Service Manual
3 Troubleshooting (continued)
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION | |
|
|
| |
|
| • Inspect flame rod 2 and associated wiring for damage | |
|
| and connection. Reference page 34 of this manual for | |
|
| removal and cleaning procedures. Replace if | |
|
| necessary. | |
|
| • Check for proper electrical grounding of unit. | |
|
| • Check incoming supply gas pressure. Natural and | |
|
| L.P. gas pressures should be between 4 - 14 inches w.c. | |
Flame Failure |
| (1.0 - 3.5 kPa). Refer to Section 6 - Gas Connections of | |
| the Crest Installation and Operation Manual for detailed | ||
Running 2 |
| ||
| information concerning the gas supply. | ||
(will require a manual |
| ||
The unit was running and lost the flame | • Verify that the plastic hose from the gas valve to the air | ||
reset once the condition | |||
has been corrected. Press | signal. | inlet is connected and is not damaged. | |
the RESET button on the |
| • Verify that the vent/air intake pipes are installed correctly | |
SMART TOUCH display |
| and there are no obstructions. | |
to reset.) |
| • Inspect flame sensor and associated wiring. Reference | |
|
| ||
|
| page 34 of this manual for removal and cleaning | |
|
| procedures. Replace if necessary. | |
|
| • Check combustion. | |
|
| • Inspect the burner. Reference page 34 of this manual for | |
|
| removal and cleaning procedures. Replace if | |
|
| necessary. | |
|
|
| |
Gas Valve / Relay |
|
| |
Failure 1 |
| • Check wiring harness connection at the gas valve and | |
(will require a manual | The main control board did not detect gas | at the main control board. | |
reset once the condition | • Replace the gas valve wire harness. | ||
has been corrected. Press | valve 1. | • Replace the gas valve. | |
the RESET button on the |
| ||
SMART TOUCH display |
|
| |
to reset.) |
|
| |
|
|
| |
Gas Valve / Relay |
|
| |
Failure 2 |
| • Check wiring harness connection at the gas valve and | |
(will require a manual | The main control board did not detect gas | at the main control board. | |
reset once the condition | • Replace the gas valve wire harness. | ||
has been corrected. Press | valve 2. | • Replace the gas valve. | |
the RESET button on the |
| ||
SMART TOUCH display |
|
| |
to reset.) |
|
| |
|
|
|
43