WIRING GUIDELINES
Terminal Layout
6 | + | 11 | A/A' |
| 1 |
C | NO | ||||
|
|
| |||
| OUT 2 |
|
| OUT 1 |
|
A) Measuring Inputs
NOTE: Any external components (like Zener diodes, etc.) connected between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage cur- rents.
TC Input
7 | NO | 12 B/B' | C | 2 | |
| |||||
|
| _ | RS485 |
|
|
|
|
|
|
| |
8 |
| 13 | C | NC | 3 |
|
| RTD |
|
| 4 |
9 |
| 14 |
|
|
10
9
+
_
Shield
_ | LINEAR |
| LINEPWR 100/240Vac Vac/dc24 |
|
TC | DIG 1 |
| ||
10 | 15 | 5 |
+
10
9
+
_
Shield
NOTE: When a relay output is used to drive an inductive load, connect an external snubber network (RC) across the terminals:
|
| R | C |
| |
in accordance with the following table: | |||||
|
|
|
|
|
|
Load | C |
| R | P | Resistor and |
Current | (∝F) |
| (Ω ) | (W) | Capacitor Voltage |
|
|
|
|
|
|
< 40 mA | 0.047 |
| 100 | 1/2 | 260 Vac |
|
|
|
|
|
|
< 150 mA | 0.1 |
| 22 | 2 | 260 Vac |
|
|
|
|
|
|
< 0.5 Amp | 0.33 |
| 47 | 2 | 260 Vac |
|
|
|
|
|
|
7
NOTE:
1)Do not run input wires with power cables.
2)For TC wiring use proper compensating cable, preferably shielded (see Thermocouple Compen- sating Cable Color Codes).
3)Shielded cable should be grounded at one end only.