3 Troubleshooting (continued) |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
Table 3A Troubleshooting Chart - No Display |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| ||||||||
FAULT | CAUSE |
|
| CORRECTIVE ACTION |
| ||||||||
|
|
|
|
| |||||||||
| - No 120 vac supplied to unit. | • | Check external line switch, fuse, or breaker. |
| |||||||||
|
|
| • | Check position of ON/OFF switch. Turn switch to the | |||||||||
|
|
|
| ON position. |
|
|
|
|
|
| |||
|
|
| • Check 120 vac through the ON/OFF switch. |
| |||||||||
|
|
| • Check wiring | harness connection | between | display | |||||||
|
|
|
| board | and | main | control | board. Connect | |||||
No Display |
|
|
| harness at both points. |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| ||
- No voltage through the switch. | • | Replace switch. |
|
|
|
|
| ||||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
| |||||
| - Bad display board. | • | Replace board. |
|
|
|
|
| |||||
|
|
|
|
|
|
| |||||||
| - Bad main control board. | • | Replace the main control board. |
|
|
| |||||||
|
|
|
|
|
| ||||||||
| - Blown fuse. | • Replace | fuse | F2 on | the main control board, see | ||||||||
|
|
|
| page 38 of this manual. |
|
|
|
| |||||
|
|
|
|
|
|
|
| ||||||
| - Main control board temperature set point | • | Review temperature setting. |
|
|
|
| ||||||
| satisfied. |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| |||||||
| - Remote thermostat satisfied. | • | Review remote thermostat setting. |
|
|
| |||||||
No Burner |
|
|
|
|
|
|
|
|
|
|
|
| |
- Outside air temperature above Warm | • | Check | location of | outside | air | sensor. | Check | ||||||
Operation | |||||||||||||
Weather Shutdown (WWSD) set point for |
| resistance of outdoor air sensor and compare to Table | |||||||||||
|
| ||||||||||||
| main control board. |
| 3C on page 38 of this manual. |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| |||||
| - Unit locked out on fault. | • | Consult | display for | specific | fault. | Refer | to fault | |||||
|
|
|
| descriptions on page 40 of this manual for corrective | |||||||||
|
|
|
| actions. |
|
|
|
|
|
|
| ||
|
|
|
| ||||||||||
| - Ramp delay active. | • | Check ramp delay parameter settings. Optional PC | ||||||||||
|
|
|
| software required. |
|
|
|
|
| ||||
Unit Does Not |
|
|
|
|
|
|
|
|
|
|
|
| |
|
| • | Turn ramp delay feature off. | See page 20 of this | |||||||||
Modulate |
|
| |||||||||||
Up to 100% |
|
|
| manual for instructions on how to turn this feature off. | |||||||||
| - Boiler controlled by BMS. | • | Check BMS parameter settings. |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|