Toshiba RAV-SM1100AT-E, RAV-SM1400AT-E, RAV-SM1101BT-E R3 Writing of the setup contents to Eeprom

Page 74
5
<REMOTE CONTROLLER>

r3 Writing of the setup contents to EEPROM

(The contents of EEPROM installed on the service P.C. board have been set up at shipment from the factory.)

1.Push SET , , and buttons of the remote controller at the same time for 4 seconds or more. 1 (Corresponded with No. in Remote controller )

In group operation control, the master indoor unit No. is displayed at the first time. (If the automatic address setup mode is interrupted in item 2. - a) - 2) in the previous page, the unit No. ALL is displayed.) In this time, the item code (DN) 10 is displayed. The fan of the selected indoor unit operates and the flap starts swinging if any.

2.Every pushing button, the indoor unit numbers in the group control are displayed successively. 2

Specify the indoor unit No. of which P.C. board has been replaced with a service P.C. board. (When the unit No. ALL is displayed, this operation cannot be performed.)

3.Using the set temperature / buttons, the item code (DN) can be moved up and down one by one. 3

4.First set a type and capacity of the indoor unit.

(Setting the type and capacity writes the data at shipment from the factory in EEPROM.)

1)Set the item code (DN) to 10. (As it is)

2)Using the timer time / buttons, set up a type. 4

(For example, 4-way air discharge cassette type is 0001) Refer to the attached table.

3)Push SET button. (OK when the display goes on.) 5

4)Using the set temperature / buttons, set 11 to the item code (DN).

5)Using the timer time / buttons, set the capacity.

(For example, 0012 for class 80) Refer to the attached table.

6)Push SET button. (OK when the display goes on.)

7)Push button to return the status to usual stop status. 6

(Approx. 1 minute is required to start handling of the remote controller.)

5.Next write the contents which have been set up at the local site such as the address setup in EEPROM. Repeat the above procedure 1. and 2.

6.Using the set temperature / buttons, set 01 to the item code (DN). (Setup of lighting time of filter sign)

7.The contents of the displayed setup data in this time should be agreed with the contents in the previous memorandum in r1.

1)If data disagree, change the displayed setup data to that in the previous memorandum by the timer time / buttons, and then push SET button. (OK when the display goes on.)

2)There is nothing to do when data agrees.

8.Using the set temperature / buttons, change the item code (DN).

As same as the above, check the contents of the setup data and then change them to data contents in the previous memorandum.

9. Then repeat the procedure 7. and 8.

10.After completion of setup, push button to return the status to the usual stop status. 6

(Approx. 1 minute is required to start handling of

 

 

 

the remote controller.)

 

SET DATA

 

* 01 to 9F are provided in the item code (DN).

 

 

 

UNIT No.

 

 

 

 

On the way of operation, DN No. may come out.

 

R.C. No.

 

 

 

 

When data has been changed by mistake and SET

 

 

 

button has been pushed, the data can be returned

4

 

 

to the data before change by pushing button if

 

 

the item code (DN) was not yet changed.

6

UNIT

3

 

1

 

 

 

SET CL

 

