Service Manual

3 Troubleshooting

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 5 - Hydronic Piping of the

 

 

Crest

Installation

and

Operation

Manual

 

 

for the proper piping methods for the Crest boiler.

 

 

• Check 120 vac to boiler pump motor on a call for

 

 

heat. If voltage is not present, check wiring back to

 

 

the main control board.

 

 

 

 

 

• Check the ARHL set point.

 

 

Auto Reset

The outlet water temperature has exceeded

• If 120 vac is present on a call for heat and the boiler

the setting of the automatic reset high limit.

pump is not operating, replace the pump.

 

High Limit

 

 

 

 

 

 

• If the system pump is a variable speed pump, ensure

 

 

 

 

that the system flow is not less than the boiler flow.

 

 

• If operating on something other than an outlet sensor,

 

 

check temperature setting of the main control board.

 

 

• If the optional manual reset high limit has tripped,

 

 

check setting of the device.

 

 

 

 

• Check resistance of water sensors and compare to

 

 

Table 3B on page 38 of this manual. Replace

 

 

sensor if necessary.

 

 

 

 

 

• Replace the main control board.

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 5 - Hydronic Piping of the

 

 

Crest

Installation

and

Operation

Manual

 

 

for the proper piping methods for the Crest boiler.

 

 

• Check voltage to boiler pump motor on a call for

 

 

heat. If voltage is not present, check wiring back to

Manual Reset

 

the main control board.

 

 

 

 

• Replace the pump relay if necessary.

 

High Limit Open

 

• If 120 vac is present on a call for heat and the boiler

(will require a manual

The outlet water temperature has exceeded

pump is not operating, replace the pump.

 

reset once the condition

 

the setting of the high limit.

• If the system pump is a variable speed pump, ensure

has been corrected. Press

the RESET button on the

 

that the system flow is not less than the boiler flow.

SMART TOUCH display

 

• If operating on either an inlet or system supply sensor,

to reset.)

 

check temperature setting of the main control board.

 

 

• If the high limit has tripped, check setting of the

 

 

device and the MRHL set point.

 

 

 

 

• Check resistance of water sensors and compare to

 

 

Table 3B on page 38 of this manual. Replace

 

 

sensor if necessary.

 

 

 

 

 

• Replace high limit (if equipped).

 

 

 

• Replace main control board.

 

 

 

 

 

 

 

 

 

44

Page 44
Image 44
Lochinvar 1.5, 3.5, 2.5 service manual Auto Reset, Manual Reset, High Limit Open

3, 2, 3.5, 2.5, 1.5 specifications

Lochinvar is a leader in manufacturing high-efficiency water heating solutions, and their Lochinvar 1.5, 1.3, and 1.0 models exemplify the company's commitment to innovation and performance. These advanced heating systems are designed to meet the diverse needs of commercial and residential applications, providing reliable hot water while ensuring energy efficiency and environmental sustainability.

The Lochinvar 1.5, 1.3, and 1.0 models incorporate cutting-edge technologies that set them apart from traditional water heaters. One of the most notable features is their use of high-efficiency condensing technology, which extracts maximum heat from the combustion process. This process allows the units to achieve high thermal efficiencies, often exceeding 95%, which not only reduces energy costs but also lowers greenhouse gas emissions.

In terms of design, Lochinvar's models are constructed with durable materials, ensuring longevity and reliability in demanding environments. The stainless steel heat exchanger is a key element that contributes to the durability and performance of the units. This material is resistant to corrosion and scale build-up, enhancing the lifespan of the heater and reducing maintenance requirements.

The Lochinvar 1.5, 1.3, and 1.0 models feature advanced control systems that provide precise temperature management and easy operation. The intuitive digital display allows users to monitor performance metrics, temperature settings, and energy consumption with ease. Additionally, these units are equipped with intelligent modulating gas valves that optimize fuel usage based on demand, ensuring efficient operation across various load conditions.

Safety is a priority in the design of Lochinvar's water heaters. The models come with built-in safety features, including flame failure detection, overheat protection, and venting safeguards. These systems work together to ensure the safe operation of the units, giving users peace of mind.

Another characteristic that makes the Lochinvar 1.5, 1.3, and 1.0 models popular among users is their compact design. These units are engineered to fit in tight spaces, making them ideal for installations where space is at a premium. Despite their small footprint, they deliver powerful performance, ensuring that users have access to the hot water they need.

In summary, Lochinvar's 1.5, 1.3, and 1.0 water heating models represent the pinnacle of efficiency, safety, and reliability. With their advanced technologies, durable construction, and user-friendly features, these units are an excellent choice for anyone seeking a high-performance water heating solution.