Toshiba RAV-SM1401BT-E, RAV-SM1400AT-E, RAV-SM1101BT-E Error mode detected by outdoor unit

Page 51

Error mode detected by outdoor unit

: Flash, : Go on, : Go off

49

Wireless sensor

Wired remote

lamp display

controller

 

 

 

 

Operation

Timer

Ready

Check code

 

 

 

 

 

 

 

H01

 

 

 

 

 

 

 

 

H02

 

 

 

 

 

 

 

 

H03

 

 

 

 

 

 

 

 

L29

 

 

 

 

 

L31

 

 

 

 

 

 

 

 

P03

 

 

 

 

 

 

 

 

P04

 

 

 

 

 

 

 

 

P22

 

 

 

 

 

P26

 

 

 

 

 

P29

 

 

 

 

 

F04

 

 

 

 

 

F06

 

 

 

 

 

F08

 

 

 

 

 

Diagnostic function

Cause of operation

Breakdown of compressor

• Displayed when error is detected

Compressor does not rotate.

Over-current protective circuit operates after specified time passed when compressor had been activated.

Current detection circuit error

Current value at AC side is high even during compressor-OFF.

Phase of power supply is missed.

Outdoor unit and other errors

Communication error between CDB and IPDU (Coming-off of connector)

Heat sink temperature error

(Detection of temperature over specified value)

Phase detection protective circuit operates. (Normal models)

Discharge temperature error

• Discharge temperature over specified value was detected.

High-pressure protection error by TE sensor (Temperature over specified value was detected.)

Outdoor DC fan error

Inverter over-current protective circuit operates. (For a short time) Short voltage of main circuit operates.

IPDU position detection circuit error

Coming-off, disconnection or short of outdoor temperature sensor (TD)

Coming-off, disconnection or short of outdoor temperature sensor (TE/TS)

Coming-off, disconnection or short of outdoor temperature sensor (TO)

Status of air conditioner

Stop

Stop

Stop

Stop

Operation continues. (Compressor stops.)

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Operation continues.

Condition

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Judgment and measures

1.Check power voltage. AC200V±20V

2.Overload operation of refrigerating cycle

3.Check current detection circuit at AC side.

1.Trouble of compressor (Compressor lock, etc.) : Replace compressor.

2.Defective cabling of compressor (Phase missing)

3.Phase-missing operation of power supply (3-phase model)

1.Compressor immediately stops even if restarted. : Check IPDU.

2.Phase-missing operation of power supply Check 3-phase power voltage and cables.

1.Check cables of CDB and IPDU.

2.Abnormal overload operation of refrigerating cycle

1.Check power phase order (Reversed phase)/phase missing.

2.Check outdoor P.C. board.

1.Check refrigerating cycle. (Gas leak)

2.Trouble of PMV

3.Check Td sensor.

1.Overload operation of refrigerating cycle

2.Check outdoor temperature sensor (TE).

3.Check outdoor CDB P.C. board.

1.Defective detection of position

2.Over-current protective circuit of outdoor fan driving unit operates.

3.Lock of outdoor fan

4.Check outdoor CDB P.C. board.

1.Inverter immediately stops even if restarted. : Compressor motor rare short

2.Check IPDU. : Cabling error

1.Position detection circuit operates even if operating compressor by removing 3P connector. : Replace IPDU.

1.Check outdoor temperature sensor (TD).

2.Check outdoor CDB P.C. board.

1.Check outdoor temperature sensor (TE/TS).

2.Check outdoor CDB P.C. board.

1.Check outdoor temperature sensor (TO).

2.Check outdoor CDB P.C. board.

For an error mode detected in outdoor unit, the fan operates because sub unit of a group operation does not communicate with the outdoor unit.

