All installations and services must be performed by qualified service personnel.
Installation, setup, and operation must be in accordance with the instruction provided by the manufacture of the power venter. Thermo Products has provided in the following section maximum and minimum vent lengths guidelines that must also be followed.
Contact Field Controls for instructions for installing the SWGII vent system
IMPORTANT: No warranty will be made on behalf of the appliance manufacturer with respect to the sidewall venting system installation or replacement. The appliance manufacturer shall not be liable for any special, incidental, indirect, or consequential damages. (Some jurisdictions do not allow exclusion or limitation of incidental or consequential damages. The above limitations or exclusions may not apply to you).
IMPORTANT: It is the installer’s responsibility to inform and demonstrate to the user the correct operation and maintenance of the appliances explained in this manual, the user’s information manual, and the sidewall vent manufacturer’s manual.
1. Horizontal Size and Lengths for Horizontal Vents
The minimum sidewall vent length is two (2) feet of straight vent pipe with one (1) elbow and one (1) adapter or transition to inducer. The maximum vent length and permitted number of elbows are shown in the following table.
Table 3: Horizontal Size and Length for Sidewall Venting
MODEL NUMBER | SIZE | Max. Length of Vent | EQUIVALENT | ||
OF | Pipe (in Feet) With | LENGTH | |||
OF FURNACE | VENT | 1 | 2 | 3 | OF VENT* |
| (In.) | ELBOW | ELBOWS | ELBOWS | (Ft) |
3 | 45 | 40 | 35 | 50 | |
|
|
|
|
|
|
|
|
|
|
| |
4 | 45 | 40 | 35 | 50 | |
|
|
|
|
|
* Each elbow used is considered to be equivalent to 5 feet of straight vent pipe.