Toshiba RAV-SM1100AT-E Outdoor fan control Object SM560, Allocations of fan tap revolutions

Page 44

5.Outdoor fan control (Object: SM560)

The outdoor fan is controlled by TO sensor and the revolutions frequency of the compressor (rps).

The outdoor fan is controlled by every 1 tap of DC fan control (8 taps). According to each operation mode, the fan is operated by selecting an outdoor fan operation tap in the following table based upon the conditions of TO sensor and the compressor operation (rps).

Allocations of fan tap revolutions

 

Tap

F1

F2

F3

F4

F5

F6

F7

F8

 

 

 

 

 

 

 

 

 

 

SM560

Revolutions per

960

870

870

870

750

700

540

390

minute (rpm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In cooling operation

Frequency of the

To 14

To 14

35 to MAX

compressor (rps)

 

 

 

 

 

 

 

TO 38°C

F7

F4

F3

 

 

 

 

TO < 38°C

F7

F5

F4

 

 

 

 

In heating operation

Frequency of the

To 14

To 14

35 to MAX

compressor (rps)

 

 

 

 

 

 

 

TO 5.5°C

F7

F6

F4

 

 

 

 

TO < 5.5°C

F6

F6

F3

 

 

 

 

6.Coil heating control

1)This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent slackness of the refrigerant inside of the compressor.

2)As usual, turn on power of the compressor for the specified time before a test run after installation, otherwise a trouble of the compressor may be caused. As same as a test run, it is recommended to turn on power of the compressor beforehand when starting operation after power of the compressor has been interrupted for a long time.

3)A judgment for electricity is performed by TD and TO sensors. If TO sensor is defective, a backup control is automatically performed by TE sensor. For a case of defective TO sensor, judge it with the outdoor LED display.

4)Coil heating is controlled by TD and TE sensor.

5)For every model, the power is turned off when TD is 30°C or more.

(In trouble of sensor)

TO [˚C]

 

18

No power-ON

Power-ON

15

 

condition

10

Continuous ON (L)

TD < 30˚C

8

 

 

 

Continuous ON (M)

* TD sensor is read in once per 15 minutes.

TO [˚C]

20

18

12

10

No power-ON

Continuous ON (L)

Continuous ON (M)

 

 

SM800

SM1100

SM1400

 

 

 

 

 

 

L

20W and equivalent

20W and equivalent

25W and equivalent

(Object: SM560)

 

 

 

 

M

40W and equivalent

40W and equivalent

50W and equivalent

 

 

 

 

 

TO [˚C]

10

9

4

3

2

1

No power-ON

Continuous ON (L)

Continuous ON (M)

Continuous ON (H)

