Service Manual
1 Service
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to access them
Menu
OUTDOOR RESET | C |
|
DELAY | D | |
RAMP | ||
|
BMS | E |
|
Sub | Parameter Name | See | Min | Max | Default | User | Installer |
|
|
|
|
| |||
Item | (as shown on the LCD screen) | Page | Value | Value | Value | Access | Access |
7 | Boost Time | 20 | 0 | 250 | 20 | No | Yes |
|
|
|
|
|
|
|
|
8 | Boost Temperature | 20 | 0 | 25 | 0 | No | Yes |
|
|
|
|
|
|
|
|
9 | Shift OA Reset Curve | 20 | 27 | 0 | No | Yes | |
1 | Ramp Delay Mode | 20 | N/A | N/A | N/A | No | Yes |
|
|
|
|
|
|
|
|
2 | Ramp Delay Time #1 | 20 | 1 | 40 | 2 | No | Yes |
|
|
|
|
|
|
|
|
3 | Ramp Delay Time #2 | 20 | 1 | 40 | 2 | No | Yes |
|
|
|
|
|
|
|
|
4 | Ramp Delay Time #3 | 20 | 1 | 40 | 2 | No | Yes |
|
|
|
|
|
|
|
|
5 | Ramp Delay Time #4 | 20 | 1 | 40 | 1 | No | Yes |
|
|
|
|
|
|
|
|
6 | Ramp Delay Time #5 | 20 | 1 | 40 | 1 | No | Yes |
|
|
|
|
|
|
|
|
7 | Ramp Delay Time #6 | 20 | 1 | 40 | 1 | No | Yes |
|
|
|
|
|
|
|
|
8 | Ramp Delay Limit #1 | 20 | 10 | 100 | 20 | No | Yes |
|
|
|
|
|
|
|
|
9 | Ramp Delay Limit #2 | 20 | 10 | 100 | 30 | No | Yes |
|
|
|
|
|
|
|
|
10 | Ramp Delay Limit #3 | 20 | 10 | 100 | 40 | No | Yes |
|
|
|
|
|
|
|
|
11 | Ramp Delay Limit #4 | 20 | 10 | 100 | 55 | No | Yes |
|
|
|
|
|
|
|
|
12 | Ramp Delay Limit #5 | 20 | 10 | 100 | 75 | No | Yes |
|
|
|
|
|
|
|
|
13 | Ramp Delay Limit #6 | 20 | 10 | 100 | 100 | No | Yes |
1 | BMS Active/Inactive | 21 | ACTIVE | INACTIVE | INACTIVE | No | Yes |
|
|
|
|
|
|
|
|
2 | BMS Mode | 21 | POWER | SETPOINT | POWER | No | Yes |
|
|
|
|
|
|
|
|
3 | BMS Volts at Min Rate | 21 | 0 | 10 | 2 | No | Yes |
|
|
|
|
|
|
|
|
4 | BMS Volts at Max Rate | 21 | 0 | 10 | 10 | No | Yes |
|
|
|
|
|
|
|
|
5 | BMS Rate at Min Volts | 21 | 4 | 100 | 4 | No | Yes |
|
|
|
|
|
|
|
|
6 | BMS Rate at Max Volts | 21 | 0 | 100 | 100 | No | Yes |
|
|
|
|
|
|
|
|
7 | BMS Volts at Min Setpoint | 21 | 0 | 10 | 2 | No | Yes |
|
|
|
|
|
|
|
|
8 | BMS Volts at Max Setpoint | 21 | 0 | 10 | 10 | No | Yes |
|
|
|
|
|
|
|
|
9 | BMS Setpoint at Min Volts | 21 | 32 | 185 | 68.9 | No | Yes |
|
|
|
|
|
|
|
|
10 | BMS Setpoint at Max Volts | 21 | 32 | 185 | 178.7 | No | Yes |
|
|
|
|
|
|
|
|
11 | BMS Volts to Enable | 21 | 0 | 10 | 2 | No | Yes |
|
|
|
|
|
|
|
|
12 | Differential to Stop BMS Demand | 21 | 0 | 10 | 0.5 | No | Yes |
|
|
|
|
|
|
|
|
13 | BMS Enable Mode | 21 | ENABLE | VOLTAGE | VOLTAGE | No | Yes |
|
|
|
|
|
|
|
|
14