Toshiba RAV-SM1400AT-E Outdoor Control, Outline of Main Controls, Current release control

Page 42

9. OUTDOOR CONTROL

9-1. Outline of Main Controls

1.Pulse Modulating Valve (PMV) control

1)PMV is controlled with 50 to 500 pulses during operation, respectively.

2)In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor.

3)In heating operation, PMV is controlled with the temperature difference between TS sensor and TE sensor.

4)For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and heating operations.

5)When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD sensor. The aimed value is usually 105°C for SM560 and 100°C for SM800, SM1100, SM1400 in both cooling and heating operations.

REQUIREMENT

A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance value an the refrigerating cycle of each sensor after repair and then start the operation.

2. Discharge temperature release control

1) This function controls the operation frequency, that is, lowers the operation frequency when the dis-

TD [˚C]

 

charge temperature has not lower or the discharge

Error stop ("P03" display with 4 times of error counts)

 

temperature has rapidly risen during PMV control. It

a

 

 

subdivides the frequency control up to a unit of

 

b

Frequency down

 

0.6Hz to stabilize the cycle.

 

 

 

 

 

2) When the discharge temperature is detected in an

c

 

 

abnormal stop zone, the unit stops the compressor

 

 

 

Frequency holding

 

and restarts after 2 minutes 30 seconds. The error

 

 

 

 

 

counter is cleared when it has continued the opera-

d

 

 

tion for 10 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency slow-up

 

If the abnormal stop zone has been detected by 4

 

 

 

(Up to command)

 

times without clearing of counter, an error ‘P03’ is

 

 

e

 

 

displayed.

 

 

 

 

 

 

 

 

 

 

 

 

 

As command is

 

* The cause is considered as excessively little amount

 

 

 

of refrigerant, defective PMV, or clogging of cycle.

 

 

 

 

 

 

 

 

[°C]

 

[A]

 

 

 

 

 

 

 

 

 

 

a

b

c

d

e

 

Frequency down

 

SM560

117

112

108

105

98

 

 

 

 

 

SM800, 1100, 1400

111

106

100

95

90

I1

Hold

 

 

 

 

 

 

 

 

 

 

3.

Current release control

 

 

 

 

1–0.5

Hold

 

 

 

 

Normal operation

 

The output frequency and the output voltage are

 

 

 

 

 

 

 

controlled by AC current value detected by T02 on the

 

 

 

outdoor P.C. board so that input current of the inverter

 

 

 

does not exceed the specified value.

 

 

 

 

 

Objective

SM560

SM800

SM1100

SM1400

model

COOL

HEAT

COOL

HEAT

COOL

HEAT

COOL

HEAT

 

 

 

 

 

 

 

 

 

I1 value [A]

9.22

11.93

12.00

13.43

18.90

19.65

19.65

19.65

 

 

 

 

 

 

 

 

 

* For the cooling only models, only COOL is objective.

40

Image 42
Contents Split Type Contents Specifications Indoor UnitConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E Outdoor Unit RAV-SM560AT-E RAV-SM800AT-ERAV-SM1100AT-E RAV-SM1400AT-E Operation Characteristic Curve Cooling HeatingCapacity Variation Ratio According to Temperature CoolingHeating Static Pressure Characteristics of Each Model AIR Ducting WorkRAV-SM1101BT-E Round duct Indoor Unit Concealed Duct Type DimensionConstruction Views External Views RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Indoor unit Systematic Refrigerating Cycle DiagramIndoor Unit/Outdoor Unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Strainer Second rps Fan Indoor OutdoorWiring Diagram ColorIdentification Color Identification MCC-813MCC-1359 For P.C. BoardMCC-1438 MCC-1398Specifications of Electrical Parts Parts name Type SpecificationsRAV-SM1100AT-E Refrigerant R410A Safety During Installation/ServicingRefrigerant Piping Installation Piping Materials and Joints UsedOuter diameter mm R410A R22 Processing of Piping Materials1 Thicknesses of annealed copper pipes Thickness mm Nominal diameterR22 clutch type Clutch type Wing nut type Flare tool for Conventional flare toolR410A clutch type Clutch type Wing nut type DiameterNm kgfcm Wrenches available on the marketTools Required ToolsGeneral tools Conventional tools can be used 1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Materials for BrazingFlux Brazing Never use gas other than Nitrogen gasMain Sub master remote controller Weekly timer Indoor Unit ControlIndoor Control Circuit Control Specifications Outline of specifications RemarksRemote controller Outline of control Command Heating Auto OperationHeat Control temp C Center Case of wired remote controllerLast push priority Operation ProhibitedTa˚C Normal control SM1401BT-E Indoor Print Circuit BoardMCC-1402 RAV-SM561BT-E / SM801BT-E / SM1101BTIndoor P.C. Board Optional Connector Specifications Function Connector Pin Specifications RemarksOutline of Main Controls Discharge temperature release controlOutdoor Control Pulse Modulating Valve PMV controlMAX Cooling operation Outdoor fan control Object SM560Allocations of fan tap revolutions Heating operationOver-current preventive control Short intermittent operation preventive controlHigh-pressure suppression TE control For SM800 Current release value shift controlDefrost control Start of heating operationOutdoor Controls Print Circuit BoardMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Wired remote controller type TroubleshootingSummary of Troubleshooting Before troubleshootingCheck Code List Error mode detected by indoor unitError mode detected by outdoor unit Diagnostic function Cause of operationError mode detected by remote controller or network adapter Timer Ready Wired remote Controller Check codeCDB side Error Mode Detected by LED on Outdoor P.C. BoardSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF Ipdu sideSW800 LED display in bit 1, bit 2, bit 3 OFF Check codeType a E09 error/*99 error Troubleshooting Procedure for Each Check CodeE01 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E08, L03, L07, L08 error/ *96 error 99 error E10 error/CF errorE18 error/97 error *99 error L09 error/46 errorL20 error/98 error L30 error/B6 errorB7 error Central controller P10 error/Ob error F10 error 0C errorP12 error/11 error P22 error/1A error Single phaseRAV-SM1100AT-E, SM1400AT-E P19 error/08 error F02 error/0d errorF01 error/0F error P26 error/14 errorP29 error/16 error H03 error/17 errorF06 error/18 error F04 error/19 errorF08 error/1b error L29 error/1C error H02 error/1d errorP03 error/1E error H01 error/1F errorP04 error/21 error Error Central controller E03 error Master indoor unit F29 error / 12 errorP31 error Sub indoor unit 20 TE, TO, TS sensor TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1Caracteristics-3 TD sensor Caracteristics-4Replacement of Service Indoor P.C. Board CaseContents R1 Readout of the setup data from EepromR2 Replacement of service P.C. board Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Memorandum for setup contents Item code table Example Type Item codeIndoor unit capacity Item code Setup to Select Function Setup AT Local Site and OthersTest Run Setup on Remote Controller Wired remote controllerItem No. DN table Selection of function Description At shipmentCabling and Setting of Remote Controller Control Setup methodOperation Monitor Function of Remote Controller Switch ContentsProcedure Requirement Calling of error historyGroup control operation System exampleLED Display Specification Microcomputer Block DiagramNetwork Address Setup Switch SW01 Network AdapterCable Connection Communication Cable SpecificationsCommunication circuit Communication cable specifications Network cable connectionHow to set by the switch on the network adapter P.C. board How to Set an Address NumberHow to set from the remote controller at indoor unit side Procedure Set the network address while the unit stopsRequirement in Service Network address No. setup table SW01Address No Contents Remarks Address Setup Address SetupAddress setup procedure Only turning on source power supply Automatic completion Address Setup & Group ControlSystem configuration Automatic address example from unset address No miscablingManual setting from remote controller Setup completes Status returns to the usual stop statusPush button if the unit stops To know the position of indoor unit body by addressPush and buttons simultaneously for 4 seconds or more Part name Procedure Remarks DetachmentsNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Detachment AttachmentProcedure Remarks Part namePart name Procedure RequirementConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex 100 Requirement101 102 103 104 105 Product106 107 108 109 110 Be sure to mount the propeller fan 111Case of RAV-SM1100AT-E Case of RAV-SM1400AT-E112 113 Part Description Exploded Views and Parts List114 Location904 901, 902, 903 35, 36, 37 115116 RAV-SM1001BT-E / SM1401BT-E117 RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-EInverter 118702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 11921,22 16,17 120706 121Inverter 26,27 23,24 28,29 122TH Sensor 123