2

72

Image 74
Contents Split Type Contents Concealed Duct Type SpecificationsIndoor Unit RAV-SM1101BT-E RAV-SM1401BT-E Outdoor Unit RAV-SM560AT-E RAV-SM800AT-ERAV-SM1100AT-E RAV-SM1400AT-E Operation Characteristic Curve Cooling HeatingHeating Capacity Variation Ratio According to TemperatureCooling Static Pressure Characteristics of Each Model AIR Ducting WorkRAV-SM1101BT-E Round duct Indoor Unit Concealed Duct Type DimensionConstruction Views External Views RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Indoor unit Systematic Refrigerating Cycle DiagramIndoor Unit/Outdoor Unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Strainer Second rps Fan Indoor OutdoorIdentification Wiring DiagramColor Color Identification MCC-813MCC-1359 For P.C. BoardMCC-1438 MCC-1398Specifications of Electrical Parts Parts name Type SpecificationsRAV-SM1100AT-E Refrigerant R410A Safety During Installation/ServicingRefrigerant Piping Installation Piping Materials and Joints UsedOuter diameter mm R410A R22 Processing of Piping Materials1 Thicknesses of annealed copper pipes Thickness mm Nominal diameterR22 clutch type Clutch type Wing nut type Flare tool for Conventional flare toolR410A clutch type Clutch type Wing nut type DiameterNm kgfcm Wrenches available on the marketGeneral tools Conventional tools can be used ToolsRequired Tools 1 Configuration of refrigerant charging Recharging of RefrigerantFlux Brazing of PipesMaterials for Brazing Brazing Never use gas other than Nitrogen gasIndoor Control Circuit Main Sub master remote controller Weekly timerIndoor Unit Control Remote controller Outline of control Command Control SpecificationsOutline of specifications Remarks Heating Auto OperationHeat Control temp C Center Case of wired remote controllerLast push priority Operation ProhibitedTa˚C Normal control SM1401BT-E Indoor Print Circuit BoardMCC-1402 RAV-SM561BT-E / SM801BT-E / SM1101BTIndoor P.C. Board Optional Connector Specifications Function Connector Pin Specifications RemarksOutline of Main Controls Discharge temperature release controlOutdoor Control Pulse Modulating Valve PMV controlMAX Cooling operation Outdoor fan control Object SM560Allocations of fan tap revolutions Heating operationOver-current preventive control Short intermittent operation preventive controlHigh-pressure suppression TE control For SM800 Current release value shift controlDefrost control Start of heating operationMCC-813 RAV-SM560AT-E Viewed from parts of P.C board Outdoor ControlsPrint Circuit Board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Wired remote controller type TroubleshootingSummary of Troubleshooting Before troubleshootingCheck Code List Error mode detected by indoor unitError mode detected by outdoor unit Diagnostic function Cause of operationError mode detected by remote controller or network adapter Timer Ready Wired remote Controller Check codeCDB side Error Mode Detected by LED on Outdoor P.C. BoardSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF Ipdu sideType a SW800 LED display in bit 1, bit 2, bit 3 OFFCheck code E09 error/*99 error Troubleshooting Procedure for Each Check CodeE01 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E08, L03, L07, L08 error/ *96 error 99 error E10 error/CF errorE18 error/97 error *99 error L09 error/46 errorB7 error Central controller L20 error/98 errorL30 error/B6 error P10 error/Ob error F10 error 0C errorP12 error/11 error RAV-SM1100AT-E, SM1400AT-E P22 error/1A errorSingle phase P19 error/08 error F02 error/0d errorF01 error/0F error P26 error/14 errorP29 error/16 error H03 error/17 errorF08 error/1b error F06 error/18 errorF04 error/19 error L29 error/1C error H02 error/1d errorP03 error/1E error H01 error/1F errorP04 error/21 error Error Central controller P31 error Sub indoor unit E03 error Master indoor unitF29 error / 12 error 20 TE, TO, TS sensor TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1Caracteristics-3 TD sensor Caracteristics-4Replacement of Service Indoor P.C. Board CaseContents R1 Readout of the setup data from EepromR2 Replacement of service P.C. board Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Indoor unit capacity Item code Memorandum for setup contents Item code table ExampleType Item code Setup to Select Function Setup AT Local Site and OthersTest Run Setup on Remote Controller Wired remote controllerItem No. DN table Selection of function Description At shipmentOperation Cabling and Setting of Remote Controller ControlSetup method Procedure Monitor Function of Remote Controller SwitchContents Requirement Calling of error historyGroup control operation System exampleLED Display Specification Microcomputer Block DiagramNetwork Address Setup Switch SW01 Network AdapterCable Connection Communication Cable SpecificationsCommunication circuit Communication cable specifications Network cable connectionHow to set by the switch on the network adapter P.C. board How to Set an Address NumberHow to set from the remote controller at indoor unit side Procedure Set the network address while the unit stopsAddress No Requirement in ServiceNetwork address No. setup table SW01 Contents Remarks Address setup procedure Address SetupAddress Setup Only turning on source power supply Automatic completion Address Setup & Group ControlSystem configuration Automatic address example from unset address No miscablingManual setting from remote controller Setup completes Status returns to the usual stop statusPush and buttons simultaneously for 4 seconds or more Push button if the unit stopsTo know the position of indoor unit body by address Part name Procedure Remarks DetachmentsNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Detachment AttachmentProcedure Remarks Part namePart name Procedure RequirementConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex 100 Requirement101 102 103 104 105 Product106 107 108 109 110 Be sure to mount the propeller fan 111Case of RAV-SM1100AT-E Case of RAV-SM1400AT-E112 113 Part Description Exploded Views and Parts List114 Location904 901, 902, 903 35, 36, 37 115116 RAV-SM1001BT-E / SM1401BT-E117 RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-EInverter 118702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 11921,22 16,17 120706 121Inverter 26,27 23,24 28,29 122TH Sensor 123