Thermo Products MDA1-100N, MDA1-50N, MHA1-75N, MHA1-100N, MHA1-50N, MHA1-125N, MDA1-75N Venting

Page 15

All installations and services must be performed by qualified service personnel.

J.Venting

1.Vertical Venting

The vent installation of this Category I furnace must be in accordance with National Fuel Gas Code, NFPA 54/ANSI Z223.1-2002 or latest edition, and/or local building codes and these instructions.

A furnace or any other gas utilization equipment must not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.

When venting two or more appliances into a common vent, the smallest appliance must be vented into the top opening.

The maximum gross stack temperature must not exceed 480°F (249°C) under any circumstances

NOTICE: This section does not apply to units, which are sidewall vented. For sidewall venting, see Section II, K, of this manual.

The following requirements must be followed when connecting this furnace to a vent system.

The MHA1/MDA1 (induced draft gas highboy and counterflow/horizontal) series furnace must be vented in accordance with these instructions into a factory built chimney or vent complying with a recognized standard. Type B1 or double wall vent as well as masonry chimneys lined with a lining material acceptable to the authority having jurisdiction are acceptable as described in the venting tables included in the appendix of the National Fuel Gas Code, NFPA 54/ANSI Z223.1- 2002, or latest edition.

A good vent is one that is sealed and has the capability of producing a -0.04 in. W.G. draft with the capacity of handling the amount of flue gas that is introduced to it.

The vent must be vertical or nearly vertical in design, unless equipped with a UL listed mechanical venter.

This furnace must not be connected into any portion of a mechanical draft system operating under a positive pressure.

This furnace shall not be vented into an unlined masonry or concrete chimney.

PVC piping is not an acceptable substitute for a chimney or a flue connector. A chimney with an internal construction of stainless steel or some other material that will withstand a gross flue gas temperature of 480ºF is required.

12

Image 15
Contents Induced Draft Highboy COUNTERFLOW/HORIZONTAL GAS Furnace Section Safety II. Installation Guidelines Page Shipping Damage PackagingSafety Codes II. Installation GuidelinesCloset and Alcove Installation Installation LocationPlenum Flue or Vent All Models Covered by This Manual Standard ClearancesRefer to Figure Non-combustible MaterialAir for Combustion and Ventilation MDA1 Horizontal Installation MDA1 Installed Horizontal Duct Work and Air Conditioning Filters/ Filter InstallationOptional Thermo Pride Filter Rack Use of Non-Thermo Pride Filter Retention MeansFormula FPMVenting Carbon Monoxide Poisoning Hazard Replacing An Existing Furnace From a Common VentCondensing in the Chimney Page Page Vent Connection to Inducer Inducer Mounting Automated Literature FAX Sidewall VentingHorizontal Size and Length for Sidewall Venting Horizontal Size and Lengths for Horizontal VentsGeneral GAS Piping Fire or Explosion Hazard GAS PipingPage Typical Gas Piping Installation of Natural GAS PipingSteel Pipe Size for Natural Gas IPS Installation of Propane GAS PipingPage Electrical Field Wiring and Replacing WiringRoom Thermostat Electronic Air Cleaner and Humidifier ConnectionsBlower and Control Panel Initial Startup To delay fan Set SwitchWhat to do if YOU Smell GAS To Turn Off Gas To Appliance Adjustment Of Heat Input Rate Page Burner Adjustment Typical Observation of Main Burner Flames Setting Supply Air Temperature RiseImportant Remove flue blockage when done Checkout ProcedureLED will also flash once at power-up Diagnostic FeaturesGeneral Inspection Shut off gas and disconnect power before continuingHouse Air Blower Filter Maintenance Procedure Filter ReplacementReturn Air Filter VI. Installers Instructions to User Appendix a Sources for Reference Standards Sequence of Operations for Heating System Appendix B Sequence of OperationsMode of Operation Control System Action Heating System Appendix C Troubleshooting FlowchartsYes Is ignitor positioned Correctly? Does system run until thermostat is satisfied? Description Part Number QTY MDA1/MHA1-50S00S4426Appendix E Replacement Parts List MHA1 Page Replacement Parts List MDA1 Page Appendix F Wiring Diagram Page MID-EFFICIENCY Highboy GAS Furnace SPECIFICATIONS5 Appendix G MID-EFFICENCY Furnace SpecificationsNominal temp. rise Heating fan speed