Service Manual
1 Service (continued)
Parameter table
Table 1B This table lists SMART TOUCH control module parameters and where to access them
Menu
SETUP | A | |
INITIAL | ||
|
SETPOINTS | B |
|
RESET |
|
OUTDOOR | C |
|
Sub | Parameter Name | See | Min | Max | Default | User | Installer |
|
|
|
|
| |||
Item | (as shown on the LCD screen) | Page | Value | Value | Value | Access | Access |
1 | Clock | 18 | N/A | N/A | N/A | Yes | Yes |
|
|
|
|
|
|
|
|
2 | Date | 18 | N/A | N/A | N/A | Yes | Yes |
|
|
|
|
|
|
|
|
3 | SH Setpoint | 18 | 32 | 185 | 120 | Yes | Yes |
|
|
|
|
|
|
|
|
4 | HWG Tank Setpoint | 18 | 32 | 185 | 120 | Yes | Yes |
|
|
|
|
|
|
|
|
5 | MRHL Setpoint | 18 | 32 | 205 | 205 | Yes | Yes |
|
|
|
|
|
|
|
|
6 | ARHL Setpoint | 18 | 32 | 200 | 200 | Yes | Yes |
|
|
|
|
|
|
|
|
7 | SH Setpoint at Low Outdoor Temp. | 19 | 32 | 185 | 180 | Yes | Yes |
|
|
|
|
|
|
|
|
8 | SH Setpoint at High Outdoor Temp. | 19 | 32 | 185 | 68 | Yes | Yes |
|
|
|
|
|
|
|
|
9 | Low Outdoor Temperature | 19 | 86 | 23 | Yes | Yes | |
|
|
|
|
|
|
|
|
10 | High Outdoor Temperature | 19 | 86 | 86 | Yes | Yes | |
|
|
|
|
|
|
|
|
11 | Boiler Pump Mode | 24 | N/A | N/A | N/A | No | Yes |
|
|
|
|
|
|
|
|
12 | System Pump Mode | 24 | N/A | N/A | N/A | No | Yes |
1 | SH Min User Setpoint | 18 | 32 | 185 | 32 | No | Yes |
|
|
|
|
|
|
|
|
2 | SH Max User Setpoint | 18 | 32 | 185 | 185 | No | Yes |
|
|
|
|
|
|
|
|
3 | SH Setpoint | 18 | 32 | 185 | 125 | Yes | Yes |
|
|
|
|
|
|
|
|
4 | SH Offset | 18 | 0 | 36 | 9.9 | No | Yes |
|
|
|
|
|
|
|
|
5 | SH Differential | 18 | 0 | 72 | 19.8 | No | Yes |
|
|
|
|
|
|
|
|
6 | HWG Tank Setpoint | 18 | 32 | 185 | 120 | Yes | Yes |
|
|
|
|
|
|
|
|
7 | HWG Tank Differential | 18 | 0 | 10 | 6.3 | No | Yes |
|
|
|
|
|
|
|
|
8 | MRHL Setting | 18 | 32 | 205 | 204.8 | Yes | Yes |
|
|
|
|
|
|
|
|
9 | ARHL Setting | 18 | 32 | 200 | 199.4 | Yes | Yes |
|
|
|
|
|
|
|
|
10 | HWG Minimum User Setpoint | 19 | 32 | 185 | 60 | No | Yes |
|
|
|
|
|
|
|
|
11 | HWG Maximum User Setpoint | 19 | 32 | 185 | 185 | No | Yes |
|
|
|
|
|
|
|
|
12 | HWG Boiler Setpoint | 19 | 32 | 185 | 180 | No | Yes |
|
|
|
|
|
|
|
|
13 | HWG Boiler Offset | 19 | 0 | 36 | 9.9 | No | Yes |
|
|
|
|
|
|
|
|
14 | HWG Boiler Differential | 19 | 0 | 72 | 185 | No | Yes |
1 | SH Setpoint at Low Outdoor Temp. | 19 | 32 | 185 | 180 | Yes | Yes |
|
|
|
|
|
|
|
|
2 | SH Setpoint at High Outdoor Temp | 19 | 32 | 185 | 68 | Yes | Yes |
|
|
|
|
|
|
|
|
3 | Low Outdoor Temperature | 19 | 86 | 23 | Yes | Yes | |
|
|
|
|
|
|
|
|
4 | High Outdoor Temperature | 19 | 86 | 86 | Yes | Yes | |
|
|
|
|
|
|
|
|
5 | Outdoor Air Shutdown | 19 | 32 | 122 | 79.7 | No | Yes |
|
|
|
|
|
|
|
|
6 | OA Shutdown Differential | 20 | 32 | 122 | 79.7 | No | Yes |
|
|
|
|
|
|
|
|
13