Sanyo C3082, C3682 service manual Cooling Capacity, Indoor Outdoor

Page 21

5-2. Cooling Capacity

Indoor Unit

:

KS3082

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

:

C3082

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

 

< Cooling Capacity (Low Ambient) >

 

 

 

 

 

 

 

 

RATING CAPACITY:

30,600 BTU/h

 

AIR FLOW RATE:

 

630 CFM

 

 

 

INDOOR

 

 

 

 

 

OUTDOOR

 

 

 

 

 

ENT. TEMP. oF (oC)

 

 

 

 

AMBIENT TEMP. oF (oC)

 

 

 

 

 

W.B.

D.B.

 

 

0

5

15

25

 

35

45

55

 

 

 

 

 

 

 

 

(-17.8)

(-15.0)

(-9.4)

(-3.9)

 

(1.7)

(7.2)

(12.8)

 

 

 

 

 

 

TC

 

30,120

30,060

29,930

29,780

 

29,590

29,330

29,070

 

 

 

 

72

(22.2)

SHC

 

21,150

21,150

21,020

20,900

 

20,780

20,660

20,530

 

 

 

59

76

(24.4)

SHC

 

23,470

23,470

23,350

23,230

 

23,230

22,980

22,860

 

 

(15.0)

80

(26.7)

SHC

 

25,920

25,920

25,790

25,790

 

25,670

25,430

25,300

 

 

 

 

84

(28.9)

SHC

 

28,240

28,240

28,120

28,120

 

27,990

27,870

27,630

 

 

 

 

88

(31.1)

SHC

 

30,120

30,060

29,930

29,780

 

29,590

29,330

29,070

 

 

 

 

 

 

TC

 

30,390

30,360

30,270

30,170

 

30,040

29,820

29,610

 

 

 

 

72

(22.2)

SHC

 

17,720

17,720

17,600

17,600

 

17,480

17,360

17,360

 

 

 

63

76

(24.4)

SHC

 

20,050

20,050

19,920

19,920

 

19,800

19,800

19,680

 

 

(17.2)

80

(26.7)

SHC

 

22,490

22,490

22,370

22,370

 

22,370

22,250

22,120

 

 

 

 

84

(28.9)

SHC

 

24,820

24,820

24,820

24,690

 

24,690

24,570

24,450

 

 

 

 

88

(31.1)

SHC

 

27,140

27,140

27,140

27,020

 

27,020

26,890

26,770

 

 

 

 

 

 

TC

 

30,490

30,480

30,450

30,400

 

30,330

30,160

30,020

 

 

 

 

72

(22.2)

SHC

 

14,180

14,180

14,180

14,180

 

14,180

14,050

14,050

 

 

 

67

76

(24.4)

SHC

 

16,500

16,500

16,500

16,500

 

16,500

16,380

16,380

 

 

(19.4)

80

(26.7)

SHC

 

19,070

18,940

18,940

18,940

 

18,940

18,820

18,820

 

 

 

 

84

(28.9)

SHC

 

21,390

21,390

21,390

21,270

 

21,270

21,150

21,150

 

 

 

 

88

(31.1)

SHC

 

23,710

23,710

23,710

23,710

 

23,590

23,590

23,470

 

 

 

 

 

 

TC

 

30,370

30,380

30,410

30,430

 

30,420

30,310

30,250

 

 

 

 

72

(22.2)

SHC

 

10,510

10,510

10,510

10,630

 

10,630

10,510

10,510

 

 

 

71

76

(24.4)

SHC

 

12,950

12,950

12,950

12,950

 

12,950

12,830

12,830

 

 

(21.7)

80

(26.7)

SHC

 

15,400

15,400

15,400

15,400

 

15,400

15,280

15,280

 

 

 

 

84

(28.9)

SHC

 

17,720

17,720

17,720

17,720

 

17,720

17,720

17,600

 

 

 

 

88

(31.1)

SHC

 

20,050

20,050

20,050

20,050

 

20,050

20,050

20,050

 

 

 

 

 

 

TC

 

30,030

30,080

30,170

30,240

 

30,310

30,250

30,270

 

 

 

75

76

(24.4)

SHC

 

9,410

9,410

9,410

9,530

 

9,530

9,530

9,530

 

 

(23.9)

80

(26.7)

SHC

 

11,850

11,850

11,850

11,970

 

11,970

11,970

11,970

 

 

 

 

84

(28.9)

SHC

 

14,180

14,180

14,300

14,300

 

14,300

14,300

14,300

 

 

 

 

88

(31.1)

SHC

 

16,500

16,620

16,620

16,620

 

16,620

16,620

16,620

 

 

 

 

 

 

TC : Total Cooling Capacity (BTU/h)

SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.

2.Above data represents the value when the operation frequency of a compressor is fixed.

