Overview
About this document
This document outlines the site and preparation requirements for a 6 m (20 ft) HP POD 20c as it is being released in North America. The customer must provide a qualified architectural or consulting engineering team to generate
This guide is part of the core documentation for the HP POD 20c. The actual location of various components or included subsystems and their operation for your
Safety and NEC compliance
The HP POD 20c is certified to UL
The HP POD 20c is not suitable for
IMPORTANT: Before installing the HP POD 20c, consult your local AHJ for applicable regulations and to review
Additional considerations for safety and NEC compliance are as follows:
•The HP POD 20c is listed as an Information Technology Product to UL 60950.
•The HP POD 20c is evaluated as a
•The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an existing facility, and are not suitable as "service entrance" for connection to the utility.
•The HP POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment, in restricted access locations, with field wiring terminals provided for permanent supply connections.
•The HP POD 20c meets the following ratings.
Feature | Specification |
|
|
Category | Rated Overvoltage Category III |
Protection | Surge protection device |
Overview 5