Toshiba RAV-SM801BT-E, RAV-SM1400AT-E, RAV-SM1101BT-E, RAV-SM1100AT-E Heating Auto, Operation

Page 35

No.

Item

 

Outline of specifications

 

 

 

Remarks

 

 

 

 

3

Room

1) Adjustment range Remote controller setup tem-

 

 

temperature

 

perature (°C)

 

 

 

 

 

 

 

 

 

 

 

 

control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL/

 

Heating

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRY

 

operation

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired type

18 to 29

 

18 to 29

 

18 to 29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) Using the item code 06, the setup temperature in

Shift of suction tempera-

 

 

 

heating operation can be compensated.

 

 

 

ture in heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup data

 

0

 

 

2

4

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp.

 

+0°C

 

+2°C

+4°C

 

+6°C

 

 

 

 

 

compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting at shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup data

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Automatic

1) Based on the difference between Ta and Ts, the

 

 

capacity control

 

operation frequency is instructed to the outdoor unit.

 

 

(GA control)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Air speed

1) Operation with (HH), (H), (L), or [AUTO] mode is

HH > H > L > LL

 

selection

 

performed by the command from the remote controller.

 

2)When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts.

<COOL>

Ta (˚C)

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

+3.0

 

 

 

 

 

 

 

 

 

 

 

HH

 

 

 

 

B

 

 

 

+2.5

 

 

 

 

 

 

 

 

 

 

(HH)

 

 

 

 

C

 

 

 

+2.0

 

 

 

 

 

 

 

 

 

 

H (HH)

 

 

 

 

D

 

 

 

+1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H (HH)

 

 

 

 

 

 

 

 

 

+1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

L(H)

 

 

 

 

+0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L(H)

 

 

 

 

 

 

 

 

Tsc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L(H)

 

 

 

F

 

 

-0.5

 

 

 

 

 

 

 

 

 

L(L)

 

 

 

G

 

 

 

 

 

 

 

 

Controlling operation in case when thermo of remote controller works is same as a case when thermo of the body works.

If the air speed has been changed once, it is not changed for 3 minutes. However when the air volume is exchanged, the air speed changes.

When cooling operation has started, the air speed selects a downward slope, that is, the high position.

If the temperature is just on the difference boundary, the air speed does not change.

Mode in the parentheses indicates one in automatic cooling operation.

