Sanyo C3682, C3082 service manual Power Supply 230V Single Phase 60Hz Cooling Capacity, Indoor

Page 24

Indoor Unit

:

KS3682

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

:

C3682

 

 

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

< Cooling Capacity >

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

34,000 BTU/h

 

AIR FLOW RATE:

630 CFM

 

 

INDOOR

 

 

 

 

OUTDOOR

 

 

 

 

ENT. TEMP. oF (oC)

 

 

AMBIENT TEMP. oF (oC)

 

 

 

 

W.B.

D.B.

 

65

75

85

95

105

115

 

 

 

 

 

 

(18.3)

(23.9)

(29.4)

(35.0)

(40.6)

(46.1)

 

 

 

 

 

TC

34,170

33,480

32,690

32,110

24,650

16,770

 

 

 

72

(22.2)

SHC

23,470

23,100

22,610

22,250

18,210

14,420

 

 

59

76

(24.4)

SHC

25,790

25,430

24,940

24,570

20,530

16,740

 

 

(15.0)

80

(26.7)

SHC

28,240

27,870

27,380

27,020

22,980

16,770

 

 

 

84

(28.9)

SHC

30,560

30,200

29,710

29,460

24,650

16,770

 

 

 

88

(31.1)

SHC

33,010

32,520

32,030

31,790

24,650

16,770

 

 

 

 

 

TC

35,010

34,360

33,600

33,100

24,850

16,910

 

 

 

72

(22.2)

SHC

20,170

19,800

19,310

19,070

15,030

11,480

 

 

63

76

(24.4)

SHC

22,490

22,120

21,760

21,390

17,360

13,810

 

 

(17.2)

80

(26.7)

SHC

24,940

24,570

24,200

23,840

19,800

16,250

 

 

 

84

(28.9)

SHC

27,260

26,890

26,530

26,280

22,120

16,910

 

 

 

88

(31.1)

SHC

29,580

29,220

28,850

28,610

24,450

16,910

 

 

 

 

 

TC

35,720

35,120

34,400

#

34,000

24,930

16,970

 

 

 

72

(22.2)

SHC

16,620

16,380

16,010

15,890

11,730

8,670

 

 

67

76

(24.4)

SHC

19,070

18,700

18,330

18,210

14,180

11,000

 

 

(19.4)

80

(26.7)

SHC

21,510

21,150

20,900

20,660

16,620

13,440

 

 

 

84

(28.9)

SHC

23,840

23,590

23,230

22,980

18,940

15,770

 

 

 

88

(31.1)

SHC

26,160

25,920

25,550

25,300

21,270

16,970

 

 

 

 

 

TC

36,270

35,710

35,040

34,780

24,870

16,950

 

 

 

72

(22.2)

SHC

13,070

12,830

12,460

12,340

8,430

5,610

 

 

71

76

(24.4)

SHC

15,400

15,150

14,790

14,790

10,750

7,940

 

 

(21.7)

80

(26.7)

SHC

17,840

17,600

17,360

17,230

13,200

10,380

 

 

 

84

(28.9)

SHC

20,170

19,920

19,680

19,560

15,520

12,710

 

 

 

88

(31.1)

SHC

22,490

22,250

22,000

21,880

17,840

15,030

 

 

 

 

 

TC

36,560

36,070

35,450

34,630

24,680

16,830

 

 

75

76

(24.4)

SHC

11,850

11,610

11,360

11,120

7,570

5,130

 

 

(23.9)

80

(26.7)

SHC

14,300

14,050

13,810

13,560

10,020

7,570

 

 

 

84

(28.9)

SHC

16,620

16,500

16,250

15,890

12,340

9,900

 

 

 

88

(31.1)

SHC

18,940

18,820

18,580

18,210

14,660

12,220

TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.

:Outdoor Ambient Temp. 95 °F (35 °C) D.B.

2.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.

3.Above data represents the value when the operation frequency of a compressor is fixed.

