SSI America 7SL instruction manual P3 = Alarm Action, Alarm Standby Function, Off =, = Safety Lock

Page 18

Example for P2 = H.A.A.c

(Alarm

(Hysteresis) threshold)

P3 = Alarm Action

(Skipped if option not is available or P1 = none)

dir =

Direct action

 

(Relay energized in alarm condition)

Alarm status* Relay No alarm status

ON

ALM LED

OFF

FLASH

ACK

FLASH

rEV

=

Reverse action

 

 

(Relay energized in non-alarm condition)

P4

=

Alarm Standby Function

(Skipped if option is not available or P1= none)

OFF =

Standby function disabled

On

=

Standby function enabled

ACK = Alarm acknowledgment from "AK" parameter or serial link.

*Alarm Status:Relay energized (P3 = dir) Relay de-energized (P3 =rEV)

Example for P2 = H.L.

If the alarm is programmed as band or deviation, this function masks the alarm condition at start up and at a “Su” setpoint change until the process variable reaches the alarm threshold, plus or minus hysteresis. This standby function masks a Process Alarm condition at start up until the process variable reaches the alarm threshold plus or minus hysteresis.

(Hysteresis)

Alarm status* Relay No alarm status

ON

ALM LED

OFF

FLASH

ACK

(Alarm

threshold)

FLASH

ACK

PF = Time Constant for Filter on Measured Value for Alarm Action

(Skipped if option is not available or P1 = none) Range: From 0 (filter OFF) to 8 seconds (First order filter with selected time constant.)

n 1 = Safety Lock

0= UNLOCKed. The device is always UNLOCKed and all parameters can be modified.

l

=

LOCKed. The device is always LOCKed and

 

 

no parameters can be modified

ACK = Alarm acknowledgment from "AK" parameter or serial link.

*Alarm Status:Relay energized (P3 = dir) Relay de-energized (P3 =rEV)

From 2 to 9999 = This number is a password, to be used in run time (see “nn”), to LOCK/UNLOCK the device.

1 8

7sl-2-00.p65

18

9/17/02, 2:40 PM

Image 18
Contents Model 7SL HIGH/LOW Limitrol 16 DIN, Four Digit HIGH/LOW Limitrol Congratulations Guide to simple set-upTable of Contents USE Wire Suitable For 75C MinimumMounting Requirements Dimensions and Panel Cutout Wiring Guidelines Terminal LayoutMeasuring Inputs TC Input RTD Linear InputRTD Input Logic Input7sl-1-00.p65 17/02, 239 PM Relay Outputs OUTSerial Interface CommonPower Line and grounding Power SupplyPreliminary Hardware Settings Limitrol with RS-485 Limitrol without RS-485Configuration KEY Functions Configuration ProcedureC2 = Acknowledgment Mode R5 = Offset AdjustmentR7 = Alarm Action on Fault R1 = Input Type and Range Value R2 = Decimal Point PositionControl Output Function C3 = Reset at Power-up C4 = Reset MemoryP2 = Alarm configuration = Safety Lock P3 = Alarm ActionAlarm Standby Function OFF =T1 = Timeout Selection tn10 = 10 second timeout Indicators Operating ModeNormal Display Mode ResetKey Functions in Normal Display Mode Parameter Display ModeKey Functions in Parameter Display Mode Operating Parameters Error List Error MessagesError Messages Dealing with Error MessagesDefault Operating Parameters List Default ParametersLoading Default Operating Parameters Loading Default Configuration ParametersDefault Configuration Parameter List ParaSpecifications Common Mode Rejection Ratio Display Update Time RangeTemperature Drift Normal Mode Rejection RatioAlarm Function Acknowledgment ModePower-Up Mode Type of AlarmNema ReferencesCEI 70-1 IEC ENV50140Calibration Procedure General GuidelinesCalibration Parameters TC Input Check ProcedureTH TC Input Final Scale Value Entering Calibration ValuesRJ. Cold Junction Compensation Check PH RTD Input Final Scale ValueRTD Check PL RTD Input Initial Scale ValueNH 5 Volt Input Final Scale Value AH Current Input Final Scale ValueCurrent Input Check Volt Input CheckUL 10 Volt Input Initial Scale Value UH 10 Volt Input Final Scale ValueMaintenance Manual Part No 7SL