Sanyo C3082, C3682 service manual Noise Reducing Control Outdoor Unit, Operation Sound

Page 33

Noise Reducing Control (Outdoor Unit)

The noise reducing control is the function used for silent operation of the air conditioner by means of setting the dip switch on the outdoor unit P.C.Board to control the fan and compressor's motor speed.

NOTE When this function is used, the cooling ability is slightly degraded. Therefore, when this function is to be enabled, make sure to receive the approval of the client.

<Operation Sound>

Specifications

Noise Reducing Control

(Fan's motor speed : 500rpm)

 

Cooling

Cooling

55 dB-A

47 dB-A

<In Cooling Operation>

Outdoor Air Temp. [°C]

 

Normal Operation

33

 

Normal Operation or

 

 

Noise Reducing Operation is kept.

28(Initial setting is the normal operation.)

Noise Reducing Operation

NOTE 1. In the test operation, high-power operation, defrost operation or low ambient cooling operation (to be cancelled at the outside temperature of 14 °C or less, or 17 °C or more), the noise reducing control is not available.

2.In the noise reducing operation, the fan's maximum motor speed is limited to 500rpm. Also, the maximum frequency (Hz) is controlled in the cooling (30Hz) or heating operation (30Hz).

<Switching Procedure to Noise Reducing Control>

(1)Remove the 3 screws fixing the inspection panel and remove the inspection panel. (Fig. 2)

(2)When the switch No. 1 of the dip switch (SW01) on the control P.C.Board is turned ON, the noise reducing control is enabled. (Fig. 3)

Control P.C.Board Inspection panel

Slide downward

Power lamp

SW01

Fig.3 Control P.C.Board

ON

1 2

Dip switch (SW01)

Fig.2 View from front

33

Image 33
Contents Destination North America Indoor Model No. Product Code NoSafety Precautions Prohibit Table of Contents Checking Electrical Components Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeUnit Specifications SpecificationsKS3082 C3082208V C3682 KS368221.9 Indoor Unit Major Component SpecificationsCB-KS3682 Microprocessor 250V 3A Outdoor Unit C3082 Outdoor UnitBoard CompressorOutdoor Unit C3682 Other Component Specifications Indoor Unit KS3082 Dimensional DataInchmm Refrigerant Flow Diagram Refrigerant Flow DiagramLow pressure performance chart Temperature ChartsOperating current performance chart Indoor discharge air performance chartWide Indoor Outdoor Cooling CapacityIndoor Cooling Capacity34,000 BTU/h Indoor Power Supply 230V Single Phase 60Hz Cooling CapacityAir Throw Distance Charts Cooling Vertical distance ftRoom air temp F 26.7C Fan speed High Horizontal distance ft Air Electrical Data Electrical CharacteristicsC3082 Voltage230V Cooling Voltage208V CoolingC3682 Voltage230V Cooling Electric Wiring Diagrams KS3082 KS36828FA2-5250-70400-3 Noise Filter P.C.BOARD 8FA2-5250-71800Functions Operation FunctionsEmergency operation Lamp colors Timer backupSwitching Procedure to Noise Reducing Control Noise Reducing Control Outdoor UnitOperation Sound Maximum Current Value Change Function Maximum Current Value Change ProcedureDescription of function C3682Compressor discharge temperature FC Compressor discharge temperature controlProtective Functions Freeze preventionTroubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Self-diagnostics Lamps Normal Replace the controllerReplace the circuit board or the fuse Using the TEST/T-RUN terminals Checking the Indoor and Outdoor UnitsChecking the indoor unit Control Check items unit operation Alarm Code E05 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Noise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Locations most susceptible to noise Trouble CorrectionChecking Electrical Components Power Supply CordMeasurement of Insulation Resistance Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy Characteristics of New Refrigerant R410A Refrigerant R410A Special Precautions When Servicing UnitWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorUnit. This may cause Never charge a large amountDamage to the compressor ExampleCase Refrigerant is Leaking Welding leaking pointsRecharging Charging Additional Refrigerant When Tubes are ExtendedRetro-Fitting Existing Systems Use of Existing UnitsOI-852-6-4181-150-00-0 Pub. OI-85264181150000 Sanyo Mode D’EMPLOIContents FeaturesInstallation Location Alert SymbolsSafety Instructions Product InformationUnit Display and Operation Button Names of PartsSymbols Remote Control Unit DisplayRemote Control Unit Temperature setting buttons Temp HR. Timer button 1-HOUR OFF TimerMode selector button High Power buttonAir conditioner Indoor unit Receiver Remote control unit Using the Remote Control UnitACL button 16 mmOperation with the Remote Control Unit Automatic fan speedManual fan speed Cooling and DRY Mode Unoccupied Indication Status Cooling ModeSpecial Remarks Setting the TimerHow it works? Clicking sound is heard from the air conditioner1030 pm 710 am 1100 am Present time To cancel a timer programAdjusting the Airflow Direction Using the 1-HOUR OFF TimerTips for Energy Saving Do notCare and Cleaning How to clean the air clean filter How to install the air clean filterCleaning the main unit and remote control unit Removing and remounting the front panelWired Remote Controller TroubleshootingOperating Range Trouble Possible Cause RemedyAppendix B Installation Instructions Contents Installation InstructionsPlease Read Before Starting Accessories Supplied with Unit Table Tools Required for Installation not suppliedGeneral Optional Copper Tubing KitAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate Countermeasures against snow and wind Precautions for Installation in a Snowy AreaUnit inch Installation with intakes facing outlets Required space around the outdoor unitFront and both sides must remain open Unit Top is open Single-unit installation Multiple-unit installation 2 or more unitsObstacle to the front of unit Obstacles to the front and rear of unit Installation in front-rear rowsTrical wiring or conduits are How to Install the Indoor UnitRemove the Rear Panel from the Unit Make a HoleIf Wooden Wall Install the Rear Panel on the WallIf Block, Brick, Concrete or Similar Type Wall Hole DiaRemoving and Installing the Grille How to remove the grilleHow to replace the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringModel Wire Size and LengthC3682 Fuse or CircuitWiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Right-side tubing MountingSwitching drain hose and drain cap Left-side tubingDrain cap Tubing and wiring to the out Do not supply power toTo unmount indoor unit Frame Fastening MethodFirst refer to . Installation Site Selection How to Install the Outdoor UnitWiring Instructions for the Outdoor Unit Routing the Tubing and WiringRefrigerant Tubing Flaring Procedure with a Flare ToolUse of the Flaring Method If the special R410A flare tool is usedFinishing the Installation Connecting Tubing between Indoor and Outdoor UnitsInsulation of Refrigerant Tubing Taping the TubesAir Purging Be sure to completely insert Hex wrench beforeAttempting to turn the valve How to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesRemote Control Unit Installation Position Service Valve ConnectionsAddress Setting of the Remote Control Unit Address Switch