24

Image 24
Contents Indoor Model No. Product Code No Destination North AmericaSafety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Indoor Air Intake Temp Outdoor Air Intake TempSpecifications Unit SpecificationsKS3082 C3082208V KS3682 C368221.9 Major Component Specifications Indoor UnitCB-KS3682 Microprocessor 250V 3A Outdoor Unit Outdoor Unit C3082Board CompressorOutdoor Unit C3682 Other Component Specifications Dimensional Data Indoor Unit KS3082Inchmm Refrigerant Flow Diagram Refrigerant Flow DiagramTemperature Charts Low pressure performance chartOperating current performance chart Indoor discharge air performance chartWide Cooling Capacity Indoor OutdoorCooling Capacity Indoor34,000 BTU/h Power Supply 230V Single Phase 60Hz Cooling Capacity IndoorAir Throw Distance Charts Cooling Vertical distance ftRoom air temp F 26.7C Fan speed High Horizontal distance ft Air Electrical Characteristics Electrical DataC3082 Voltage230V Cooling Voltage208V CoolingC3682 Voltage230V Cooling Electric Wiring Diagrams KS3082 KS36828FA2-5250-70400-3 8FA2-5250-71800 Noise Filter P.C.BOARDFunctions Operation FunctionsEmergency operation Timer backup Lamp colorsSwitching Procedure to Noise Reducing Control Noise Reducing Control Outdoor UnitOperation Sound Maximum Current Value Change Procedure Maximum Current Value Change FunctionDescription of function C3682Compressor discharge temperature control Compressor discharge temperature FCProtective Functions Freeze preventionTroubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Self-diagnostics Lamps Normal Replace the controllerReplace the circuit board or the fuse Using the TEST/T-RUN terminals Checking the Indoor and Outdoor UnitsChecking the indoor unit Control Check items unit operation Serial Communication Error Identification Procedure Alarm Code E05Off Blinking Illuminated Before the OperationTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Trouble Diagnosis of Fan Motor Indoor Fan MotorOutdoor Fan Motor Noise Malfunction and Electromagnetic Interference Noise malfunctionElectromagnetic interference Locations most susceptible to noise Trouble CorrectionPower Supply Cord Checking Electrical ComponentsMeasurement of Insulation Resistance Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy Refrigerant R410A Special Precautions When Servicing Unit Characteristics of New Refrigerant R410AWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tubing Installation Procedures Tools Specifically for R410AProcedure for Replacing Compressor Case of Compressor MalfunctionNever charge a large amount Unit. This may causeDamage to the compressor ExampleCase Refrigerant is Leaking Welding leaking pointsRecharging When Tubes are Extended Charging Additional RefrigerantRetro-Fitting Existing Systems Use of Existing UnitsOI-852-6-4181-150-00-0 Mode D’EMPLOI Pub. OI-85264181150000 SanyoFeatures ContentsAlert Symbols Installation LocationSafety Instructions Product InformationNames of Parts Unit Display and Operation ButtonRemote Control Unit Display SymbolsRemote Control Unit HR. Timer button 1-HOUR OFF Timer Temperature setting buttons TempMode selector button High Power buttonUsing the Remote Control Unit Air conditioner Indoor unit Receiver Remote control unitACL button 16 mmOperation with the Remote Control Unit Automatic fan speedManual fan speed Cooling and DRY Mode Cooling Mode Unoccupied Indication StatusSetting the Timer Special RemarksHow it works? Clicking sound is heard from the air conditionerTo cancel a timer program 1030 pm 710 am 1100 am Present timeUsing the 1-HOUR OFF Timer Adjusting the Airflow DirectionTips for Energy Saving Do notCare and Cleaning How to install the air clean filter How to clean the air clean filterCleaning the main unit and remote control unit Removing and remounting the front panelTroubleshooting Wired Remote ControllerOperating Range Trouble Possible Cause RemedyAppendix B Installation Instructions Installation Instructions ContentsPlease Read Before Starting Tools Required for Installation not supplied Accessories Supplied with Unit TableGeneral Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationSolid base must not cover the hole of the bottom plate Precautions for Installation in a Snowy Area Countermeasures against snow and windUnit inch Installation with intakes facing outlets Required space around the outdoor unitFront and both sides must remain open Unit Top is open Single-unit installation Multiple-unit installation 2 or more unitsObstacle to the front of unit Installation in front-rear rows Obstacles to the front and rear of unitHow to Install the Indoor Unit Trical wiring or conduits areRemove the Rear Panel from the Unit Make a HoleInstall the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall Hole DiaRemoving and Installing the Grille How to remove the grilleHow to replace the grille Wiring Instructions General precautions on wiring Shape the Indoor Side TubingWire Size and Length ModelC3682 Fuse or CircuitWiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Mounting Right-side tubingSwitching drain hose and drain cap Left-side tubingDrain cap Do not supply power to Tubing and wiring to the outTo unmount indoor unit Frame Fastening MethodHow to Install the Outdoor Unit First refer to . Installation Site SelectionWiring Instructions for the Outdoor Unit Routing the Tubing and WiringFlaring Procedure with a Flare Tool Refrigerant TubingUse of the Flaring Method If the special R410A flare tool is usedConnecting Tubing between Indoor and Outdoor Units Finishing the InstallationInsulation of Refrigerant Tubing Taping the TubesAir Purging Be sure to completely insert Hex wrench beforeAttempting to turn the valve How to Test Run the Air Conditioner Basic Functions of the Service Valves Pump DownService Valve Connections Remote Control Unit Installation PositionAddress Switch Address Setting of the Remote Control Unit