SM560

L10W and equivalent

M 20W and equivalent

H 30W and equivalent

42

Image 44
Contents Split Type Contents Concealed Duct Type SpecificationsIndoor Unit RAV-SM1101BT-E RAV-SM1401BT-E Outdoor Unit RAV-SM560AT-E RAV-SM800AT-ERAV-SM1100AT-E RAV-SM1400AT-E Operation Characteristic Curve Cooling HeatingHeating Capacity Variation Ratio According to TemperatureCooling Static Pressure Characteristics of Each Model AIR Ducting WorkRAV-SM1101BT-E Round duct Dimension Construction Views External ViewsIndoor Unit Concealed Duct Type RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Systematic Refrigerating Cycle Diagram Indoor Unit/Outdoor UnitIndoor unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Strainer Second rps Fan Indoor OutdoorIdentification Wiring DiagramColor Color Identification MCC-813MCC-1359 For P.C. BoardMCC-1438 MCC-1398Specifications of Electrical Parts Parts name Type SpecificationsRAV-SM1100AT-E Safety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping Materials and Joints UsedProcessing of Piping Materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Nominal diameterFlare tool for Conventional flare tool R410A clutch type Clutch type Wing nut typeR22 clutch type Clutch type Wing nut type DiameterNm kgfcm Wrenches available on the marketGeneral tools Conventional tools can be used ToolsRequired Tools 1 Configuration of refrigerant charging Recharging of RefrigerantFlux Brazing of PipesMaterials for Brazing Brazing Never use gas other than Nitrogen gasIndoor Control Circuit Main Sub master remote controller Weekly timerIndoor Unit Control Remote controller Outline of control Command Control SpecificationsOutline of specifications Remarks Heating Auto OperationHeat Control temp C Case of wired remote controller Last push priorityCenter Operation ProhibitedTa˚C Normal control Indoor Print Circuit Board MCC-1402SM1401BT-E RAV-SM561BT-E / SM801BT-E / SM1101BTIndoor P.C. Board Optional Connector Specifications Function Connector Pin Specifications RemarksDischarge temperature release control Outdoor ControlOutline of Main Controls Pulse Modulating Valve PMV controlMAX Outdoor fan control Object SM560 Allocations of fan tap revolutionsCooling operation Heating operationShort intermittent operation preventive control High-pressure suppression TE control For SM800Over-current preventive control Current release value shift controlDefrost control Start of heating operationMCC-813 RAV-SM560AT-E Viewed from parts of P.C board Outdoor ControlsPrint Circuit Board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Troubleshooting Summary of TroubleshootingWired remote controller type Before troubleshootingCheck Code List Error mode detected by indoor unitError mode detected by outdoor unit Diagnostic function Cause of operationError mode detected by remote controller or network adapter Timer Ready Wired remote Controller Check codeError Mode Detected by LED on Outdoor P.C. Board SW800 LED display in bit 1, bit 2, bit 3, bit 4 OFFCDB side Ipdu sideType a SW800 LED display in bit 1, bit 2, bit 3 OFFCheck code Troubleshooting Procedure for Each Check Code E01 error/*99 errorE09 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E10 error/CF error E18 error/97 error *99 errorE08, L03, L07, L08 error/ *96 error 99 error L09 error/46 errorB7 error Central controller L20 error/98 errorL30 error/B6 error P10 error/Ob error F10 error 0C errorP12 error/11 error RAV-SM1100AT-E, SM1400AT-E P22 error/1A errorSingle phase P19 error/08 error F02 error/0d errorF01 error/0F error P26 error/14 errorP29 error/16 error H03 error/17 errorF08 error/1b error F06 error/18 errorF04 error/19 error L29 error/1C error H02 error/1d errorP03 error/1E error H01 error/1F errorP04 error/21 error Error Central controller P31 error Sub indoor unit E03 error Master indoor unitF29 error / 12 error TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1 Caracteristics-320 TE, TO, TS sensor TD sensor Caracteristics-4Replacement of Service Indoor P.C. Board CaseR1 Readout of the setup data from Eeprom R2 Replacement of service P.C. boardContents Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Indoor unit capacity Item code Memorandum for setup contents Item code table ExampleType Item code Setup AT Local Site and Others Test Run Setup on Remote ControllerSetup to Select Function Wired remote controllerItem No. DN table Selection of function Description At shipmentOperation Cabling and Setting of Remote Controller ControlSetup method Procedure Monitor Function of Remote Controller SwitchContents Calling of error history Group control operationRequirement System exampleMicrocomputer Block Diagram Network Address Setup Switch SW01LED Display Specification Network AdapterCommunication Cable Specifications Communication circuit Communication cable specificationsCable Connection Network cable connectionHow to Set an Address Number How to set from the remote controller at indoor unit sideHow to set by the switch on the network adapter P.C. board Procedure Set the network address while the unit stopsAddress No Requirement in ServiceNetwork address No. setup table SW01 Contents Remarks Address setup procedure Address SetupAddress Setup Address Setup & Group Control System configurationOnly turning on source power supply Automatic completion Automatic address example from unset address No miscablingManual setting from remote controller Setup completes Status returns to the usual stop statusPush and buttons simultaneously for 4 seconds or more Push button if the unit stopsTo know the position of indoor unit body by address Part name Procedure Remarks DetachmentsNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Detachment AttachmentProcedure Remarks Part namePart name Procedure RequirementConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex 100 Requirement101 102 103 104 105 Product106 107 108 109 110 111 Case of RAV-SM1100AT-EBe sure to mount the propeller fan Case of RAV-SM1400AT-E112 113 Exploded Views and Parts List 114Part Description Location904 901, 902, 903 35, 36, 37 115116 RAV-SM1001BT-E / SM1401BT-E117 RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-EInverter 118702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 11921,22 16,17 120706 121Inverter 26,27 23,24 28,29 122TH Sensor 123