Image 51
Contents Split Type Contents Specifications Indoor UnitConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E RAV-SM560AT-E RAV-SM800AT-E Outdoor UnitRAV-SM1100AT-E RAV-SM1400AT-E Cooling Heating Operation Characteristic CurveCapacity Variation Ratio According to Temperature CoolingHeating AIR Ducting Work Static Pressure Characteristics of Each ModelRAV-SM1101BT-E Round duct RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-E DimensionConstruction Views External Views Indoor Unit Concealed Duct TypeRAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Outdoor unit Systematic Refrigerating Cycle DiagramIndoor Unit/Outdoor Unit Indoor unitRAV-SM801BT-E RAV-SM1001BT-E Second rps Fan Indoor Outdoor StrainerWiring Diagram ColorIdentification MCC-813 Color IdentificationFor P.C. Board MCC-1359MCC-1398 MCC-1438Parts name Type Specifications Specifications of Electrical PartsRAV-SM1100AT-E Piping Materials and Joints Used Safety During Installation/ServicingRefrigerant Piping Installation Refrigerant R410ANominal diameter Processing of Piping Materials1 Thicknesses of annealed copper pipes Thickness mm Outer diameter mm R410A R22Diameter Flare tool for Conventional flare toolR410A clutch type Clutch type Wing nut type R22 clutch type Clutch type Wing nut typeWrenches available on the market Nm kgfcmTools Required ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingBrazing of Pipes Materials for BrazingFlux Never use gas other than Nitrogen gas BrazingMain Sub master remote controller Weekly timer Indoor Unit ControlIndoor Control Circuit Control Specifications Outline of specifications RemarksRemote controller Outline of control Command Operation Heating AutoHeat Control temp C Operation Prohibited Case of wired remote controllerLast push priority CenterTa˚C Normal control RAV-SM561BT-E / SM801BT-E / SM1101BT Indoor Print Circuit BoardMCC-1402 SM1401BT-EFunction Connector Pin Specifications Remarks Indoor P.C. Board Optional Connector SpecificationsPulse Modulating Valve PMV control Discharge temperature release controlOutdoor Control Outline of Main ControlsMAX Heating operation Outdoor fan control Object SM560Allocations of fan tap revolutions Cooling operationCurrent release value shift control Short intermittent operation preventive controlHigh-pressure suppression TE control For SM800 Over-current preventive controlStart of heating operation Defrost controlOutdoor Controls Print Circuit BoardMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Before troubleshooting TroubleshootingSummary of Troubleshooting Wired remote controller typeError mode detected by indoor unit Check Code ListDiagnostic function Cause of operation Error mode detected by outdoor unitTimer Ready Wired remote Controller Check code Error mode detected by remote controller or network adapterIpdu side Error Mode Detected by LED on Outdoor P.C. BoardSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF CDB sideSW800 LED display in bit 1, bit 2, bit 3 OFF Check codeType a New Check Code/Present Check Code Central Control Side Troubleshooting Procedure for Each Check CodeE01 error/*99 error E09 error/*99 errorE04 error/04 error L09 error/46 error E10 error/CF errorE18 error/97 error *99 error E08, L03, L07, L08 error/ *96 error 99 errorL20 error/98 error L30 error/B6 errorB7 error Central controller F10 error 0C error P10 error/Ob errorP12 error/11 error P22 error/1A error Single phaseRAV-SM1100AT-E, SM1400AT-E F02 error/0d error P19 error/08 errorP26 error/14 error F01 error/0F errorH03 error/17 error P29 error/16 errorF06 error/18 error F04 error/19 errorF08 error/1b error H02 error/1d error L29 error/1C errorH01 error/1F error P03 error/1E errorP04 error/21 error Error Central controller E03 error Master indoor unit F29 error / 12 errorP31 error Sub indoor unit TD sensor Caracteristics-4 TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1Caracteristics-3 20 TE, TO, TS sensorCase Replacement of Service Indoor P.C. BoardMinimum requirements for item code R1 Readout of the setup data from EepromR2 Replacement of service P.C. board ContentsR3 Writing of the setup contents to Eeprom Memorandum for setup contents Item code table Example Type Item codeIndoor unit capacity Item code Wired remote controller Setup AT Local Site and OthersTest Run Setup on Remote Controller Setup to Select FunctionDescription At shipment Item No. DN table Selection of functionCabling and Setting of Remote Controller Control Setup methodOperation Monitor Function of Remote Controller Switch ContentsProcedure System example Calling of error historyGroup control operation RequirementNetwork Adapter Microcomputer Block DiagramNetwork Address Setup Switch SW01 LED Display SpecificationNetwork cable connection Communication Cable SpecificationsCommunication circuit Communication cable specifications Cable ConnectionProcedure Set the network address while the unit stops How to Set an Address NumberHow to set from the remote controller at indoor unit side How to set by the switch on the network adapter P.C. boardRequirement in Service Network address No. setup table SW01Address No Contents Remarks Address Setup Address SetupAddress setup procedure Automatic address example from unset address No miscabling Address Setup & Group ControlSystem configuration Only turning on source power supply Automatic completionSetup completes Status returns to the usual stop status Manual setting from remote controllerPush button if the unit stops To know the position of indoor unit body by addressPush and buttons simultaneously for 4 seconds or more Detachments Part name Procedure RemarksNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Attachment DetachmentPart name Procedure RemarksRequirement Part name ProcedureConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement 100101 102 103 104 Product 105106 107 108 109 110 Case of RAV-SM1400AT-E 111Case of RAV-SM1100AT-E Be sure to mount the propeller fan112 113 Location Exploded Views and Parts List114 Part Description115 904 901, 902, 903 35, 36, 37RAV-SM1001BT-E / SM1401BT-E 116RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-E 117118 Inverter119 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704120 21,22 16,17121 706122 Inverter 26,27 23,24 28,29123 TH Sensor