Grounding requirements
The HP POD 20c structure and internal components are all bonded together. A common grounding electrode conductor connection point is provided on the
WARNING: To avoid the risk of personal injury or electric shock, the HP POD 20c must be properly grounded (earthed) in accordance with national, regional, and local regulations.
The following is a list of component requirements for grounding and bonding:
•Grounding of the HP POD 20c must comply with the requirements of Article 250 of the NEC, NFPA
•Bonding of the piping systems and any exposed structural steel that is installed to support the HP POD 20c must be in accordance with the NEC (NA).
Grounding feature | Specification |
|
|
Grounding electrode | • The grounding electrode conductor connection bus pad is located on the outside of |
conductor pad | the HP POD 20c on the hot aisle side of the utility end of the POD and below the |
| transformer cabinet. |
| • The grounding pad must be connected to the grounding electrode system or |
| building steel in accordance with Article 250 of the NEC or equivalent regional |
| regulation. |
|
|
Grounding lugs | • Grounding lugs cannot be attached to any painted surface. |
| • Grounding lugs must be |
| grounding. |
|
|
Ground rod system or | The customer must provide an effective grounding system with a ground rod or a |
ground well | ground well. |
IMPORTANT: Before installing the HP POD 20c, consult your local AHJ for applicable regulations and to review
The following figure shows the grounding electrode conductor connection that is located on the cold aisle of the HP POD 20c.
Side view shown