3 Troubleshooting (continued)

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

 

• Check the wiring connections to switch. Wires should

 

 

 

be connected to the common and normally open

 

 

 

terminals.

 

 

 

Remove switch and check for blockage in the orifice.

 

 

• Vent/air intake lengths exceed the maximum allowed

Blower Proving

 

 

lengths. Refer to Section 2 - General Venting of the

 

 

Crest Installation and Operation Manual for

Switch Open 2

 

 

proper lengths.

 

(will require a manual

 

• Check for obstruction or blockage in

the vent/air

reset once the condition

Pressure switch contacts are open.

 

intake pipes or at terminations.

 

has been corrected. Press

• Inspect the burner. Reference page 34 of this manual

the RESET button on the

 

 

 

for removal and cleaning procedures.

Replace if

display to reset.)

 

 

 

 

necessary.

 

 

 

 

 

 

 

• Verify combustion air blower 2 is operating. Replace if

 

 

 

necessary.

 

 

 

• Inspect the heat exchanger. Reference page 35 of

 

 

 

this manual for removal and cleaning procedures.

 

 

• Faulty pressure switch. Replace switch.

 

 

 

Burner Supply

 

• Inspect the combustion air temperature sensor and

Temperature

 

 

associated wiring.

 

Differential

Combustion air to burner 1 temperature

• Measure the resistance of the combustion air

(will require a manual

is higher than combustion air to burner 2

 

temperature sensor and compare to Table 3E on

reset once the condition

temperature or vice versa.

 

page 38 of this manual

 

has been corrected. Press

 

• Replace the sensor if necessary.

 

the RESET button on the

 

• Verify that the vent / air intake pipes

are properly

display to reset.)

 

 

installed and that there are no obstructions.

 

 

 

 

 

• Check if the vent backflow preventer is installed for

Burner Supply

 

 

boilers commonly vented.

 

Temperature

 

• Check if the vent backflow preventer is stuck open

High 1

 

 

while the unit is off.

 

(will require a manual

Combustion air temperature is very high.

• Inspect the combustion air temperature sensor and

reset once the condition

 

associated wiring.

 

 

 

 

has been corrected. Press

 

• Measure the resistance of the combustion air

the RESET button on the

 

 

temperature sensor and compare to Table 3E on

display to reset.)

 

 

page 38 of this manual.

 

 

 

Replace the sensor if necessary.

 

 

 

 

 

 

• Check if the vent backflow preventer is installed for

Burner Supply

 

 

boilers commonly vented.

 

Temperature

 

• Check if the vent backflow preventer is stuck open

High 2

 

 

while the unit is off.

 

(will require a manual

Combustion air temperature is very high.

• Inspect the combustion air temperature sensor and

reset once the condition

 

associated wiring.

 

 

 

 

has been corrected. Press

 

• Measure the resistance of the combustion air

the RESET button on the

 

 

temperature sensor and compare to Table 3E on

display to reset.)

 

 

page 38 of this manual.

 

 

 

Replace the sensor if necessary.

 

 

 

 

 

 