Lochinvar 1.5, 3.5, 2.5 service manual Service, Parameter table, Delay, Ramp

Models: 3.5 2.5 1.5

1 56
Download 56 pages 20.39 Kb
Page 14
Image 14
DELAY

Service Manual

1 Service

Parameter table

Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to access them

Menu

OUTDOOR RESET

C

 

DELAY

D

RAMP

 

BMS

E

 

Sub

Parameter Name

See

Min

Max

Default

User

Installer

 

 

 

 

 

Item

(as shown on the LCD screen)

Page

Value

Value

Value

Access

Access

7

Boost Time

20

0

250

20

No

Yes

 

 

 

 

 

 

 

 

8

Boost Temperature

20

0

25

0

No

Yes

 

 

 

 

 

 

 

 

9

Shift OA Reset Curve

20

-27

27

0

No

Yes

1

Ramp Delay Mode

20

N/A

N/A

N/A

No

Yes

 

 

 

 

 

 

 

 

2

Ramp Delay Time #1

20

1

40

2

No

Yes

 

 

 

 

 

 

 

 

3

Ramp Delay Time #2

20

1

40

2

No

Yes

 

 

 

 

 

 

 

 

4

Ramp Delay Time #3

20

1

40

2

No

Yes

 

 

 

 

 

 

 

 

5

Ramp Delay Time #4

20

1

40

1

No

Yes

 

 

 

 

 

 

 

 

6

Ramp Delay Time #5

20

1

40

1

No

Yes

 

 

 

 

 

 

 

 

7

Ramp Delay Time #6

20

1

40

1

No

Yes

 

 

 

 

 

 

 

 

8

Ramp Delay Limit #1

20

10

100

20

No

Yes

 

 

 

 

 

 

 

 

9

Ramp Delay Limit #2

20

10

100

30

No

Yes

 

 

 

 

 

 

 

 

10

Ramp Delay Limit #3

20

10

100

40

No

Yes

 

 

 

 

 

 

 

 

11

Ramp Delay Limit #4

20

10

100

55

No

Yes

 

 

 

 

 

 

 

 

12

Ramp Delay Limit #5

20

10

100

75

No

Yes

 

 

 

 

 

 

 

 

13

Ramp Delay Limit #6

20

10

100

100

No

Yes

1

BMS Active/Inactive

21

ACTIVE

INACTIVE

INACTIVE

No

Yes

 

 

 

 

 

 

 

 

2

BMS Mode

21

POWER

SETPOINT

POWER

No

Yes

 

 

 

 

 

 

 

 

3

BMS Volts at Min Rate

21

0

10

2

No

Yes

 

 

 

 

 

 

 

 

4

BMS Volts at Max Rate

21

0

10

10

No

Yes

 

 

 

 

 

 

 

 

5

BMS Rate at Min Volts

21

4

100

4

No

Yes

 

 

 

 

 

 

 

 

6

BMS Rate at Max Volts

21

0

100

100

No

Yes

 

 

 

 

 

 

 

 

7

BMS Volts at Min Setpoint

21

0

10

2

No

Yes

 

 

 

 

 

 

 

 

8

BMS Volts at Max Setpoint

21

0

10

10

No

Yes

 

 

 

 

 

 

 

 

9

BMS Setpoint at Min Volts

21

32

185

68.9

No

Yes

 

 

 

 

 

 

 

 

10

BMS Setpoint at Max Volts

21

32

185

178.7

No

Yes

 

 

 

 

 

 

 

 

11

BMS Volts to Enable

21

0

10

2

No

Yes

 

 

 

 

 

 

 

 

12

Differential to Stop BMS Demand

21

0

10

0.5

No

Yes

 

 

 

 

 

 

 

 

13

BMS Enable Mode

21

ENABLE

VOLTAGE

VOLTAGE

No

Yes

 

 

 

 

 

 

 

 

RAMP 14 Manual background

Page 14
Image 14