Key Functions in Normal Display Mode

“FUNC” = By pressing it, the display changes from “Normal Display Mode” to “Parameter Display Mode.”

=Pressing it for more than ten seconds initiates the Lamp Test. During the Lamp Test the device functions normally while all display segments and LED's are lit with a 50% duty cycle. No timeout is applied to a lamp test.

All parameters (except) can be modified only when the device is UNLOCKed.

The LOCK/UNLOCK status can be selected in configura- tion using parameter n1 or during the operating mode with the parameter password.

To switch from LOCKED to UNLOCKED, enter the n1 parameter setting. To switch from UNLOCKED to LOCKED, enter any number other than the n1 parameter setting.

Press the "FUNC" key again to end the

Lamp Test.

"" or “" = By pressing these keys it is possible to change the displayed information. See “Normal Display Mode” on previous page.

“RESET” = Press and hold for 1 second to initiate “reset.”

Parameter Display Mode

The "FUNC" key initiates the Parameter Display Mode when pressed for less than 10 seconds in the "Normal Display Mode."

The lower display shows the parameter identification code while the upper display shows the parameter value. The value of these parameters can be modified with the and keys.

Press the "FUNC" key again to store the new value and advance to the next parameter.

If no keys are pressed within the timeout period (see t1), the display will automatically return to the "Normal Dis- play Mode" in the previous display and any modifications of the last displayed parameter will be lost.

When the device is in remote (the serial link controls the device) no parameters can be modified.

Key Functions in Parameter Display Mode

FUNC = Press the “FUNC” key again and the instrument stores the new setting

(if changed) and goes to the next parameter.

or

=

Changes the setting of the selected

 

 

parameter.

RESET

=

Press and hold for more than 1 second to

 

 

initiate reset.

2 1

7sl-3-00.p65

21

9/17/02, 2:41 PM

Image 21
Contents Model 7SL HIGH/LOW Limitrol 16 DIN, Four Digit HIGH/LOW Limitrol Guide to simple set-up CongratulationsUSE Wire Suitable For 75C Minimum Table of ContentsMounting Requirements Dimensions and Panel Cutout Wiring Guidelines Terminal LayoutMeasuring Inputs TC Input RTD Input Linear InputRTD Logic Input7sl-1-00.p65 17/02, 239 PM OUT Relay OutputsCommon Serial InterfacePower Line and grounding Power SupplyPreliminary Hardware Settings Limitrol without RS-485 Limitrol with RS-485Configuration Procedure Configuration KEY FunctionsR7 = Alarm Action on Fault R5 = Offset AdjustmentC2 = Acknowledgment Mode R1 = Input Type and Range Value R2 = Decimal Point PositionControl Output Function C3 = Reset at Power-up C4 = Reset MemoryP2 = Alarm configuration Alarm Standby Function P3 = Alarm Action= Safety Lock OFF =T1 = Timeout Selection tn10 = 10 second timeout Normal Display Mode Operating ModeIndicators ResetKey Functions in Normal Display Mode Parameter Display ModeKey Functions in Parameter Display Mode Operating Parameters Error Messages Error MessagesError List Dealing with Error MessagesLoading Default Operating Parameters Default ParametersDefault Operating Parameters List Loading Default Configuration ParametersPara Default Configuration Parameter ListSpecifications Temperature Drift Display Update Time RangeCommon Mode Rejection Ratio Normal Mode Rejection RatioPower-Up Mode Acknowledgment ModeAlarm Function Type of AlarmCEI 70-1 IEC ReferencesNema ENV50140Calibration Procedure General GuidelinesCalibration Parameters TH TC Input Final Scale Value ProcedureTC Input Check Entering Calibration ValuesRTD Check PH RTD Input Final Scale ValueRJ. Cold Junction Compensation Check PL RTD Input Initial Scale ValueCurrent Input Check AH Current Input Final Scale ValueNH 5 Volt Input Final Scale Value Volt Input CheckUH 10 Volt Input Final Scale Value UL 10 Volt Input Initial Scale ValueMaintenance Manual Part No 7SL