All installations and services must be performed by qualified service personnel.

E. Checkout Procedure

Before any system of gas piping is finally put into service, it shall be carefully tested to assure that it is “gas-tight”, as indicated in the General Gas Piping Requirements section of this manual.

NOTICE: All controls on the unit should be checked for proper functioning prior to the qualified service personnel leaving the job site. Specifically the following should be checked:

1.With heating system in normal heating operation, check to make certain blower will start and stop automatically under control of integrated furnace control.

2.Check safety limit control as follows:

a.Shut off incoming power.

b.Block return air opening or disconnect blower motor leads.

c.Restore power to appliance.

d.In the heating mode, set the thermostat above room temperature producing “a call for heat”.

e.When high air temperatures are reached within the furnace, the high limit control should act to shutdown the main burners.

f.Shut off the electrical power.

IMPORTANT: Remove blockage or reconnect blower motor and restore power.

3.Make certain the thermostat will automatically start and stop the appliance.

4.Block the vent terminal outlet gradually with a flat piece of metal, until the pressure switch functions shutting off the main burners.

IMPORTANT: Remove flue blockage when done.

NOTICE: Heat exchanger oil will burn off on initial firing creating an unpleasant odor. To prevent this odor from occurring more than once, it is suggested the furnace be allowed to run for 30 minutes, or until odor has dissipated.

36

Image 39
Contents Induced Draft Highboy COUNTERFLOW/HORIZONTAL GAS Furnace Section Safety II. Installation Guidelines Page Shipping Damage PackagingSafety Codes II. Installation GuidelinesCloset and Alcove Installation Installation LocationPlenum Flue or Vent All Models Covered by This Manual Standard ClearancesRefer to Figure Non-combustible MaterialAir for Combustion and Ventilation MDA1 Horizontal Installation MDA1 Installed Horizontal Duct Work and Air Conditioning Filters/ Filter InstallationOptional Thermo Pride Filter Rack Use of Non-Thermo Pride Filter Retention MeansFormula FPMVenting Carbon Monoxide Poisoning Hazard Replacing An Existing Furnace From a Common VentCondensing in the Chimney Page Page Vent Connection to Inducer Inducer Mounting Automated Literature FAX Sidewall VentingHorizontal Size and Length for Sidewall Venting Horizontal Size and Lengths for Horizontal VentsGeneral GAS Piping Fire or Explosion Hazard GAS PipingPage Typical Gas Piping Installation of Natural GAS PipingSteel Pipe Size for Natural Gas IPS Installation of Propane GAS PipingPage Electrical Field Wiring and Replacing WiringRoom Thermostat Electronic Air Cleaner and Humidifier ConnectionsBlower and Control Panel Initial Startup To delay fan Set SwitchWhat to do if YOU Smell GAS To Turn Off Gas To Appliance Adjustment Of Heat Input Rate Page Burner Adjustment Typical Observation of Main Burner Flames Setting Supply Air Temperature RiseImportant Remove flue blockage when done Checkout ProcedureLED will also flash once at power-up Diagnostic FeaturesGeneral Inspection Shut off gas and disconnect power before continuingHouse Air Blower Filter Maintenance Procedure Filter ReplacementReturn Air Filter VI. Installers Instructions to User Appendix a Sources for Reference Standards Sequence of Operations for Heating System Appendix B Sequence of OperationsMode of Operation Control System Action Heating System Appendix C Troubleshooting FlowchartsYes Is ignitor positioned Correctly? Does system run until thermostat is satisfied? Description Part Number QTY MDA1/MHA1-50S00S4426Appendix E Replacement Parts List MHA1 Page Replacement Parts List MDA1 Page Appendix F Wiring Diagram Page MID-EFFICIENCY Highboy GAS Furnace SPECIFICATIONS5 Appendix G MID-EFFICENCY Furnace SpecificationsNominal temp. rise Heating fan speed