MOUNTING REQUIREMENTS

Select a mounting location with the following characteristics:

1)Minimal vibration.

2)An ambient temperature range between 0 and 50°C (32 and 122 °F).

3)Easy access to the rear of the instrument.

4)No corrosive gases (sulfuric gas, ammonia, etc.).

5)No water or other fluid (i.e. condensation).

6)Relative humidity of 20% to 80% non condensing.

The instrument can be mounted on a panel up to 15 mm (0.591 in) thick with a square cutout of 45 x 45 mm (1.772 x 1.772 in). For outline refer to Dimensions and Panel Cutout.

Panel surface texture must be better than 6.3 µmm.

The instrument is shipped with a rubber panel gasket (50 to 60 Sh). To assure the IP65 and NEMA 4 protection, insert the panel gasket between the instrument and the panel as shown below.

Install the instrument as follows:

1)Insert the instrument in the gasket.

2)Insert the instrument in the panel cutout.

3)Pushing the instrument against the panel, insert the mounting bracket.

4)Torque the mounting bracket screws between 0.3 and 0.4 Nm (2.66 and 3.54 lbf-in).

5)To insure NEMA 4X/IP65 protection, make sure the instrument does not move within the cutout .

Bracket

Panel

Gasket

5

7sl-1-00.p65

5

9/17/02, 2:39 PM

Image 5 Contents
Model 7SL HIGH/LOW Limitrol 16 DIN, Four Digit HIGH/LOW Limitrol Guide to simple set-up CongratulationsUSE Wire Suitable For 75C Minimum Table of ContentsMounting Requirements Dimensions and Panel Cutout Measuring Inputs TC Input Wiring GuidelinesTerminal Layout RTD Input Linear InputRTD Logic Input7sl-1-00.p65 17/02, 239 PM OUT Relay OutputsCommon Serial InterfacePreliminary Hardware Settings Power Line and groundingPower Supply Limitrol without RS-485 Limitrol with RS-485Configuration Procedure Configuration KEY FunctionsR7 = Alarm Action on Fault R5 = Offset AdjustmentC2 = Acknowledgment Mode R1 = Input Type and Range Value R2 = Decimal Point PositionControl Output Function P2 = Alarm configuration C3 = Reset at Power-upC4 = Reset Memory Alarm Standby Function P3 = Alarm Action= Safety Lock OFF =T1 = Timeout Selection tn10 = 10 second timeout Normal Display Mode Operating ModeIndicators ResetKey Functions in Parameter Display Mode Key Functions in Normal Display ModeParameter Display Mode Operating Parameters Error Messages Error MessagesError List Dealing with Error MessagesLoading Default Operating Parameters Default ParametersDefault Operating Parameters List Loading Default Configuration ParametersPara Default Configuration Parameter ListSpecifications Temperature Drift Display Update Time RangeCommon Mode Rejection Ratio Normal Mode Rejection RatioPower-Up Mode Acknowledgment ModeAlarm Function Type of AlarmCEI 70-1 IEC ReferencesNema ENV50140Calibration Parameters Calibration ProcedureGeneral Guidelines TH TC Input Final Scale Value ProcedureTC Input Check Entering Calibration ValuesRTD Check PH RTD Input Final Scale ValueRJ. Cold Junction Compensation Check PL RTD Input Initial Scale ValueCurrent Input Check AH Current Input Final Scale ValueNH 5 Volt Input Final Scale Value Volt Input CheckUH 10 Volt Input Final Scale Value UL 10 Volt Input Initial Scale ValueMaintenance Manual Part No 7SL