| Service Manual |
| |
3 | Troubleshooting (continued) |
|
|
| |||
|
| ||||||
|
| ||||||
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface |
| ||||||
|
|
|
|
|
| ||
| FAULT | DESCRIPTION |
| CORRECTIVE ACTION |
| ||
|
|
|
|
| |||
|
|
|
| • Vent/air intake lengths exceed the maximum allowed | |||
|
|
|
| lengths. Refer to Section 2 - General Venting of the | |||
Fan Speed Low 1 |
|
| Crest Installation and Operation Manual | for | |||
|
| proper lengths. |
| ||||
| (will require a manual | The actual fan 1 RPM is 30% lower than | • Check for obstruction or blockage in the vent/air | ||||
reset once the condition | what is being called for. | intake pipes or at terminations. |
| ||||
has been corrected. Press |
|
| • Check the wiring connections at fan 1 and at | the | |||
the RESET button on the |
|
| |||||
|
| main control board. |
| ||||
SMART TOUCH display |
|
|
| ||||
|
| • Replace the fan. |
| ||||
| to reset.) |
|
|
| |||
|
|
|
|
| |||
|
| Blown fuse. | • Replace fuse F2 on the control board, see page 36 | ||||
|
| of this manual. |
| ||||
|
|
|
|
| |||
|
|
|
|
| |||
|
|
|
| • Vent/air intake lengths exceed the maximum allowed | |||
|
|
|
| lengths. Refer to Section 2 - General Venting of the | |||
|
|
|
| Crest Installation and Operation Manual | for | ||
Fan Speed Low 2 |
|
| proper lengths. |
| |||
| (will require a manual | The actual fan 2 RPM is 30% lower than | • Check for obstruction or blockage in the vent/air | ||||
reset once the condition | what is being called for. | intake pipes or at terminations. |
| ||||
has been corrected. Press |
|
| • Check the wiring connections at fan 2 and at | the | |||
the RESET button on the |
|
| |||||
|
| main control board. |
| ||||
SMART TOUCH display |
|
|
| ||||
|
| • Replace the fan. |
| ||||
| to reset.) |
|
|
| |||
|
|
|
|
| |||
|
| Blown fuse. | • Replace fuse F2 on the control board, see page 36 | ||||
|
| of this manual. |
| ||||
|
|
|
|
| |||
|
|
|
|
| |||
|
|
|
| • Vent/air intake lengths exceed the maximum allowed | |||
Fan Speed High 1 |
|
| lengths. Refer to Section 2 - General Venting of the | ||||
|
| Crest Installation and Operation Manual | for | ||||
| (will require a manual |
|
| proper lengths. |
| ||
reset once the condition | The actual fan 1 RPM is 30% higher than | • Check for obstruction or blockage in the vent/air | |||||
has been corrected. Press | |||||||
what is being called for. | intake pipes or at terminations. |
| |||||
the RESET button on the | • Check the wiring connections at the fan and at the | ||||||
SMART TOUCH display |
|
| |||||
|
| main control board. |
| ||||
| to reset.) |
|
|
| |||
|
|
|
|
|
| ||
|
|
|
| • Replace the fan. |
| ||
|
|
|
|
| |||
|
|
|
| • Vent/air intake lengths exceed the maximum allowed | |||
Fan Speed High 2 |
|
| lengths. Refer to Section 2 - General Venting of the | ||||
|
| Crest Installation and Operation Manual | for | ||||
| (will require a manual |
|
| proper lengths. |
| ||
reset once the condition | The actual fan 2 RPM is 30% higher than | • Check for obstruction or blockage in the vent/air | |||||
has been corrected. Press | |||||||
what is being called for. | intake pipes or at terminations. |
| |||||
the RESET button on the | • Check the wiring connections at the fan and at the | ||||||
SMART TOUCH display |
|
| |||||
|
| main control board. |
| ||||
| to reset.) |
|
|
| |||
|
|
|
|
|
| ||
|
|
|
| • Replace the fan. |
| ||
|
|
|
|
|
|
|
45