3 Troubleshooting

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

Flame Out of

 

 

 

Sequence 1

 

• Check supply voltage for proper polarity.

(will require a manual

 

The flame detector 1 circuit is seeing a flame

• Check external wiring for voltage feedback.

reset once the condition

has been corrected.

signal while no flame is present.

• Check the internal wiring for bad connections.

Press the RESET button

 

 

 

 

on the SMART TOUCH

 

 

 

display to reset.)

 

 

 

 

 

 

Flame Out of

 

• Check combustion of burner 1 and adjust valve 1 if

 

 

necessary.

Sequence 2

 

• Check supply voltage for proper polarity.

(will require a manual

 

The flame detector 2 circuit is seeing a flame

• Check external wiring for voltage feedback.

reset once the condition

has been corrected.

signal from burner 1.

• Check the flame rod and make sure it is clean.

Press the RESET button

 

 

Check internal wiring for bad connections.

on the SMART TOUCH

 

 

Remove and inspect the burner.

display to reset.)

 

 

 

 

 

 

• Inspect flame rod 1 and associated wiring for damage

 

 

 

and connection. Reference page 34 of this manual for

 

 

 

removal and cleaning procedures. Replace if necessary.

 

 

• Check for proper electrical grounding of unit.

 

 

• Check incoming supply gas pressure. Natural and

 

 

 

L.P. gas pressures should be between 4 - 14 inches w.c.

Flame Failure

 

 

(1.0 - 3.5 kPa). Refer to Section 6 - Gas Connections of

 

 

the Crest Installation and Operation Manual for detailed

Running 1

 

 

information concerning the gas supply.

(will require a manual

The unit was running and lost the flame

• Verify that the plastic hose from the gas valve to the air

reset once the condition

has been corrected.

signal.

 

inlet is connected and is not damaged.

• Verify that the vent/air intake pipes are installed correctly

Press the RESET button

 

on the SMART TOUCH

 

 

and there are no obstructions.

display to reset.)

 

• Inspect flame sensor and associated wiring. Reference

 

 

 

 

 

page 34 of this manual for removal and cleaning

 

 

 

procedures. Replace if necessary.

 

 

Check combustion.

 

 

• Inspect the burner. Reference page 34 of this manual for

 

 

 

removal and cleaning procedures. Replace if necessary.

 

 

 

 