Sanyo C3082, C3682 service manual 34,000 BTU/h

Page 23

Indoor Unit

:

KS3682

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

:

C3682

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

 

< Cooling Capacity (Low Ambient) >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

34,000 BTU/h

 

AIR FLOW RATE:

 

630 CFM

 

 

 

INDOOR

 

 

 

 

 

OUTDOOR

 

 

 

 

 

ENT. TEMP. oF (oC)

 

 

 

 

AMBIENT TEMP. oF (oC)

 

 

 

 

 

W.B.

D.B.

 

 

0

5

15

25

 

35

45

55

 

 

 

 

 

 

 

 

(-17.8)

(-15.0)

(-9.4)

(-3.9)

 

(1.7)

(7.2)

(12.8)

 

 

 

 

 

 

TC

 

30,900

30,870

30,800

30,710

 

30,590

30,400

30,210

 

 

 

 

72

(22.2)

SHC

 

21,510

21,510

21,510

21,510

 

21,390

21,270

21,150

 

 

 

59

76

(24.4)

SHC

 

23,960

23,840

23,840

23,840

 

23,710

23,590

23,470

 

 

(15.0)

80

(26.7)

SHC

 

26,400

26,400

26,280

26,280

 

26,160

26,040

25,920

 

 

 

 

84

(28.9)

SHC

 

28,730

28,730

28,610

28,610

 

28,480

28,480

28,360

 

 

 

 

88

(31.1)

SHC

 

30,900

30,870

30,800

30,710

 

30,590

30,400

30,210

 

 

 

 

 

 

TC

 

31,010

31,010

30,990

30,950

 

30,890

30,750

30,620

 

 

 

 

72

(22.2)

SHC

 

17,970

17,970

17,970

17,970

 

17,970

17,840

17,840

 

 

 

63

76

(24.4)

SHC

 

20,410

20,410

20,290

20,290

 

20,290

20,170

20,170

 

 

(17.2)

80

(26.7)

SHC

 

22,860

22,860

22,740

22,740

 

22,740

22,610

22,610

 

 

 

 

84

(28.9)

SHC

 

25,180

25,180

25,180

25,060

 

25,060

25,060

24,940

 

 

 

 

88

(31.1)

SHC

 

27,510

27,510

27,510

27,510

 

27,380

27,380

27,260

 

 

 

 

 

 

TC

 

30,910

30,940

30,980

31,000

 

31,010

30,930

30,880

 

 

 

 

72

(22.2)

SHC

 

14,420

14,420

14,420

14,420

 

14,420

14,420

14,420

 

 

 

67

76

(24.4)

SHC

 

16,740

16,740

16,740

16,740

 

16,740

16,740

16,740

 

 

(19.4)

80

(26.7)

SHC

 

19,190

19,190

19,190

19,190

 

19,190

19,190

19,190

 

 

 

 

84

(28.9)

SHC

 

21,510

21,510

21,640

21,640

 

21,640

21,510

21,510

 

 

 

 

88

(31.1)

SHC

 

23,840

23,960

23,960

23,960

 

23,960

23,960

23,840

 

 

 

 

 

 

TC

 

30,570

30,620

30,730

30,820

 

30,910

30,900

30,930

 

 

 

 

72

(22.2)

SHC

 

10,630

10,630

10,750

10,750

 

10,750

10,750

10,750

 

 

 

71

76

(24.4)

SHC

 

12,950

12,950

13,070

13,070

 

13,070

13,070

13,070

 

 

(21.7)

80

(26.7)

SHC

 

15,400

15,400

15,520

15,520

 

15,520

15,520

15,520

 

 

 

 

84

(28.9)

SHC

 

17,720

17,840

17,840

17,840

 

17,970

17,970

17,970

 

 

 

 

88

(31.1)

SHC

 

20,170

20,170

20,170

20,170

 

20,290

20,290

20,290

 

 

 

 

 

 

TC

 

30,010

30,090

30,260

30,430

 

30,590

30,650

30,770

 

 

 

75

76

(24.4)

SHC

 

9,410

9,410

9,530

9,530

 

9,650

9,650

9,650

 

 

(23.9)

80

(26.7)

SHC

 

11,850

11,850

11,970

11,970

 

12,100

12,100

12,100

 

 

 

 

84

(28.9)

SHC

 

14,180

14,180

14,300

14,300

 

14,420

14,420

14,420

 

 

 

 

88

(31.1)

SHC

 

16,500

16,620

16,620

16,740

 

16,740

16,740

16,870

 

 

 

 

 

 

TC :

Total Cooling Capacity (BTU/h)

SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.

2.Above data represents the value when the operation frequency of a compressor is fixed.