33

Image 35
Contents Split Type Contents Concealed Duct Type SpecificationsIndoor Unit RAV-SM1101BT-E RAV-SM1401BT-E RAV-SM560AT-E RAV-SM800AT-E Outdoor UnitRAV-SM1100AT-E RAV-SM1400AT-E Cooling Heating Operation Characteristic CurveHeating Capacity Variation Ratio According to TemperatureCooling AIR Ducting Work Static Pressure Characteristics of Each ModelRAV-SM1101BT-E Round duct RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-E DimensionConstruction Views External Views Indoor Unit Concealed Duct TypeRAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Outdoor unit Systematic Refrigerating Cycle DiagramIndoor Unit/Outdoor Unit Indoor unitRAV-SM801BT-E RAV-SM1001BT-E Second rps Fan Indoor Outdoor StrainerIdentification Wiring DiagramColor MCC-813 Color IdentificationFor P.C. Board MCC-1359MCC-1398 MCC-1438Parts name Type Specifications Specifications of Electrical PartsRAV-SM1100AT-E Piping Materials and Joints Used Safety During Installation/ServicingRefrigerant Piping Installation Refrigerant R410ANominal diameter Processing of Piping Materials1 Thicknesses of annealed copper pipes Thickness mm Outer diameter mm R410A R22Diameter Flare tool for Conventional flare toolR410A clutch type Clutch type Wing nut type R22 clutch type Clutch type Wing nut typeWrenches available on the market Nm kgfcmGeneral tools Conventional tools can be used ToolsRequired Tools Recharging of Refrigerant 1 Configuration of refrigerant chargingFlux Brazing of PipesMaterials for Brazing Never use gas other than Nitrogen gas BrazingIndoor Control Circuit Main Sub master remote controller Weekly timerIndoor Unit Control Remote controller Outline of control Command Control SpecificationsOutline of specifications Remarks Operation Heating AutoHeat Control temp C Operation Prohibited Case of wired remote controllerLast push priority CenterTa˚C Normal control RAV-SM561BT-E / SM801BT-E / SM1101BT Indoor Print Circuit BoardMCC-1402 SM1401BT-EFunction Connector Pin Specifications Remarks Indoor P.C. Board Optional Connector SpecificationsPulse Modulating Valve PMV control Discharge temperature release controlOutdoor Control Outline of Main ControlsMAX Heating operation Outdoor fan control Object SM560Allocations of fan tap revolutions Cooling operationCurrent release value shift control Short intermittent operation preventive controlHigh-pressure suppression TE control For SM800 Over-current preventive controlStart of heating operation Defrost controlMCC-813 RAV-SM560AT-E Viewed from parts of P.C board Outdoor ControlsPrint Circuit Board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Before troubleshooting TroubleshootingSummary of Troubleshooting Wired remote controller typeError mode detected by indoor unit Check Code ListDiagnostic function Cause of operation Error mode detected by outdoor unitTimer Ready Wired remote Controller Check code Error mode detected by remote controller or network adapterIpdu side Error Mode Detected by LED on Outdoor P.C. BoardSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF CDB sideType a SW800 LED display in bit 1, bit 2, bit 3 OFFCheck code New Check Code/Present Check Code Central Control Side Troubleshooting Procedure for Each Check CodeE01 error/*99 error E09 error/*99 errorE04 error/04 error L09 error/46 error E10 error/CF errorE18 error/97 error *99 error E08, L03, L07, L08 error/ *96 error 99 errorB7 error Central controller L20 error/98 errorL30 error/B6 error F10 error 0C error P10 error/Ob errorP12 error/11 error RAV-SM1100AT-E, SM1400AT-E P22 error/1A errorSingle phase F02 error/0d error P19 error/08 errorP26 error/14 error F01 error/0F errorH03 error/17 error P29 error/16 errorF08 error/1b error F06 error/18 errorF04 error/19 error H02 error/1d error L29 error/1C errorH01 error/1F error P03 error/1E errorP04 error/21 error Error Central controller P31 error Sub indoor unit E03 error Master indoor unitF29 error / 12 error TD sensor Caracteristics-4 TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1Caracteristics-3 20 TE, TO, TS sensorCase Replacement of Service Indoor P.C. BoardMinimum requirements for item code R1 Readout of the setup data from EepromR2 Replacement of service P.C. board ContentsR3 Writing of the setup contents to Eeprom Indoor unit capacity Item code Memorandum for setup contents Item code table ExampleType Item code Wired remote controller Setup AT Local Site and OthersTest Run Setup on Remote Controller Setup to Select FunctionDescription At shipment Item No. DN table Selection of functionOperation Cabling and Setting of Remote Controller ControlSetup method Procedure Monitor Function of Remote Controller SwitchContents System example Calling of error historyGroup control operation RequirementNetwork Adapter Microcomputer Block DiagramNetwork Address Setup Switch SW01 LED Display SpecificationNetwork cable connection Communication Cable SpecificationsCommunication circuit Communication cable specifications Cable ConnectionProcedure Set the network address while the unit stops How to Set an Address NumberHow to set from the remote controller at indoor unit side How to set by the switch on the network adapter P.C. boardAddress No Requirement in ServiceNetwork address No. setup table SW01 Contents Remarks Address setup procedure Address SetupAddress Setup Automatic address example from unset address No miscabling Address Setup & Group ControlSystem configuration Only turning on source power supply Automatic completionSetup completes Status returns to the usual stop status Manual setting from remote controllerPush and buttons simultaneously for 4 seconds or more Push button if the unit stopsTo know the position of indoor unit body by address Detachments Part name Procedure RemarksNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Attachment DetachmentPart name Procedure RemarksRequirement Part name ProcedureConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement 100101 102 103 104 Product 105106 107 108 109 110 Case of RAV-SM1400AT-E 111Case of RAV-SM1100AT-E Be sure to mount the propeller fan112 113 Location Exploded Views and Parts List114 Part Description115 904 901, 902, 903 35, 36, 37RAV-SM1001BT-E / SM1401BT-E 116RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-E 117118 Inverter119 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704120 21,22 16,17121 706122 Inverter 26,27 23,24 28,29123 TH Sensor