Thermo Products MDA1-100N, MDA1-50N, MHA1-75N, MHA1-100N Mode of Operation Control System Action

Page 47

All installations and services must be performed by qualified service personnel.

Mode of Operation

Control System Action

Main Burner

Operation

Repeated Trials for Ignition.

Call for Heat

Satisfied

System Lockout

After delay-to-fan-on period ends, circulating air fan is energized at heating speed. The (optional) electronic air cleaner and humidifier are energized.

When thermostat is satisfied, contacts open and the gas valve is de-energized. After proof of flame loss, inducer and (optional) humidifier are de-energized. The delay-to-fan-off period begins (180 seconds)

If ignition attempt is unsuccessful, one more retry will be made before the ignition control module goes into system lockout.

If flame is detected,then lost, the ignition control module will repeat the initial ignition sequence for a total of four recycles. After four unsuccessful recycle attempts, the control will go into system lockout. The ignition control module will reset automatically in 60 minutes.

If system is in lockout, try to reset by interrupting the power

to the furnace at the disconnecting switch or interrupting the call for heat at the thermostat. If this does

not restart the system, refer to the troubleshooting section of this manual.

End of Cycle

After the delay-to-fan-off

 

period ends, the circulating

 

air fan and {optional)

 

electronic air cleaner are

 

de-energized.

44

Image 47
Contents Induced Draft Highboy COUNTERFLOW/HORIZONTAL GAS Furnace Section Safety II. Installation Guidelines Page Shipping Damage PackagingSafety Codes II. Installation GuidelinesCloset and Alcove Installation Installation LocationPlenum Flue or Vent All Models Covered by This Manual Standard ClearancesRefer to Figure Non-combustible MaterialAir for Combustion and Ventilation MDA1 Horizontal Installation MDA1 Installed Horizontal Duct Work and Air Conditioning Filters/ Filter InstallationOptional Thermo Pride Filter Rack Use of Non-Thermo Pride Filter Retention MeansFormula FPMVenting Carbon Monoxide Poisoning Hazard Replacing An Existing Furnace From a Common VentCondensing in the Chimney Page Page Vent Connection to Inducer Inducer Mounting Automated Literature FAX Sidewall VentingHorizontal Size and Length for Sidewall Venting Horizontal Size and Lengths for Horizontal VentsGeneral GAS Piping Fire or Explosion Hazard GAS PipingPage Typical Gas Piping Installation of Natural GAS PipingSteel Pipe Size for Natural Gas IPS Installation of Propane GAS PipingPage Electrical Field Wiring and Replacing WiringRoom Thermostat Electronic Air Cleaner and Humidifier ConnectionsBlower and Control Panel Initial Startup To delay fan Set SwitchWhat to do if YOU Smell GAS To Turn Off Gas To Appliance Adjustment Of Heat Input Rate Page Burner Adjustment Typical Observation of Main Burner Flames Setting Supply Air Temperature RiseImportant Remove flue blockage when done Checkout ProcedureLED will also flash once at power-up Diagnostic FeaturesGeneral Inspection Shut off gas and disconnect power before continuingHouse Air Blower Return Air Filter Filter Maintenance ProcedureFilter Replacement VI. Installers Instructions to User Appendix a Sources for Reference Standards Sequence of Operations for Heating System Appendix B Sequence of OperationsMode of Operation Control System Action Heating System Appendix C Troubleshooting FlowchartsYes Is ignitor positioned Correctly? Does system run until thermostat is satisfied? Description Part Number QTY MDA1/MHA1-50S00S4426Appendix E Replacement Parts List MHA1 Page Replacement Parts List MDA1 Page Appendix F Wiring Diagram Page MID-EFFICIENCY Highboy GAS Furnace SPECIFICATIONS5 Appendix G MID-EFFICENCY Furnace SpecificationsNominal temp. rise Heating fan speed