Thermo Products MHA1-75N, MDA1-50N, MHA1-100N, MHA1-50N, MDA1-75N Air for Combustion and Ventilation

Page 9

All installations and services must be performed by qualified service personnel.

E. Air for Combustion and Ventilation

:

Relief openings in the front or top of the furnace casing should not be obstructed or blocked. These openings supply combustion and ventilation air to the furnace.

Chloride, fluoride, iodide, and bromide bearing compounds when present, even in low concentrations, in air supplied for combustion to the furnace, can result in accelerated and severe corrosion of the heat exchanger and/or the venting systems. This condition can occur with less efficient furnaces, but is accelerated on furnaces with efficiencies of 80% or greater.

Many, household chemicals contain chloride-bearing compounds. There are many compounds representative of this classification of chemicals. A few common examples are listed below.

Cleaning solvents

Varnish and paint removers

Bleaches

Fabric softeners

Water softener salt

Tile adhesives

Avoid installing the furnace in areas where it is evident these chemicals are being stored, or used, within close proximity to the furnace. In addition, avoid storing or using any chemicals of an unknown nature in close proximity to the furnace. If it is necessary to store or use these chemicals in the same space as the furnace, all containers should be sealed when not in use. If possible, keep these chemicals in a separate, well-ventilated, room that is closed off, from the furnace, with a door.

The furnace shall be installed in a location within the building that permits a satisfactory supply of air for combustion, ventilation, and proper operation of the venting system. While all forms of building construction cannot be covered in detail in this manual, this requirement may usually be met by application of one of the following methods in ordinary building construction. Consult the National Fuel Gas Code, NFPA 54/ANSI Z223.1 – 2002, or the latest edition, for special cases and further details. However, local installation codes always take precedence and must be followed, if applicable.

6

Image 9
Contents Induced Draft Highboy COUNTERFLOW/HORIZONTAL GAS Furnace Section Safety II. Installation Guidelines Page Shipping Damage PackagingSafety Codes II. Installation GuidelinesCloset and Alcove Installation Installation LocationRefer to Figure Standard ClearancesNon-combustible Material Plenum Flue or Vent All Models Covered by This ManualAir for Combustion and Ventilation MDA1 Horizontal Installation MDA1 Installed Horizontal Duct Work and Air Conditioning Filters/ Filter InstallationOptional Thermo Pride Filter Rack Use of Non-Thermo Pride Filter Retention MeansFormula FPMVenting Carbon Monoxide Poisoning Hazard Replacing An Existing Furnace From a Common VentCondensing in the Chimney Page Page Vent Connection to Inducer Inducer Mounting Automated Literature FAX Sidewall VentingHorizontal Size and Length for Sidewall Venting Horizontal Size and Lengths for Horizontal VentsGeneral GAS Piping Fire or Explosion Hazard GAS PipingPage Typical Gas Piping Installation of Natural GAS PipingSteel Pipe Size for Natural Gas IPS Installation of Propane GAS PipingPage Electrical Field Wiring and Replacing WiringRoom Thermostat Electronic Air Cleaner and Humidifier ConnectionsBlower and Control Panel Initial Startup To delay fan Set SwitchWhat to do if YOU Smell GAS To Turn Off Gas To Appliance Adjustment Of Heat Input Rate Page Burner Adjustment Typical Observation of Main Burner Flames Setting Supply Air Temperature RiseImportant Remove flue blockage when done Checkout ProcedureLED will also flash once at power-up Diagnostic FeaturesGeneral Inspection Shut off gas and disconnect power before continuingHouse Air Blower Filter Maintenance Procedure Filter ReplacementReturn Air Filter VI. Installers Instructions to User Appendix a Sources for Reference Standards Sequence of Operations for Heating System Appendix B Sequence of OperationsMode of Operation Control System Action Heating System Appendix C Troubleshooting FlowchartsYes Is ignitor positioned Correctly? Does system run until thermostat is satisfied? Description Part Number QTY MDA1/MHA1-50S00S4426Appendix E Replacement Parts List MHA1 Page Replacement Parts List MDA1 Page Appendix F Wiring Diagram Page MID-EFFICIENCY Highboy GAS Furnace SPECIFICATIONS5 Appendix G MID-EFFICENCY Furnace SpecificationsNominal temp. rise Heating fan speed