6. Air Purging

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.

pressure in the system rises

operating current rises

cooling (or heating) efficiency drops

moisture in the air may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant system

Air Purging with a Vacuum Pump (for Test Run)

(1)Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.

(2)Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both nar- row and wide tubes.

(3)Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig. 57)

 

CAUTION

The service port on the wide tube

 

 

 

service valve uses a Schrader core

 

 

 

 

 

 

valve to access the refrigerant sys-

 

 

 

tem. The valve core is similar to

 

 

 

those used in automobile tires.

 

 

 

Therefore, be sure to use a vacuum

 

 

 

hose connector which has a push-

 

 

 

pin inside.

 

 

 

Be sure to use a manifold valve

 

CAUTION

 

 

for air purging. If it is not avail-

 

 

 

 

 

 

 

 

able, use a stop valve (field sup-

 

 

 

ply) for this purpose. The “Hi”

 

 

 

knob of the manifold valve must

 

 

 

always be kept closed.

(4)With the “Lo” knob of the manifold valve open, run the vacuum pump. The operation time for the vacu- um pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:

Table 7

Required time for evacuation when 100 liter/h vacuum pump is used

If tubing length is

If tubing length is

less than 33 ft. (10 m)

more than 33 ft. (10 m)

 

 

10 min. or more

15 min. or more

 

 

Indoor unit

Outdoor unit

Manifold valve (Exclusively for R410A)

Pressure

Lo

Hi

gauge

 

 

Charging hose

(Exclusively for R410A)

Vacuum pump adapter (Exclusively for R410A)

(with reverse flow prevention)

Vacuum pump

Fig. 57

NOTE

To prevent other refrigerants from being mistakenly charged to units which use R410A, the size of the charge port on the service valve is different from the one for other refrigerant types. For servicing such as recharging, the specified charging hose, manifold and vacuum pump adapter (with reverse flow prevention) for R410A must be used.

NOTE

The required time in Table 7 is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.

25

Image 98
Contents Indoor Model No. Product Code No Destination North AmericaSafety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Indoor Air Intake Temp Outdoor Air Intake TempKS3082 SpecificationsUnit Specifications C3082208V KS3682 C368221.9 Major Component Specifications Indoor UnitCB-KS3682 Microprocessor 250V 3A Board Outdoor UnitOutdoor Unit C3082 CompressorOutdoor Unit C3682 Other Component Specifications Dimensional Data Indoor Unit KS3082Inchmm Refrigerant Flow Diagram Refrigerant Flow DiagramOperating current performance chart Temperature ChartsLow pressure performance chart Indoor discharge air performance chartWide Cooling Capacity Indoor OutdoorCooling Capacity Indoor34,000 BTU/h Power Supply 230V Single Phase 60Hz Cooling Capacity IndoorRoom air temp F 26.7C Fan speed High Horizontal distance ft Air Throw Distance ChartsCooling Vertical distance ft Air C3082 Voltage230V Cooling Electrical CharacteristicsElectrical Data Voltage208V CoolingC3682 Voltage230V Cooling 8FA2-5250-70400-3 Electric Wiring DiagramsKS3082 KS3682 8FA2-5250-71800 Noise Filter P.C.BOARDEmergency operation FunctionsOperation Functions Timer backup Lamp colorsOperation Sound Switching Procedure to Noise Reducing ControlNoise Reducing Control Outdoor Unit Description of function Maximum Current Value Change ProcedureMaximum Current Value Change Function C3682Protective Functions Compressor discharge temperature controlCompressor discharge temperature FC Freeze preventionMethod of Self-Diagnostics TroubleshootingPrecautions before Performing Inspection or Repair Self-diagnostics Lamps Replace the circuit board or the fuse NormalReplace the controller Checking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Off Blinking Illuminated Serial Communication Error Identification ProcedureAlarm Code E05 Before the OperationTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Trouble Diagnosis of Fan Motor Indoor Fan MotorOutdoor Fan Motor Electromagnetic interference Noise Malfunction and Electromagnetic InterferenceNoise malfunction Locations most susceptible to noise Trouble CorrectionMeasurement of Insulation Resistance Power Supply CordChecking Electrical Components Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy What is New Refrigerant R410A? Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A CharacteristicsChecklist before Servicing Tubing Installation Procedures Tools Specifically for R410AProcedure for Replacing Compressor Case of Compressor MalfunctionDamage to the compressor Never charge a large amountUnit. This may cause ExampleRecharging Case Refrigerant is LeakingWelding leaking points Retro-Fitting Existing Systems When Tubes are ExtendedCharging Additional Refrigerant Use of Existing UnitsOI-852-6-4181-150-00-0 Mode D’EMPLOI Pub. OI-85264181150000 SanyoFeatures ContentsSafety Instructions Alert SymbolsInstallation Location Product InformationNames of Parts Unit Display and Operation ButtonRemote Control Unit Display SymbolsRemote Control Unit Mode selector button HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp High Power buttonACL button Using the Remote Control UnitAir conditioner Indoor unit Receiver Remote control unit 16 mmManual fan speed Operation with the Remote Control UnitAutomatic fan speed Cooling and DRY Mode Cooling Mode Unoccupied Indication StatusHow it works? Setting the TimerSpecial Remarks Clicking sound is heard from the air conditionerTo cancel a timer program 1030 pm 710 am 1100 am Present timeTips for Energy Saving Using the 1-HOUR OFF TimerAdjusting the Airflow Direction Do notCare and Cleaning Cleaning the main unit and remote control unit How to install the air clean filterHow to clean the air clean filter Removing and remounting the front panelOperating Range TroubleshootingWired Remote Controller Trouble Possible Cause RemedyAppendix B Installation Instructions Installation Instructions ContentsPlease Read Before Starting General Tools Required for Installation not suppliedAccessories Supplied with Unit Table Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationSolid base must not cover the hole of the bottom plate Precautions for Installation in a Snowy Area Countermeasures against snow and windUnit inch Front and both sides must remain open Installation with intakes facing outletsRequired space around the outdoor unit Unit Obstacle to the front of unit Top is open Single-unit installationMultiple-unit installation 2 or more units Installation in front-rear rows Obstacles to the front and rear of unitRemove the Rear Panel from the Unit How to Install the Indoor UnitTrical wiring or conduits are Make a HoleIf Block, Brick, Concrete or Similar Type Wall Install the Rear Panel on the WallIf Wooden Wall Hole DiaHow to replace the grille Removing and Installing the GrilleHow to remove the grille Wiring Instructions General precautions on wiring Shape the Indoor Side TubingC3682 Wire Size and LengthModel Fuse or CircuitWiring Instructions for Inter-unit Connections For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit For solid core wiring or F-cable Mounting Right-side tubingDrain cap Switching drain hose and drain capLeft-side tubing To unmount indoor unit Do not supply power toTubing and wiring to the out Frame Fastening MethodWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitFirst refer to . Installation Site Selection Routing the Tubing and WiringUse of the Flaring Method Flaring Procedure with a Flare ToolRefrigerant Tubing If the special R410A flare tool is usedInsulation of Refrigerant Tubing Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Taping the TubesAir Purging Attempting to turn the valve Be sure to completely insertHex wrench before How to Test Run the Air Conditioner Basic Functions of the Service Valves Pump DownService Valve Connections Remote Control Unit Installation PositionAddress Switch Address Setting of the Remote Control Unit