Thermo Products MDA1-125N Electronic Air Cleaner and Humidifier Connections, Room Thermostat

Page 30

All installations and services must be performed by qualified service personnel.

3.Electronic Air Cleaner and Humidifier Connections

The ignition module on this furnace has designated terminals to control the operation of an electronic air cleaner and/or humidifier. These terminals provide line voltage for the control of these accessories (See Figure 8).

NOTICE: It is important to confirm that the operating voltage of the humidifier or EAC being installed matches the output of this control. If not, a field supplied relay or transformer may be necessary to provide the proper control and supply voltage for the accessory being installed. See the manufacturers instructions for the humidifier or EAC for additional requirements.

4.Room Thermostat

A room thermostat is not furnished with this furnace. However, a thermostat is required to properly operate the furnace control system.

The room thermostat should be located in the natural circulating path of the room air. The thermostat should not be placed where exposed to cold air infiltration, i.e. drafts from outside openings such as windows and doors, or where exposed to air currents from supply or return air registers, or such that natural circulation of air is blocked, such as behind doors, in shelves, or in corners. It should always be located on an interior wall.

In addition, the room thermostat should not be exposed to heat from a nearby fireplace, electrical appliances, lamps, rays from the sun, or mounted directly on a wall containing warm air ducts, a chimney, or a gas vent. These sources of heat could adversely affect the operation of the thermostat, preventing it from properly controlling the room temperature.

Generally, a room thermostat should be set at the lowest temperature that is comfortable to the building occupants. This will result in the lowest cost to heat the building.

Proper control of the indoor temperature can only be achieved if the thermostat is calibrated to the heating and/or cooling cycle. A vital consideration of this calibration is related to the thermostat heat anticipator.

The proper thermostat heat anticipator setting is 0.8 AMPS for furnace operation only. To increase length of the heating cycles, increase setting of heat scale; to decrease length of cycle, decrease setting of heat scale.

Anticipators for the heating operation are of two types, pre-set and adjustable. Those that are pre-set will not have an adjustment scale and are generally marked accordingly.

27

Image 30
Contents Induced Draft Highboy COUNTERFLOW/HORIZONTAL GAS Furnace Section Safety II. Installation Guidelines Page Packaging Shipping DamageSafety II. Installation Guidelines CodesInstallation Location Closet and Alcove InstallationNon-combustible Material Standard ClearancesRefer to Figure Plenum Flue or Vent All Models Covered by This ManualAir for Combustion and Ventilation MDA1 Horizontal Installation MDA1 Installed Horizontal Filters/ Filter Installation Duct Work and Air ConditioningUse of Non-Thermo Pride Filter Retention Means Optional Thermo Pride Filter RackFPM FormulaVenting Replacing An Existing Furnace From a Common Vent Carbon Monoxide Poisoning HazardCondensing in the Chimney Page Page Vent Connection to Inducer Inducer Mounting Sidewall Venting Automated Literature FAXHorizontal Size and Lengths for Horizontal Vents Horizontal Size and Length for Sidewall VentingGAS Piping General GAS Piping Fire or Explosion HazardPage Installation of Natural GAS Piping Typical Gas PipingInstallation of Propane GAS Piping Steel Pipe Size for Natural Gas IPSPage Field Wiring and Replacing Wiring ElectricalElectronic Air Cleaner and Humidifier Connections Room ThermostatBlower and Control Panel To delay fan Set Switch Initial StartupWhat to do if YOU Smell GAS To Turn Off Gas To Appliance Adjustment Of Heat Input Rate Page Burner Adjustment Setting Supply Air Temperature Rise Typical Observation of Main Burner FlamesCheckout Procedure Important Remove flue blockage when doneDiagnostic Features LED will also flash once at power-upShut off gas and disconnect power before continuing General InspectionHouse Air Blower Filter Maintenance Procedure Filter ReplacementReturn Air Filter VI. Installers Instructions to User Appendix a Sources for Reference Standards Appendix B Sequence of Operations Sequence of Operations for Heating SystemMode of Operation Control System Action Appendix C Troubleshooting Flowcharts Heating SystemYes Is ignitor positioned Correctly? Does system run until thermostat is satisfied? MDA1/MHA1-50S00S4426 Description Part Number QTYAppendix E Replacement Parts List MHA1 Page Replacement Parts List MDA1 Page Appendix F Wiring Diagram Page Appendix G MID-EFFICENCY Furnace Specifications MID-EFFICIENCY Highboy GAS Furnace SPECIFICATIONS5Nominal temp. rise Heating fan speed