Example for P2 = H.A.A.c
(Alarm
(Hysteresis) threshold)
P3 = Alarm Action
(Skipped if option not is available or P1 = none)
dir = | Direct action |
| (Relay energized in alarm condition) |
Alarm status* Relay No alarm status
ON
ALM LED
OFF
FLASH
ACK
FLASH
rEV | = | Reverse action |
|
| (Relay energized in |
P4 | = | Alarm Standby Function |
(Skipped if option is not available or P1= none) | ||
OFF = | Standby function disabled | |
On | = | Standby function enabled |
ACK = Alarm acknowledgment from "AK" parameter or serial link.
*Alarm Status:Relay energized (P3 = dir) Relay
Example for P2 = H.L.
If the alarm is programmed as band or deviation, this function masks the alarm condition at start up and at a “Su” setpoint change until the process variable reaches the alarm threshold, plus or minus hysteresis. This standby function masks a Process Alarm condition at start up until the process variable reaches the alarm threshold plus or minus hysteresis.
(Hysteresis)
Alarm status* Relay No alarm status
ON
ALM LED
OFF
FLASH
ACK
(Alarm
threshold)
FLASH
ACK
PF = Time Constant for Filter on Measured Value for Alarm Action
(Skipped if option is not available or P1 = none) Range: From 0 (filter OFF) to 8 seconds (First order filter with selected time constant.)
n 1 = Safety Lock
0= UNLOCKed. The device is always UNLOCKed and all parameters can be modified.
l | = | LOCKed. The device is always LOCKed and |
|
| no parameters can be modified |
ACK = Alarm acknowledgment from "AK" parameter or serial link.
*Alarm Status:Relay energized (P3 = dir) Relay
From 2 to 9999 = This number is a password, to be used in run time (see “nn”), to LOCK/UNLOCK the device.
1 8