Service Manual
3 Troubleshooting (continued)
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT | DESCRIPTION |
| CORRECTIVE ACTION |
|
|
|
| ||
|
| • Verify that the boiler pump is set to the proper speed | ||
|
|
| or that the boiler pump is the proper size. Reference | |
|
|
| Section 5 - Hydronic Piping of the Knight | Boiler |
Outlet Temp |
|
| Installation and Operation Manual for boiler pump | |
High | Outlet water temperature has exceeded the |
| specifications. |
|
(continued) | maximum outlet water temperature. | • | Inspect the outlet sensors and associated wiring. | |
|
| |||
|
|
| Measure the resistance of the sensors and compare to | |
|
|
| the tables on page 38 of this manual. |
|
|
|
|
| |
|
| • Check set point of the external control. |
| |
|
| • Check the wiring between the external control and the | ||
Rem Ctrl Flt | External control is cycling too often. |
| unit. |
|
|
|
|
| |
|
| • Replace the control. |
| |
|
|
|
|
|
Parameters |
|
|
|
|
Saved |
|
|
|
|
(will require a manual |
|
|
|
|
reset once the condition | After downloading parameters from a laptop, | • Press the RESET button on the | SMART | |
has been corrected. Press | the main control board must be reset. |
| TOUCH display panel. |
|
the RESET button on the |
|
|
| |
SMART TOUCH display |
|
|
|
|
to reset.) |
|
|
|
|
|
|
| ||
| While the unit is in Service Mode, the outlet | • Establish a heating load to remove the heat from the | ||
| temperature has exceeded 185°F. |
| boiler loop. |
|
|
| • Verify that the system is full of water and that all air | ||
|
|
| has been properly purged from the system. |
|
|
| • Verify that the boiler is piped properly into the heating | ||
|
|
| system. Refer to Section 5 - Hydronic Piping of the | |
|
|
| Crest Installation and Operation Manual for the proper | |
Service Blk |
|
| piping methods for the Crest boiler. |
|
| • Check 120 vac to the boiler pump motor on a call for | |||
|
| |||
|
|
| heat. If voltage is not present, check the wiring back | |
|
|
| to the main control board. Replace the main control | |
|
|
| board if necessary. |
|
|
| • If 120 vac is present on a call for heat and the boiler | ||
|
|
| pump is not operating, replace the pump. |
|
|
| • Verify that the boiler pump is set to the proper speed | ||
|
|
| or that the boiler pump is the proper size. Reference | |
|
|
| Section 5 - Hydronic Piping of the Crest | |
|
|
| Installation and Operation Manual for | boiler |
|
|
| pump specifications. |
|
|
|
|
|
|
47