23

Image 23
Contents Destination North America Indoor Model No. Product Code NoSafety Precautions Prohibit Table of Contents Checking Electrical Components Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeC3082 SpecificationsUnit Specifications KS3082208V C3682 KS368221.9 Indoor Unit Major Component SpecificationsCB-KS3682 Microprocessor 250V 3A Compressor Outdoor UnitOutdoor Unit C3082 BoardOutdoor Unit C3682 Other Component Specifications Indoor Unit KS3082 Dimensional DataInchmm Refrigerant Flow Diagram Refrigerant Flow DiagramIndoor discharge air performance chart Temperature ChartsLow pressure performance chart Operating current performance chartWide Indoor Outdoor Cooling CapacityIndoor Cooling Capacity34,000 BTU/h Indoor Power Supply 230V Single Phase 60Hz Cooling CapacityRoom air temp F 26.7C Fan speed High Horizontal distance ft Air Throw Distance ChartsCooling Vertical distance ft Air Voltage208V Cooling Electrical CharacteristicsElectrical Data C3082 Voltage230V CoolingC3682 Voltage230V Cooling 8FA2-5250-70400-3 Electric Wiring DiagramsKS3082 KS3682 Noise Filter P.C.BOARD 8FA2-5250-71800Emergency operation FunctionsOperation Functions Lamp colors Timer backupOperation Sound Switching Procedure to Noise Reducing ControlNoise Reducing Control Outdoor Unit C3682 Maximum Current Value Change ProcedureMaximum Current Value Change Function Description of functionFreeze prevention Compressor discharge temperature controlCompressor discharge temperature FC Protective FunctionsMethod of Self-Diagnostics TroubleshootingPrecautions before Performing Inspection or Repair Self-diagnostics Lamps Replace the circuit board or the fuse NormalReplace the controller Checking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Before the Operation Serial Communication Error Identification ProcedureAlarm Code E05 Off Blinking IlluminatedTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Locations most susceptible to noise Trouble Correction Noise Malfunction and Electromagnetic InterferenceNoise malfunction Electromagnetic interferenceMeasurement of Insulation Resistance for Electrical Parts Power Supply CordChecking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Assy Characteristics Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A What is New Refrigerant R410A?Checklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorExample Never charge a large amountUnit. This may cause Damage to the compressorRecharging Case Refrigerant is LeakingWelding leaking points Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing SystemsOI-852-6-4181-150-00-0 Pub. OI-85264181150000 Sanyo Mode D’EMPLOIContents FeaturesProduct Information Alert SymbolsInstallation Location Safety InstructionsUnit Display and Operation Button Names of PartsSymbols Remote Control Unit DisplayRemote Control Unit High Power button HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp Mode selector button16 mm Using the Remote Control UnitAir conditioner Indoor unit Receiver Remote control unit ACL buttonManual fan speed Operation with the Remote Control UnitAutomatic fan speed Cooling and DRY Mode Unoccupied Indication Status Cooling ModeClicking sound is heard from the air conditioner Setting the TimerSpecial Remarks How it works?1030 pm 710 am 1100 am Present time To cancel a timer programDo not Using the 1-HOUR OFF TimerAdjusting the Airflow Direction Tips for Energy SavingCare and Cleaning Removing and remounting the front panel How to install the air clean filterHow to clean the air clean filter Cleaning the main unit and remote control unitTrouble Possible Cause Remedy TroubleshootingWired Remote Controller Operating RangeAppendix B Installation Instructions Contents Installation InstructionsPlease Read Before Starting Optional Copper Tubing Kit Tools Required for Installation not suppliedAccessories Supplied with Unit Table GeneralAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate Countermeasures against snow and wind Precautions for Installation in a Snowy AreaUnit inch Front and both sides must remain open Installation with intakes facing outletsRequired space around the outdoor unit Unit Obstacle to the front of unit Top is open Single-unit installationMultiple-unit installation 2 or more units Obstacles to the front and rear of unit Installation in front-rear rowsMake a Hole How to Install the Indoor UnitTrical wiring or conduits are Remove the Rear Panel from the UnitHole Dia Install the Rear Panel on the WallIf Wooden Wall If Block, Brick, Concrete or Similar Type WallHow to replace the grille Removing and Installing the GrilleHow to remove the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringFuse or Circuit Wire Size and LengthModel C3682Wiring Instructions for Inter-unit Connections For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit For solid core wiring or F-cable Right-side tubing MountingDrain cap Switching drain hose and drain capLeft-side tubing Frame Fastening Method Do not supply power toTubing and wiring to the out To unmount indoor unitRouting the Tubing and Wiring How to Install the Outdoor UnitFirst refer to . Installation Site Selection Wiring Instructions for the Outdoor UnitIf the special R410A flare tool is used Flaring Procedure with a Flare ToolRefrigerant Tubing Use of the Flaring MethodTaping the Tubes Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Insulation of Refrigerant TubingAir Purging Attempting to turn the valve Be sure to completely insertHex wrench before How to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesRemote Control Unit Installation Position Service Valve ConnectionsAddress Setting of the Remote Control Unit Address Switch