions Configuration ProcedureR5 = Offset Adjustment R7 = Alarm Action on FaultC2 = Acknowledgment Mode R1 = Input Type and Range Value R2 = Decimal Point PositionControl Output Function C3 = Reset at Power-up C4 = Reset MemoryP2 = Alarm configuration P3 = Alarm Action Alarm Standby Function= Safety Lock OFF =T1 = Timeout Selection tn10 = 10 second timeout Operating Mode Normal Display ModeIndicators ResetKey Functions in Normal Display Mode Parameter Display ModeKey Functions in Parameter Display Mode Operating Parameters Error Messages Error MessagesError List Dealing with Error MessagesDefault Parameters Loading Default Operating ParametersDefault Operating Parameters List Loading Default Configuration ParametersDefault Configuration Parameter List ParaSpecifications Display Update Time Range Temperature DriftCommon Mode Rejection Ratio Normal Mode Rejection RatioAcknowledgment Mode Power-Up ModeAlarm Function Type of AlarmReferences CEI 70-1 IECNema ENV50140Calibration Procedure General GuidelinesCalibration Parameters Procedure TH TC Input Final Scale ValueTC Input Check Entering Calibration ValuesPH RTD Input Final Scale Value RTD CheckRJ. Cold Junction Compensation Check PL RTD Input Initial Scale ValueAH Current Input Final Scale Value Current Input CheckNH 5 Volt Input Final Scale Value Volt Input CheckUL 10 Volt Input Initial Scale Value UH 10 Volt Input Final Scale ValueMaintenance Manual Part No 7SL