SSI America 7SL instruction manual Operating Mode, Normal Display Mode, Indicators, Reset, Alm

Page 20

OPERATING MODE

1)Remove the instrument from its case.

2)Set switch V101 to the closed position.

3)Re-insert the instrument in its case.

4)Switch on the instrument.

Normal Display Mode

On powerup the device starts in the "Normal Display Mode."

By pressing the or key, it is possible to change the displayed information; therefore, one of the following display modes can be selected:

1)The upper display shows the measured value while the lower display shows the "Pu" (Process variable)

2)The upper display shows the setpoint threshold while the lower display shows "Su." If this display was active at power down, it will be active at powerup.

3)The upper display shows the setpoint1 threshold while the lower display shows "S1." This information is available only if C1 = Hi.Lo If this display was active at power down, it will be active at powerup

4)The upper display shows the total time (hh.mm) of the last reset condition while the lower displays shows “t.” (if no data is available, the upper display will show

"- - - -" ). The information is lost at power down and at powerup the device will display the process variable.

5)The upper display shows the maximum value of process variable detected during the last "reset" con- dition while the lower display shows "Ph." (if no data is available, the upper display will show “- - - -” ). This information is not available if C1 = Lo. The information is lost at power down and at powerup the device will display the process variable.

NOTE: In case the reset condition was generated by a fault condition in the measure variable, the upper display

will indicate "m.Err"

6)The upper display shows the minimum value of the process variable detected during the last "reset" con- dition while the lower display shows "PL.” (if no data is available, the upper display will show “- - - -”) This information is not available if C1 = Hi. The information is lost at power down and at powerup the device will display the process variable .

NOTE: in case the “reset condition” was generated by a fault condition in the measure variable, the upper

display will indicate "m.Err"

At powerup the display will show the process variable unless otherwise stated in one of the above display options

If, at power off, the device was in reset condition and configured to save it (C4 = 0), and/or it was programmed for manual reset at startup (C3 = 1), then at the next power up the lower display will be flashing.

Indicators

 

 

“RESET“

=

Indicates control output status

 

 

as follows:

 

 

a) With configuration parameter

 

 

C2 = 0

 

 

LED ON when Output is OFF

 

 

LED OFF when Output is ON

 

 

b) With configuration parameter

 

 

C2 = 1

 

 

LED flashes when Output is OFF

 

 

LED ON when Output is OFF

 

 

and acknowledged

 

 

LED OFF when Output is ON

“ALM”

=

Indicates alarm status as follows:

 

 

Flashes when alarm is ON

 

 

ON when alarm has been

 

 

acknowledged

 

 

OFF when alarm is OFF

2 0

7sl-3-00.p65

20

9/17/02, 2:41 PM

Image 20
Contents Model 7SL HIGH/LOW Limitrol 16 DIN, Four Digit HIGH/LOW Limitrol Congratulations Guide to simple set-upTable of Contents USE Wire Suitable For 75C MinimumMounting Requirements Dimensions and Panel Cutout Measuring Inputs TC Input Wiring GuidelinesTerminal Layout Linear Input RTD InputRTD Logic Input7sl-1-00.p65 17/02, 239 PM Relay Outputs OUTSerial Interface CommonPreliminary Hardware Settings Power Line and groundingPower Supply Limitrol with RS-485 Limitrol without RS-485Configuration KEY Functions Configuration ProcedureR5 = Offset Adjustment R7 = Alarm Action on FaultC2 = Acknowledgment Mode R1 = Input Type and Range Value R2 = Decimal Point PositionControl Output Function P2 = Alarm configuration C3 = Reset at Power-upC4 = Reset Memory P3 = Alarm Action Alarm Standby Function= Safety Lock OFF =T1 = Timeout Selection tn10 = 10 second timeout Operating Mode Normal Display ModeIndicators ResetKey Functions in Parameter Display Mode Key Functions in Normal Display ModeParameter Display Mode Operating Parameters Error Messages Error MessagesError List Dealing with Error MessagesDefault Parameters Loading Default Operating ParametersDefault Operating Parameters List Loading Default Configuration ParametersDefault Configuration Parameter List ParaSpecifications Display Update Time Range Temperature DriftCommon Mode Rejection Ratio Normal Mode Rejection RatioAcknowledgment Mode Power-Up ModeAlarm Function Type of AlarmReferences CEI 70-1 IECNema ENV50140Calibration Parameters Calibration ProcedureGeneral Guidelines Procedure TH TC Input Final Scale ValueTC Input Check Entering Calibration ValuesPH RTD Input Final Scale Value RTD CheckRJ. Cold Junction Compensation Check PL RTD Input Initial Scale ValueAH Current Input Final Scale Value Current Input CheckNH 5 Volt Input Final Scale Value Volt Input CheckUL 10 Volt Input Initial Scale Value UH 10 Volt Input Final Scale ValueMaintenance Manual Part No 7SL