21

Image 21
Contents Destination North America Indoor Model No. Product Code NoSafety Precautions Prohibit Table of Contents Checking Electrical Components Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeUnit Specifications SpecificationsKS3082 C3082208V C3682 KS368221.9 Indoor Unit Major Component SpecificationsCB-KS3682 Microprocessor 250V 3A Outdoor Unit C3082 Outdoor UnitBoard CompressorOutdoor Unit C3682 Other Component Specifications Indoor Unit KS3082 Dimensional DataInchmm Refrigerant Flow Diagram Refrigerant Flow DiagramLow pressure performance chart Temperature ChartsOperating current performance chart Indoor discharge air performance chartWide Indoor Outdoor Cooling CapacityIndoor Cooling Capacity34,000 BTU/h Indoor Power Supply 230V Single Phase 60Hz Cooling CapacityAir Throw Distance Charts Cooling Vertical distance ftRoom air temp F 26.7C Fan speed High Horizontal distance ft Air Electrical Data Electrical CharacteristicsC3082 Voltage230V Cooling Voltage208V CoolingC3682 Voltage230V Cooling Electric Wiring Diagrams KS3082 KS36828FA2-5250-70400-3 Noise Filter P.C.BOARD 8FA2-5250-71800Functions Operation FunctionsEmergency operation Lamp colors Timer backupSwitching Procedure to Noise Reducing Control Noise Reducing Control Outdoor UnitOperation Sound Maximum Current Value Change Function Maximum Current Value Change ProcedureDescription of function C3682Compressor discharge temperature FC Compressor discharge temperature controlProtective Functions Freeze preventionTroubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Self-diagnostics Lamps Normal Replace the controllerReplace the circuit board or the fuse Using the TEST/T-RUN terminals Checking the Indoor and Outdoor UnitsChecking the indoor unit Control Check items unit operation Alarm Code E05 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Noise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Locations most susceptible to noise Trouble CorrectionChecking Electrical Components Power Supply CordMeasurement of Insulation Resistance Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy Characteristics of New Refrigerant R410A Refrigerant R410A Special Precautions When Servicing UnitWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorUnit. This may cause Never charge a large amountDamage to the compressor ExampleCase Refrigerant is Leaking Welding leaking pointsRecharging Charging Additional Refrigerant When Tubes are ExtendedRetro-Fitting Existing Systems Use of Existing UnitsOI-852-6-4181-150-00-0 Pub. OI-85264181150000 Sanyo Mode D’EMPLOIContents FeaturesInstallation Location Alert SymbolsSafety Instructions Product InformationUnit Display and Operation Button Names of PartsSymbols Remote Control Unit DisplayRemote Control Unit Temperature setting buttons Temp HR. Timer button 1-HOUR OFF TimerMode selector button High Power buttonAir conditioner Indoor unit Receiver Remote control unit Using the Remote Control UnitACL button 16 mmOperation with the Remote Control Unit Automatic fan speedManual fan speed Cooling and DRY Mode Unoccupied Indication Status Cooling ModeSpecial Remarks Setting the TimerHow it works? Clicking sound is heard from the air conditioner1030 pm 710 am 1100 am Present time To cancel a timer programAdjusting the Airflow Direction Using the 1-HOUR OFF TimerTips for Energy Saving Do notCare and Cleaning How to clean the air clean filter How to install the air clean filterCleaning the main unit and remote control unit Removing and remounting the front panelWired Remote Controller TroubleshootingOperating Range Trouble Possible Cause RemedyAppendix B Installation Instructions Contents Installation InstructionsPlease Read Before Starting Accessories Supplied with Unit Table Tools Required for Installation not suppliedGeneral Optional Copper Tubing KitAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate Countermeasures against snow and wind Precautions for Installation in a Snowy AreaUnit inch Installation with intakes facing outlets Required space around the outdoor unitFront and both sides must remain open Unit Top is open Single-unit installation Multiple-unit installation 2 or more unitsObstacle to the front of unit Obstacles to the front and rear of unit Installation in front-rear rowsTrical wiring or conduits are How to Install the Indoor UnitRemove the Rear Panel from the Unit Make a HoleIf Wooden Wall Install the Rear Panel on the WallIf Block, Brick, Concrete or Similar Type Wall Hole DiaRemoving and Installing the Grille How to remove the grilleHow to replace the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringModel Wire Size and LengthC3682 Fuse or CircuitWiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Right-side tubing MountingSwitching drain hose and drain cap Left-side tubingDrain cap Tubing and wiring to the out Do not supply power toTo unmount indoor unit Frame Fastening MethodFirst refer to . Installation Site Selection How to Install the Outdoor UnitWiring Instructions for the Outdoor Unit Routing the Tubing and WiringRefrigerant Tubing Flaring Procedure with a Flare ToolUse of the Flaring Method If the special R410A flare tool is usedFinishing the Installation Connecting Tubing between Indoor and Outdoor UnitsInsulation of Refrigerant Tubing Taping the TubesAir Purging Be sure to completely insert Hex wrench beforeAttempting to turn the valve How to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesRemote Control Unit Installation Position Service Valve ConnectionsAddress Setting of the Remote Control Unit Address Switch