Service Manual
3 Troubleshooting
Checking temperature sensors
The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor
It is important to note that the flue and outlet inlet air - S11/S13 #1 and S12/S14 #2 water sensors have two temperature sensing devices in one housing. These devices are designated as S1/S9, outlet sensor and S3/S10, flue sensor. Please reference the wiring diagram in the Crest Installation and Operation Manual for correct terminal location.
Table 3B - Inlet Water/System Sensor Resistance vs. Temperature
Temperature Resistance Temperature Resistance
50 | 18,780 | 158 | 1,990 |
68 | 12,263 | 176 | 1,458 |
86 | 8,194 | 194 | 1,084 |
104 | 5,592 | 212 | 817 |
1223,893
1402,760
Table 3C - Outdoor Air Sensor Resistance vs. Temperature
Temperature | Resistance | Temperature | Resistance |
490,813 | 20 | 46,218 | |
336,606 | 30 | 34,558 | |
234,196 | 40 | 26,099 | |
165,180 | 50 | 19,900 | |
10 | 118,018 | 60 | 15,311 |
0 | 85,362 | 70 | 11,883 |
10 | 62,465 | 80 | 9,299 |
Table 3D - Outlet Water Sensor Resistance vs. Temperature
| Outlet |
| S1 |
|
| R/Y | Outlet |
| S9 |
| RW/Y |
| ||||
|
| S11 |
|
| GY/Y |
| S13 |
| BR/Y |
| ||||||
|
| S12 |
|
| BK/Y |
| S14 |
| T/Y |
| ||||||
| Temperature |
| Resistance |
| Temperature |
| Resistance | Temperature |
| Resistance |
| Temperature |
| Resistance |
| |
| 50 | 19,553 | 158 |
| 2,004 | 50 | 40,030 | 158 | 3,478 |
| ||||||
| 68 | 12,690 | 176 |
| 1,464 | 68 | 25,030 | 176 | 2,492 |
| ||||||
| 86 | 8,406 | 194 |
| 1,084 | 86 | 16,090 | 194 | 1,816 |
| ||||||
| 104 | 5,715 | 212 |
| 816 | 104 | 10,610 | 212 | 1,344 |
| ||||||
| 122 | 3,958 |
|
|
|
|
| 122 | 7,166 |
|
|
|
|
| ||
| 140 | 2,786 |
|
|
|
|
| 140 | 4,943 |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Table 3E - Flue Sensor Resistance vs. Temperature |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Flue |
| S3 |
|
| GY/Y | Flue |
| S10 |
| W/Y |
| ||||
| Temperature |
| Resistance |
| Temperature | Resistance | Temperature |
| Resistance |
| Temperature |
| Resistance |
| ||
| 50 |
| 40,030 |
| 158 |
| 3,478 | 50 |
| 258,500 |
| 158 |
| 16,870 |
| |
| 68 |
| 25,030 |
| 176 |
| 2,492 | 68 |
| 125,500 |
| 176 |
| 12,000 |
| |
| 86 |
| 16,090 |
| 194 |
| 1,816 | 86 |
| 80,220 |
| 194 |
| 8,674 |
| |
| 104 |
| 10,610 |
| 212 |
| 1,344 | 104 |
| 52,590 |
| 212 |
| 6,369 |
| |
| 122 |
| 7,166 |
|
|
|
|
| 122 |
| 35,270 |
|
|
|
|
|
| 140 |
| 4,943 |
|
|
|
|
| 140 |
| 24,160 |
|
|
|
|
|