CONFIGURATION KEY FUNCTIONS
RESET In Configuration Mode, used only to scroll back parameters
Used in Configuration Mode to decrease the parameter value.
Used in Configuration Mode to increase the parameter value.
FUNC | Monitors/Modifies parameters. |
+ | Loads the default parameters. |
+ FUNC or + FUNC
Increases/decreases values at a higher rate when modifying parameters.
+ RESET or + RESET
Jumps to the Maximum or Minimum parameter value when modifying parameters.
CONFIGURATION PROCEDURE
1)Remove the instrument from its case.
2)Open switch V101 (See illustrations under “Prelimi- nary Hardware Settings.”)
3)
4)Switch on power to the instrument. The upper display will show COnF.
5)Press the “” key and the lower display will show the firmware version.
Press the "FUNC" key to start the configuration proce- dure with the first parameter (L1). Press the "RESET" key to start the configuration procedure with the last parameter (d1).
The following is a complete list of parameters. The lower display will show the parameter code (L1 to d1) and the upper display will show the selection code or numerical value. No timeout is applied in the configuration mode.
L1 = Serial Interface Protocol (Skipped if option is not available.) OFF = No serial interface nbUS= Modbus
jbUS = Jbus
L2 = Serial Link Device Address (Skipped if option is not available or L1 = OFF) From 1 to 255
NOTE: The device can connect up to 31 instruments.
L3 = Baud Rate for Serial Link
(Skipped if option is not available or L1 = OFF) Set value from 600 to 19200 baud.
(19200 baud is shown on display as 1920)
L4 = Byte Format for Serial Link (Skipped if option is not available or L1 = OFF) 8E = 8 bits + even parity
8O = 8 bits + odd parity
8 = 8 bits without parity