Operation | 30 |
|
|
|
|
the energy consumption state (see the Fault and Troubleshooting section for complete details):
Display- Display State | Description | |
TURBINE FAULT | Turbine is stopped and contains a GFI fault. | |
GFI | ||
| ||
TURBINE FAULT | Voltage sensed but Anemometer not sensing wind | |
NO WIND SPEED | speed. | |
TURBINE FAULT | Turbine is stopped and contains an over current fault. | |
TURBINE OVER CURRENT | ||
TURBINE FAULT | Turbine is stopped and contains an over temperature | |
TURBINE OVER VOLTAGE | fault. | |
TURBINE FAULT | Anemometer is sensing wind speed but there is no | |
NO TURBINE | voltage sensed. | |
TURBINE FAULT | Turbine is stopped and contains a low battery fault. | |
LOW BATT | ||
| ||
TURBINE FAULT | Turbine is stopped and contains a high battery fault. | |
HIGH BATT | ||
| ||
TURBINE FAULT | Turbine is stopped and contains an over temperature | |
OVER TEMP | fault. | |
TURBINE FAULT | Turbine is stopped and contains an over current fault. | |
CHARGE OVER CURRENT | ||
| ||
|
| |
TURBINE FAULT | See Figure 4.4 | |
INVERTER NO OUTPUT | ||
| ||
|
| |
TURBINE FAULT |
| |
INVERTER OVER | See Figure 4.4 | |
CURRENT |
|
Figure 4.3 Turbine Fault Stop States
•Turbine User Stop State
The turbine will enter its User Stop state if the user engages the manual stop command in the technician’s menu accessible via the SMARTBOX™ Controller. When the SMARTBOX™ Controller is in user mode, the turbine is immediately stopped. While in user stop mode, no A/C will be produced so the inverter is shut off and the transfer switch is switched back to the grid. The SMARTBOX™ Controller must be placed in run mode before a charge cycle can start again.
Display - Stopped State | Description |
TURBINE STOPPED | Turbine is stopped with no faults. Back light is off with |
PRESS ANY KEY | no information scroll. |
System Protection
•Cool Down
The turbine will shut off and begin cool down if the charger reaches or exceeds a temperature of 125°c or/and the enclosure reaches or exceeds a temperature of 60°c. The turbine will resume working after the charger temperature drops below 70°c and/ or the enclosure temperature drops below 45°c.
•Over Wind Speed
The turbine will turn off when wind speed reaches 42mph or higher. It will resume working after the wind speed drops to 35mph or lower.
SMARTBOX™ Controller for HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev14