Toshiba RAV-SM561BT-E, RAV-SM1400AT-E, RAV-SM1101BT-E P29 error/16 error, H03 error/17 error

Page 64

[P29 error]/[16 error]

 

NO

 

 

 

 

Are connections of

 

 

Check and correct circuit cabling

 

 

 

 

 

cable/connector normal?

 

 

 

such as cabling to compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

Is compressor normal?

YES

 

 

 

Is not earthed?

YES

 

 

 

Compressor error

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is not winding shorted?

 

 

 

 

 

 

 

 

 

 

Compressor error

Replace

 

 

 

 

 

 

 

 

 

(Is resistance between windings 0.6 to 1.2

?)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

Is not winding opened?

 

 

 

 

 

 

 

 

 

 

 

 

Compressor error

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check IPDU P.C. board.

 

 

* For RAV-SM560AT-E, replace control P.C. board.

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[H03 error]/[17 error]

Are cablings of power and

current sensor normal?

YES

Check IPDU.

Defect Replace

NO

Check and correct circuit cables.

* For RAV-SM560AT-E, replace control P.C. board.

62

Image 64
Contents Split Type Contents Indoor Unit SpecificationsConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E Outdoor Unit RAV-SM560AT-E RAV-SM800AT-ERAV-SM1100AT-E RAV-SM1400AT-E Operation Characteristic Curve Cooling HeatingCooling Capacity Variation Ratio According to TemperatureHeating Static Pressure Characteristics of Each Model AIR Ducting WorkRAV-SM1101BT-E Round duct Dimension Construction Views External ViewsIndoor Unit Concealed Duct Type RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Systematic Refrigerating Cycle Diagram Indoor Unit/Outdoor UnitIndoor unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Strainer Second rps Fan Indoor OutdoorColor Wiring DiagramIdentification Color Identification MCC-813MCC-1359 For P.C. BoardMCC-1438 MCC-1398Specifications of Electrical Parts Parts name Type SpecificationsRAV-SM1100AT-E Safety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping Materials and Joints UsedProcessing of Piping Materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Nominal diameterFlare tool for Conventional flare tool R410A clutch type Clutch type Wing nut typeR22 clutch type Clutch type Wing nut type DiameterNm kgfcm Wrenches available on the marketRequired Tools ToolsGeneral tools Conventional tools can be used 1 Configuration of refrigerant charging Recharging of RefrigerantMaterials for Brazing Brazing of PipesFlux Brazing Never use gas other than Nitrogen gasIndoor Unit Control Main Sub master remote controller Weekly timerIndoor Control Circuit Outline of specifications Remarks Control SpecificationsRemote controller Outline of control Command Heating Auto OperationHeat Control temp C Case of wired remote controller Last push priorityCenter Operation ProhibitedTa˚C Normal control Indoor Print Circuit Board MCC-1402SM1401BT-E RAV-SM561BT-E / SM801BT-E / SM1101BTIndoor P.C. Board Optional Connector Specifications Function Connector Pin Specifications RemarksDischarge temperature release control Outdoor ControlOutline of Main Controls Pulse Modulating Valve PMV controlMAX Outdoor fan control Object SM560 Allocations of fan tap revolutionsCooling operation Heating operationShort intermittent operation preventive control High-pressure suppression TE control For SM800Over-current preventive control Current release value shift controlDefrost control Start of heating operationPrint Circuit Board Outdoor ControlsMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Troubleshooting Summary of TroubleshootingWired remote controller type Before troubleshootingCheck Code List Error mode detected by indoor unitError mode detected by outdoor unit Diagnostic function Cause of operationError mode detected by remote controller or network adapter Timer Ready Wired remote Controller Check codeError Mode Detected by LED on Outdoor P.C. Board SW800 LED display in bit 1, bit 2, bit 3, bit 4 OFFCDB side Ipdu sideCheck code SW800 LED display in bit 1, bit 2, bit 3 OFFType a Troubleshooting Procedure for Each Check Code E01 error/*99 errorE09 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E10 error/CF error E18 error/97 error *99 errorE08, L03, L07, L08 error/ *96 error 99 error L09 error/46 errorL30 error/B6 error L20 error/98 errorB7 error Central controller P10 error/Ob error F10 error 0C errorP12 error/11 error Single phase P22 error/1A errorRAV-SM1100AT-E, SM1400AT-E P19 error/08 error F02 error/0d errorF01 error/0F error P26 error/14 errorP29 error/16 error H03 error/17 errorF04 error/19 error F06 error/18 errorF08 error/1b error L29 error/1C error H02 error/1d errorP03 error/1E error H01 error/1F errorP04 error/21 error Error Central controller F29 error / 12 error E03 error Master indoor unitP31 error Sub indoor unit TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1 Caracteristics-320 TE, TO, TS sensor TD sensor Caracteristics-4Replacement of Service Indoor P.C. Board CaseR1 Readout of the setup data from Eeprom R2 Replacement of service P.C. boardContents Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Type Item code Memorandum for setup contents Item code table ExampleIndoor unit capacity Item code Setup AT Local Site and Others Test Run Setup on Remote ControllerSetup to Select Function Wired remote controllerItem No. DN table Selection of function Description At shipmentSetup method Cabling and Setting of Remote Controller ControlOperation Contents Monitor Function of Remote Controller SwitchProcedure Calling of error history Group control operationRequirement System exampleMicrocomputer Block Diagram Network Address Setup Switch SW01LED Display Specification Network AdapterCommunication Cable Specifications Communication circuit Communication cable specificationsCable Connection Network cable connectionHow to Set an Address Number How to set from the remote controller at indoor unit sideHow to set by the switch on the network adapter P.C. board Procedure Set the network address while the unit stopsNetwork address No. setup table SW01 Requirement in ServiceAddress No Contents Remarks Address Setup Address SetupAddress setup procedure Address Setup & Group Control System configurationOnly turning on source power supply Automatic completion Automatic address example from unset address No miscablingManual setting from remote controller Setup completes Status returns to the usual stop statusTo know the position of indoor unit body by address Push button if the unit stopsPush and buttons simultaneously for 4 seconds or more Part name Procedure Remarks DetachmentsNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Detachment AttachmentProcedure Remarks Part namePart name Procedure RequirementConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex 100 Requirement101 102 103 104 105 Product106 107 108 109 110 111 Case of RAV-SM1100AT-EBe sure to mount the propeller fan Case of RAV-SM1400AT-E112 113 Exploded Views and Parts List 114Part Description Location904 901, 902, 903 35, 36, 37 115116 RAV-SM1001BT-E / SM1401BT-E117 RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-EInverter 118702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 11921,22 16,17 120706 121Inverter 26,27 23,24 28,29 122TH Sensor 123