Table 3F Troubleshooting Chart - Noisy System

 

 

 

 

 

Service Manual

 

3 Troubleshooting (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3F Troubleshooting Chart - Noisy System

 

 

 

 

 

 

 

 

 

FAULT

CAUSE

 

CORRECTIVE ACTION

 

 

 

 

 

 

- Supply gas problem. Natural and LP gas

• Refer to Section 6 - Gas Connections of the Crest

 

 

pressures should be between 4 inches w.c.

Installation and Operation Manual for detailed

 

 

(1.0 kPa) and 14 inches w.c. (3.5 kPa).

information concerning the gas supply.

 

 

 

 

 

 

- Gas/air mixture problem.

• Refer to the Gas Valve Adjustment Procedure on

 

 

 

 

page 53 of this manual for the proper gas valve setting.

 

Noisy

 

 

Verify that the vent/air intake lengths do not exceed the

 

 

 

maximum listed in the General Venting section of the

 

Operation

 

 

 

 

 

Crest Installation and Operation Manual.

 

 

 

 

 

 

- Dirty/damaged burner.

• Refer to page 34 in this manual for the burner removal

 

 

 

 

and inspection procedure. Clean or replace the burner

 

 

 

 

as necessary.

 

 

 

 

 

 

- Air in the piping system.

• Properly purge all air from the piping system.

 

 

 

 

 

 

 

 

 

• Replace fuse F4 on the control board, see page 36 of

 

 

- Blown fuse.

this manual.

 

 

 

 

 

 

No Pump

 

 

 

 

- Faulty pump.

• Replace pump.

 

Operation -

 

 

 

 

Boiler Pump

 

 

• Replace main control board.

 

System Pump

- Internal fault on control board.

 

or

 

 

 

 

 

 

 

 

 

 

 

 

HWG Pump

- Faulty pump relay.

• Replace relay.

 

 

 

 

 

 

 

 

 

 

 

• Reference the Boiler Pump Mode and System

 

 

- Incorrect parameter setting.

Pump Mode parameters in the Service section of this

 

 

manual.

 

 

 

 

 

 

 

 

 

 

- System pressure exceeds relief valve

• Lower the system pressure below the rating of

 

Relief Valve

setting.

the supplied relief valve or replace the standard relief

 

 

 

valve with a higher rated valve up to the maximum

 

Opening

 

 

pressure of the heat exchanger 160 psi (40 kPa).

 

 

 

 

• Improperly sized expansion tank.

 

 

 

 

 

 

 

Noisy 39 No Pump