Thermo Products MHA1-50N, MDA1-50N, MHA1-75N Does system run until thermostat is satisfied?

Page 51

All installations and services must be performed by qualified service personnel.

Yes

Does system run until thermostat is satisfied?

Yes

No

 

No

 

Is LED light on ignition

 

 

control module flashing?

 

 

 

 

 

 

 

 

 

Yes

If LED Light Flashes:

 

1

Flash, then pause

System lockout

2

Flashes, then pause

Pressure switch stuck closed

3

Flashes, then pause

Pressure switch stuck open

4

Flashes, then pause

Open high limit, aux. limit, or roll-out switch

6

Flashes, then pause

115 Volt AC power reversed

7

Flashes, then pause

Low flame sense signal

8

Flashes, then pause

Check ignitor or improper grounding

Continuous flashing

Flame has been sensed when no flame

 

(no pause)

should be present (no call for heat)

Check all wiring for loose connections.

Does burner shut off

No

when thermostat is

 

 

satisfied?

 

 

 

Yes

Does the circulating air

No

blower turn off after

thermostat is satisfied

 

within 180 seconds?

 

Yes

Troubleshooting Complete.

Check for short in wire to

thermostat. Replace

thermostat if necessary.

Check DIP switch settings on ignition control module against those on connection diagram. Reset if necessary.

48

Image 51
Contents Induced Draft Highboy COUNTERFLOW/HORIZONTAL GAS Furnace Section Safety II. Installation Guidelines Page Shipping Damage PackagingSafety Codes II. Installation GuidelinesCloset and Alcove Installation Installation LocationPlenum Flue or Vent All Models Covered by This Manual Standard ClearancesRefer to Figure Non-combustible MaterialAir for Combustion and Ventilation MDA1 Horizontal Installation MDA1 Installed Horizontal Duct Work and Air Conditioning Filters/ Filter InstallationOptional Thermo Pride Filter Rack Use of Non-Thermo Pride Filter Retention MeansFormula FPMVenting Carbon Monoxide Poisoning Hazard Replacing An Existing Furnace From a Common VentCondensing in the Chimney Page Page Vent Connection to Inducer Inducer Mounting Automated Literature FAX Sidewall VentingHorizontal Size and Length for Sidewall Venting Horizontal Size and Lengths for Horizontal VentsGeneral GAS Piping Fire or Explosion Hazard GAS PipingPage Typical Gas Piping Installation of Natural GAS PipingSteel Pipe Size for Natural Gas IPS Installation of Propane GAS PipingPage Electrical Field Wiring and Replacing WiringRoom Thermostat Electronic Air Cleaner and Humidifier ConnectionsBlower and Control Panel Initial Startup To delay fan Set SwitchWhat to do if YOU Smell GAS To Turn Off Gas To Appliance Adjustment Of Heat Input Rate Page Burner Adjustment Typical Observation of Main Burner Flames Setting Supply Air Temperature RiseImportant Remove flue blockage when done Checkout ProcedureLED will also flash once at power-up Diagnostic FeaturesGeneral Inspection Shut off gas and disconnect power before continuingHouse Air Blower Filter Maintenance Procedure Filter ReplacementReturn Air Filter VI. Installers Instructions to User Appendix a Sources for Reference Standards Sequence of Operations for Heating System Appendix B Sequence of OperationsMode of Operation Control System Action Heating System Appendix C Troubleshooting FlowchartsYes Is ignitor positioned Correctly? Does system run until thermostat is satisfied? Description Part Number QTY MDA1/MHA1-50S00S4426Appendix E Replacement Parts List MHA1 Page Replacement Parts List MDA1 Page Appendix F Wiring Diagram Page MID-EFFICIENCY Highboy GAS Furnace SPECIFICATIONS5 Appendix G MID-EFFICENCY Furnace SpecificationsNominal temp. rise Heating fan speed