Honeywell WT6500 owner manual System Faults, Non Grid-Tie SmartBox Fault Specifications

Page 38

31

Operation

 

 

 

 

System Faults

The SMARTBOX™ Controller constantly monitors the status of the turbine. Any time the turbine senses a fault, the dynamic brake will stop the turbine and the SMARTBOX™ Controller will stop producing energy from the turbine. “TURBINE FAULT” will be displayed on the LCD screen along with the fault detected. The user must clear any faults in order to restart the turbine.

If a fault occurs, follow these steps to clear it:

1.View the faults listed and correct the fault.

2.Press ENTER on the front panel. If the fault is fixed the controller will go to stop state. If the system finds any other faults, the next fault will be displayed.

3.When all faults are clear, go to start/stop turbine in the menu and restart the turbine.

Non Grid-Tie SmartBox Fault Specifications

Fault

Description

State Required for Fault

GFI

GFI - Ground Fault

 

 

Voltage from Turbine but

Turbine Voltage > 40

NO WINDSPEED

VDC and Wind Speed <

no data from anemometer

 

1 MPH for 1 minute

 

 

TURBINE OVER CUR-

Turbine over current

Current from turbine > 18

RENT

Amps

 

TURBINE OVER VOLTAGE

Turbine over voltage

Voltage from turbine >

190 VDC

 

 

 

Anemometer reporting

Turbine Voltage < 5 VDC

NO TURBINE

windspeed but no voltage

and WindSpeed > 10

 

from wind turbine.

MPH for 1 minute

LOW BATTERY

Battery too low

Battery Voltage < 15 VDC

for 1 minute

 

 

HIGH BATTERY

Battery too high

Battery Voltage > 32 VDC

OVER TEMP

Enclosure or Heat Sink

Enclosure > 65°C or Heat

over temp

Sink > 140°C

 

CHARGE OVER CURRENT

Current to batteries over

Charge current > 66

limit

Amps

INVERTER NO OUTPUT

Inverter is on, but not

Inverter AC output < 100

outputting A/C

VAC for 1 minute

 

INVERTER OVER CUR-

Inverter is over current

Inverter AC Current >

RENT

limit

14.5 Amps for 3 minutes

Figure 4.4 Non-Grid-Tie SmartBox Specifications

SMARTBOX™ Controller for HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev14

Image 38
Contents Smartbox Controller Important Safety Instructions Safety InstructionsSafety Icons General Safety InstructionsBattery Safety Information Limitations on USESafety Instructions Safety Instructions Table of Contents Commisioning Introduction For Information On SeeParts Inspection Smartbox ControllerMajor System Components Not to be used Battery OverviewBattery Types Minimum to be usedAmp-hour Ratings Battery SelectionAC Load Detail and Selection Recommended Appliances Not RecommendedIntroduction Installation Smartbox ControllerSystem Diagrams Turbine Block DiagramRisk of Fire or Explosion Smartbox Controller DiagramMounting EXPLOSION/CORROSION Damage Minimum Clearance for Proper MountingEquipment Damage Shock Hazard WiringGrounding Shock Hazard and Fire HazardWiring Diagram Turbine toTurbine Wiring and Distances Turbine Current Rating and WiringTurbine Over-current Protection Reverse Polarity DamageBattery Wiring Battery Connection LocationBattery Over-current Protection Shock or Fire HazardAC Input Wiring AC Output WiringTurbine Smartbox Controller AC Output Over-current ProtectionControl Wiring Junction BOXEnclosure Internal Wiring Battery SetupConnecting the Smartbox Controller Battery Setup ChartFire and Shock Hazard Warranty Void WarningTo connect the Smartbox Controller Smartbox Installation Commissioning For Information on See Commissioning ProcessCheck all connections for polarity Set the battery type FloodedCommissioning Process Display DescriptionShows if a turbine voltage was found Press Enter to start the turbineCommissioning Operation Starting/Stopping Turbine IntroductionTurbine Operating States Viewing Operating StatusController Energy Consumption States Turbine Operating StatesCool Down System ProtectionTurbine User Stop State Over Wind SpeedFault Description State Required for Fault System FaultsNon Grid-Tie SmartBox Fault Specifications System Menu and Navigation Smartbox Controller Front PanelNavigation Buttons Operations MenuTechnician Menu View Data Menu Battery Setup Menu Operation Specifications Charge Non Grid-Tie Smart Box Electrical SpecificationsInput EnvironmentWindTronics